Kendrion Kuhnke Automation GmbH
Construction and Functionality
Kuhnke Vico
48
10.6 Applicable Standards and Limits
10.6.1 EMC standards
EMC immunity to:
Generic standard EN 61000-6-2:2011 -06
Electromagnetic compatibility (EMC) – Part 6-2: Generic standards - Immunity for industrial
environments
ESD: EN 61000-4-2
8 kV under air discharge (severity 3),
4 kV under contact discharge (severity 2)
HF irradiation (housing): EN 61000-4-3
80 MHz … 1000 MHz, 10 V/m, 80% AM (1 kHz)
1.4 GHz ... 2.0 GHz, 3 V/m, 80% AM (1 kHz)
2 GHz ... 2.7 GHz, 1 V/m, 80% AM (1 kHz)
HF carried by wire: EN 61000-4-6
150 kHz … 80 MHz, 10 V, 80% AM (1 kHz)
EN 61000-4-4:
Burst, severity 3
EN 61000-4-5:
Surge, severity 3
The high energy of every pulse occurring in surge mode requires an
adequate external wiring by some means of lightning protection such as
lightning stroke current and surge arresters.
EMC noise emission to:
Generic standard DIN EN 61000-6-4: Emission standard for industrial environments (Class A)