- 4 -
Quick reference guide Programming
KEMPER KHS-Hygienic Flushing with Timer
Cold water Figure 686 03 007
Cold and hot water Figure 686 03 008
Note:
A KHS-Service- Mobile Figure 686 03 003 is always required for commissioning!
1. Set the number of valves
Only required for cold water Figure 686 03 007!
For Figure 686 03 008, the factory settings of
Flush interval: 48 h / Flush duration 180 sec.
immediately active.
After the first time they are switched on, all cold-water hygienic flushes show in the display:
in alternation
That is not a system error! The board is factory delivered for hot and cold water (2 valves delivered and
notices that only 1 valve is connected).
Take the following steps with the KHS-Service-Mobile
Factory settings subsequently active:
Flushing interval. 48 h / Flush duration 180 sec.
Cold water Figure 686 03 007
Menu item / Designation Key
press Display
1.
1 x switch-on key
Err1 / 48
2. 08 Unidirect
1x OK
Err1 / 48
3. 40 HygSpülng (Flushing)
1x OK
Err1 / 48
4. 00 ON/OFF
1x OK
_ SH _
5. 43 AnzVentil (Num. of valves)
1x OK
_ SH _
6.
43 AnzVentil OK? (Num. of valves
OK?) 1x
OK
_ SH _
7. 43 AnzVentil
1 2
1x
◄
2
8. 43 AnzVentil 1
2
1x
OK
1
9. 00 ON/OFF
1x OK
48
Err1
48h