PRO and PURE specifications (control unit)
Power supply
230 (±10 %) V AC
Event-entry storage
100 000 units
Contamination level
3
Protection class
II with functional earth
Type
type 1.Y (according to EN 60730-1)
Overvoltage category
III
Altitude
max. 2000 MSL
LITE specifications (control unit)
Power supply
24 V DC
Event-entry storage
depends on BMS
Contamination level
3
Note!
Thermal disinfection!
•
If, during thermal disinfection, a flushing is carried out at 70 °C for 3 minutes on a KHS Hygiene Flush Box, this
must be precisely logged.
•
To do this on a KHS Hygiene Flush Box PURE or LITE, for temperature monitoring purposes, the reversible cover
must be opened and the trap cover removed so that the temperature of the exiting spray can be monitored.
•
To do this on a KHS Hygiene Flush Box PRO, for temperature monitoring purposes, the reversible cover must be
opened and a WLAN connection to the Hygiene Flush Box established. This allows the temperature to be monito-
red via the built-in flow and temperature sensor.
62
Note!
Hot potable water!
•
Hot water must only be connected if cold water is connected to the other port of the Hygiene Flush Box.
•
Hot water shall only be flushed to avoid stagnation in distribution pipes (water exchange of non-circulating water;
<3 litres).
©