K410068602008-00 / 09.2018
8
2.2.1
Connection of the components
Terminal characters
Meaning
1
Flushing valve
–
Switching output 230V
2
L (+)
Flushing valve
–
Voltage output 230V
3
N (-)
Flushing valve
–
N
4
L (+)
Power supply
–
L1 230V
5
N (-)
Power supply
–
N
6
SW IN
External input - 230V (MASTER only)
7
PE
Protective earth conductor
–
PE
8
H
A CAN bus
–
High
9
L
A CAN bus
–
Low
10
GND
A CAN bus
–
Ground
11
H
B CAN bus
–
High
12
L
B CAN bus
–
Low
13
GND
B CAN bus
–
Ground
14
+ 5V
Flow measurement valve
–
Voltage output 5V
15
FLOW
Flow measurement valve
–
Flow input
17
GND
Flow measurement valve
–
Ground
18
Input 1 Pt1000
19
Input 1 Pt1000
20
Input 2 Pt1000
21
Input 2 Pt1000
22
IN
Free drain / water sensor (conductors interchangeable)
23
IN
Free drain / water sensor (conductors interchangeable)
24
Alarm relay
–
External voltage input
25
Monitoring of ext. voltage = Fault
26
Monitoring of ext. voltage = Operation
24
25
26
1
2 3
4
5
6
7
8
9
10
11
12
13
14
15
17
18
19
8
20
21
22
23