background image

17

VENT CONNECTIONS TO BLOWER ASSEMBLY

Figure 21 shows the optimal placement of the 2" to 3" or 3" to 4" reducer;
however, the vent can be reduced at any point in the vent system as long
as the maximum vent length is not exceeded.

FIGURE 21.

VENTING AND INSTALLATION

Plan the layout of the vent system from the vent termination to the water
heater considering all of the 90° and 45° elbows plus the number of feet
of pipe that would be needed to install the total vent system. The water
heater must be vented to the outdoors as described in these instructions.
DO NOT connect this water heater to an existing vent or chimney. It must
be vented separately from all other appliances. Nonmetallic vent may be
used if it has “Heat Deflection Temperature” (HDT@66 psi) or 455 kPa of
at least 157°F or 69°C. Typical nonmetallic vent materials meeting this
requirement are: PVC (Schedule 40, ASTM D-1785), Coex Cellular Core
(Schedule 40, ASTM F-441), CPVC (Schedule 40, ASTM D-2846), ABS
(Schedule 40, ASTM D-2661). The fittings, other than the supplied Vent
Termination should be equivalent to the following: PVC (Schedule 40,
DWV, ASTM D-2665), CPVC (Schedule 40, DWV, ASTM F-438), ABS
(Schedule 40 DWV, ASTM D-2661).

The cement used should be as recommended by the vent pipe
manufacturer. See the instructions on pages 20 and 21 for the proper
method of cutting and cementing the PVC pipe and fittings.

The unit may be vented horizontally through a wall or vertically through
the roof.  Pipe runs must be adequately supported along both vertical
and horizontal runs as follows:

• For Schedule 40, 2" PVC, ABS, Coex Cellular Core vent pipe: Every

3 feet (0.9 m).

• For Schedule 40, 3" PVC, ABS, Coex Cellular Core vent pipe: Every

3.5 feet (1.1 m).

• For Schedule 40, 4" PVC, ABS, Coex Cellular Core vent pipe: Every

4 feet (1.2 m).

• For Schedule 40, 2" CPVC vent pipe: Every 5 feet (1.5 m).

• For Schedule 40, 3" CPVC vent pipe: Every 6 feet (1.8 m).

• For Schedule 40, 4" CPVC vent pipe: Every 6.5 feet (2.0 m).

It is imperative that the first hanger (or support) be located on the horizontal
run immediately adjacent to the first 90-degree elbow from the vertical
rise. Support method used should isolate the vent pipe from the floor
joists or other structural members to prevent the transmission of noise
and vibration.  Do not support, pin, or otherwise secure the venting
system in a way that restricts the normal thermal expansion and
contraction of the chosen venting material.

If the water heater is being installed as a replacement for an existing
power vented heater in pre-existing venting, a thorough inspection of
the existing venting system must be performed prior to any installation
work.  Verify that the correct material as detailed above has been
used, and that the minimum or maximum vent lengths and terminal
location as detailed in this manual have been met.  Carefully inspect the
entire venting system for any signs of cracks or fractures, particularly
at the joints between elbows and other fittings and the straight runs of
vent pipe.  Check the system for signs of sagging or other stresses in
the joints as a result of misalignment of any components in the system.
If any of these conditions are found, they must be corrected in
accordance with the venting instructions in this manual before
completing the installation and putting the water heater into service.

Except where instructed in this manual, the mixing of 2", 3" and 4" vent
pipe is NOT ALLOWED.  If 2" pipe is to be used, then a 2" to 3" bell reducer
is recommended.  Figure 21 shows the recommended location for the
bell reducer.  If the bell reducer is located at the rubber boot on the
blower assembly, then a short section of 3" vent pipe needs to be
installed in the rubber boot for proper connection of the 2" to 3" bell
reducer. That length can be the minimum length required for the connection.

If 4" pipe is to be used, then a 3" to 4" bell reducer is recommended.
Figure 21 shows the recommended location for the bell reducer.  If the
bell reducer is located at the rubber boot on the blower assembly, then
a short section of 3" vent pipe needs to be installed in the rubber boot
for proper connection of the 3" to 4" bell reducer.   That length can be
the minimum length required for the connection.

The water heaters covered by this manual are supplied with a 2" Schedule
40 PVC 22.5° Vent Terminal.  If you decide to vent with 3" or 4" pipe, a
Schedule 40 DWV 45° Vent Terminal must be used.  For your convenience,
we have included a screen for both 3" and 4" Vent Terminals.

The vent piping should be connected to the blower with a rubber
adapter and secured with hose clamps. The adapter and clamps are
provided with the heater.

