K410068602008-00 / 09.2018
19
Main view
When all the devices have been added,
they are displayed in the main view, as
shown below. The individual devices can
then be configured in Device settings.
3.1.2.3 Device settings
In the "Device settings" submenu, the
individual Control System are logically
assigned to the integrated actuators
and sensors. The valve control type is
also determined.
Control type
Description
B valve
Terminal flushing valve, with several A valves hydraulically
preconnected.
A valve
Flushing valve which switches the water exchange for one line.
C valve
Terminal flushing valve for one line.
Safety device
Valve which protects a distribution line.
Only
measurement
Slave for the acquisition and long-term monitoring of sensor
values.
Configuration of the B Valve
Device selection
Control type
Valve
See Miscellaneous settings
Check to see if the antenna icon can always be
seen and if the LEDs light up green on all KHS
Mini Control System. Only then has a proper
connection been established.
When using A/B valve technology, always make sure that the B valve is
configured first. A valves can then be assigned to the B valve. The assignment
of the A valves is shown in the following. For information on valve technology,
please see Chapter 10.1.
Summary of Contents for KHS Mini Control System MASTER 2.0
Page 7: ...K410068602008 00 09 2018 7...