Defining temperatures
Once a line type has been selected, define
the temperatures. With the “Temperature
flushing” line type, a start/stop tempera
-
ture must be given, together with the ma-
ximum duration of the water exchange.
Routine time
In this sample project, it is cold water. The
cold water temperature in winter could
always be below the starting tempera-
ture. Nevertheless, to prevent stagnation,
routine water exchanges can simulate
operation for the intended purpose. The
„Routine“ line type can be selected from
the drop-down list.
The desired weekday can also be selected
from a drop-down list. Click in the box
of the weekday in question to activate it
with a check mark.
Routine time
If there is no temperature flushing within 7
days, water exchange is guaranteed
through the „Routine time“ operating
mode. In the „Routine time“ operating
mode, the starting time, the duration and
the weekdays of the water exchange can be
defined.