Even though the flue gas temperature leaving the blower is between
140°F (69°C) and 175°F (79°C), some installations will have water
vapor condense in the vent piping. If this occurs, then adequate means
of draining and disposing of the condensate needs to be made by
 the installer.

CONDENSATION

Condensate formation does not occur in all installations of power vented
water heaters, but should be protected against on installations where it
can form in the venting system. Condensation in the venting system of
power vented water heaters is dependent upon installation conditions
including, but not limited to ambient temperature and humidity of installation
location, ambient temperature and humidity of venting space, vent
discharge and slope, and product usage. In certain conditions, installations
in unconditioned space or having long horizontal or vertical vent runs
may accumulate condensate. In these conditions, the vent pipe should
be sloped downward away from the blower assembly 1/4" (6.4 mm) per
five feet (1.5 m) of pipe but not more than 1 1/2" (3.8 cm) in the total vent
length. If the vent piping is vented level or sloped upwards away from
the blower assembly, then adequate means for draining and disposing
of the condensate needs to be made by the installer (if condensate is
detected). If you have condensate, then a 3/8" drain hose can be connected
to the built-in drain port of the rubber boot on the blower assembly. For
your convenience, the rubber boot is supplied with a removable cap on
the built-in drain port. Prior to operating the water heater, make sure the
removable cap is installed on the drain port (if a drain hose is not needed).

MAXIMUM VENT LENGTHS

40,000 BTU Units:

For 2" Venting, the maximum equivalent feet of pipe allowed
is 40 feet (12.2 m).

 This does not include the supplied vent termination

for the water heater.  For the 2" venting, one 90° elbow is approximately
equal to 5 feet (1.5 m).  One 45° elbow is approximately equal to 2.5
feet (0.8 m).  It is recommended that at least 2 feet (0.6 m) of spacing
be used in between all 45° elbows and all 90°elbows.

For 3" Venting, the maximum equivalent feet of pipe allowed
is 120 feet (36.6 m). 

This does not include the Vent Termination (supplied

locally) for the water heater.  For the 3" venting, one 90° elbow is
approximately equal to 5 feet (1.5 m).  One 45° elbow is approximately
equal to 2.5 feet (0.8 m).  It is recommended that at least 2 feet (0.6 m)
of spacing be used in between all 45° elbows and all 90°elbows.

For 4" Venting, the maximum equivalent feet of pipe allowed
is 160 feet (48.8 m). 

This does not include the Vent Termination (supplied

locally) for the water heater.  For the 4" venting, one 90° elbow is
approximately equal to 8 feet (2.4 m).  One 45° elbow is approximately
equal to 4 feet (1.2 m).  It is recommended that at least 2 feet (0.6 m) of
spacing be used in between all 45° elbows and all 90°elbows.

Summary of Contents for ECONOMIZER 6 153.332070

Page 1: ...lon Nat 153 332060 40 Gallon LP 153 332070 50 Gallon LP For Your Safety ANODORANTISADDEDTOTHEGASUSEDBYTHISWATERHEATER Safety Instructions Installation Operation Care and Maintenance Troubleshooting Parts List THE ECONOMIZER 6 GAS WATER HEATER POWER VENTED GAS MODELS WITH HOT SURFACE IGNITION Si no puede leer o entender el inglés y necesita el manual instructivo y o etiquetas en español puede obten...

Page 2: ...u and others who install use or service this water heater All safety messages will generally tell you about the type of hazard what can happen if you do not follow the safety message and how to avoid the risk of injury IMPORTANT DEFINITIONS Gas Supplier The Natural Gas or Propane Utility or service who supplies gas for utilization by the gas burning appliances within this application The gas suppl...

Page 3: ...3 SAFETY PRECAUTIONS ...

Page 4: ...mbly Installation 15 16 Vent Connections to Blower Assembly 17 Venting and Installation 17 Condensation 17 Maximum Vent Lengths 17 Venting 18 Vent Terminal Installation 18 19 Vertical Vent Through Roof 19 Vertical Vent Termination Restrictions 19 Vent Pipe Preparation 20 21 OPERATING INSTRUCTIONS 22 23 Lighting and Operating Label 22 Temperature Regulation 23 FOR YOUR INFORMATION 24 25 Start Up Co...

Page 5: ...e manual that you must read and be aware of All warnings and all instructions are essential to the proper operation of the water heater and your safety Since we cannot put everything on the first few pages READ THE ENTIRE MANUAL BEFORE ATTEMPTINGTOINSTALLOROPERATETHEWATERHEATER 2 The installation must conform with these instructions and the local code authority having jurisdiction In the absence o...

