K410068602008-00 / 09.2018
56
Routine time
In this sample project, it is cold water.
The cold water temperature in winter
could always be below the starting
temperature. Nevertheless, to prevent
stagnation, routine water exchanges can
simulate operation for the intended
purpose. The "Routine" line type can be
selected from the drop-down list.
The desired weekday can also be
selected from a drop-down list. Click in
the box of the weekday in question to
activate it with a check mark.
Routine time
If there is no temperature flushing within 7
days, water exchange is guaranteed
through the "Routine time" operating mode.
In the "Routine time" operating mode, the
starting time, the duration and the
weekdays of the water exchange can be
defined.
Routine duration
If there is no temperature flushing within
the configured interval, the water exchange
is guaranteed through the "Routine
duration" operating mode. To accomplish
that, the decisive interval (max. 168 h) and
the duration of the water exchange can be
stored in the "Routine duration" operating
mode.
Routine volume
If there is no temperature flushing within
the configured interval, the water exchange
is guaranteed through the "Routine volume"
operating mode. To accomplish this, the
decisive interval (max. 168 h), the volume
and the maximum flushing time of the water
exchange can be assigned to the "Routine
volume" operating mode.
Save settings
For the new parameters of the input
box to become effective, the settings
must by saved by clicking the
WRITE
TO CONTROL
button.