- 5 -
2. Setting the flushing times
Factory setting: 180 sec.
Possible selection: 10 sec. – 999 sec.
Cold water Figure 686 03 007
Menu item / Designation Key
press
Display
1. 00 ON/OFF
1x OK
48
2. 41 IntSpZ V2 (Int. flush time)
1x OK
_ SH _
3. 41 IntSpZ V2 OK? (Int. flush time)
1x OK
180
4. 41 IntSpZ V2 __ (Int. flush time)
1x e.g. 120
120
5. 41 IntSpZ V2 120 (Int. flush time)
1x OK
120
6. 00 ON/OFF
1x OK
48
Cold and hot water Figure 686 03 008
Menu item / Designation Key
press
Display
1. 00 ON/OFF
1x OK
48
2. 41 IntSpZ V2 (Int. flush time)
1x OK
_ SH _
3. 41 IntSpZ V2 OK? (Int. flush time)
1x OK
180
4. 41 IntSpZ V2 __ (Int. flush time)
1x e.g. 120
120
5. 41 IntSpZ V2 120 (Int. flush time)
1x OK
120
6. 40 IntSpZ V1
1x OK
120
7. 40 IntSpZ V1 OK? (Int. flush time)
1x OK
180
8. 40 IntSpZ V1 (Int. flush time)
1x e.g. 60
60
9. 40 IntSpZ V1 60
1x OK
60
10. 00 ON/OFF
1x OK
48
3. Switching the mode (only if required!)
4. Setting the flushing interval
Cold water Figure 686 03 007
Cold and hot water Figure 686 03 008
Menu item / Designation Key
press Display
1. 00 ON/OFF
1x OK
48
2. 42 Interval Z
1x OK
_ SH _
3. 42 Interval Z OK? (time)
1x OK
48
4. 42 Interval Z __ (time)
1x e.g. 24
24
5. 42 Interval Z 24 (time)
1x OK
24
6. 00 ON/OFF
1x OK
24
Mode 1:
Mode 2:
4 h – 72 h
48 h – 336 h
Converting the mode on the
board:
(Factory setting: 48 h)
Key press, board MODE
=
Change: Mode 1 / 2
Check: LED 1 / 2