3.1.2.4 Operating modes
In the "Operating modes" submenu, programs and times are added to the actuators and
sensors.
Mode
Description
Time Control
Triggers a water exchange of defined duration at a certain
point in time.
Temperature control
Triggers a water exchange when a predefined start
temperature is reached, until a predefined stop temperature
is reached.
Volume control
Triggers a water exchange with a defined flush volume at a
certain point in time.
Backup
Backs up a distribution line by means of a water sensor in a
predefined time window.
Datalogging
Acquires sensor values in a predefined time window with a
predefined sampling rate.
Routine
Triggers a water exchange for a predefined duration or
quantity if a temperature control has not actuated for a
certain time.
If two or more valves are simultaneously opened in a drinking water
system, under certain circumstances pressure fluctuations or a large
pressure drop can occur in the system. For that reason, make sure
beforehand that the required flow pressure is continuously guaranteed at
all tapping points. You are recommended not to perform simultaneous
water exchanging measures.
If
the program switch is "Activated" (see Chapter
3.1.2.6), a query is presented during the operating
modes configuration to determine the program this
applies to (see right). The two mentioned flushing
programs can be switched using an external
manual switch. The electrical connection is shown
in Chapter 2.2.
Configuration of time control