Page 6: ... LESS AND AVAILABLE IN 28 711 mm DIAMETER FOR WATER HEATERS HAVING A DIAMETER 26 660 mm OR LESS Basic Tools You may or may not need all these tools depending on your type of installation These tools can be purchased at your local Sears Store Pipe Wrenches 2 14 356 mm Screwdriver Tin Snips 6 1 82 m Tape or Folding Ruler Garden Hose Drill Pipe Dope or Teflon Tape Additional Tools Needed When Sweat S...

Page 7: ...alve U Ground Joint Union V Drip Leg Sediment Trap W Drain Valve X Gas Valve Thermostat Y Drain Pan Z Air Intake Screen Base Pan AA Inner Door BB Outer Door CC HSI Burner Assembly DD Air Intake Screen Blower Assembly EE FV Sensor Assembly NATURAL HOT SURFACE IGNITER MAIN BURNER HOT SURFACE IGNITOR SENSOR PROPANE HOT SURFACE IGNITER MAIN BURNER TEMPERATURE INDICATORS TEMPERATUREADJUSTMENT BUTTONS H...

Page 8: ...can be lifted off after any screw or other attached devices are removed Make sure existing vent complies with maximum and minimum vent lengths on page17 6 If you have copper piping to the water heater the two copper water pipes can be cut with a hacksaw approximately four inches away from where they connect to the water heater see Figure 6 This will avoid cutting off pipes too short Additional cut...

Page 9: ...ger an alarm or turn off the incoming water to the water heater when leakage is detected Sensors mounted in the drain pan that turn off the water supply to the entire home when water is detected in the drain pan Water supply shut off devices that activate based on the water pressure differential between the cold water and hot water pipes connected to the water heater Devices that will turn off the...

Page 10: ...r meets or exceeds the National Appliance Energy Conservation Act standards with respect to insulation and standby loss requirements making an insulation blanket unnecessary Should you choose to apply an insulation blanket to this heater you should follow these instructions For identification of components mentioned below see Figure 1 Failure to follow these instructions can restrict the air flow ...

Page 11: ...re inch per 4 000 Btu per hour 5 5 cm2 kW of total input rating of all equipment in the enclosure see Figure 12 FIGURE12 2 When communicating with the outdoors through vertical ducts each opening shall have a minimum free area of 1 square inch per 4 000 Btu per hour 5 5 cm2 kW of total input rating of all equipment in the enclosure see Figure 13 3 When communicating with the outdoors through horiz...

Page 12: ...r tubing to an adapter before attaching the adapter to the cold water inlet connection Do not solder the cold water supply line directly to the cold water inlet It will harm the dip tube and damage the tank Look at the top cover of the water heater The water outlet is marked HOT Put two or three turns of teflon tape around the threaded end of the threaded to sweat coupling and around both ends of ...

Page 13: ...pressure not to exceed the marked hydrostatic working pressure of the water heater 150 psi 1 035 kPa and a discharge capacity not less than the water heater input rate as shown on the model rating plate For safe operation of the water heater the relief valve must not be removed from its designated opening nor plugged The temperature pressure relief valve must be installed directly into the fitting...

Page 14: ...plosion from leaking gas If the main gas line Shut off serving all gas appliances is used also turn off the gas at each appliance Leave all gas appliances shut off until the water heater installation is complete A gas line of sufficient size must be run to the water heater Consult thecurrenteditionofNationalFuelGasCodeANSIZ223 1 NFPA54and your gas supplier concerning pipe size There must be A read...

Page 15: ...ll be either a tee fitting with a capped nipple in the bottom outlet or other device recognized as an effective sediment trap If a tee fitting is used it shall be installed in conformance with one of the methods of installation shown in Figures 18 and 19 FIGURE20 FILLING THE WATER HEATER Never use this water heater unless it is completely full of water To prevent damage to the tank the tank must b...

Page 16: ...heater operates on 110 120 Vac therefore a grounded outlet must be within reach of the six 6 foot 1 8 m flexible power cord supplied with the unit see Figure 1 The power cord supplied may be used only where local codes permit If local codes do not permit the use of a flexible power supply cord a Make sure the unit is unplugged from wall outlet Remove screws and open panel on front of control box b...

Page 17: ... vent pipe needs to be installed in the rubber boot for proper connection of the 2 to 3 bell reducer Thatlengthcanbetheminimumlengthrequiredfortheconnection If 4 pipe is to be used then a 3 to 4 bell reducer is recommended Figure 21 shows the recommended location for the bell reducer If the bell reducer is located at the rubber boot on the blower assembly then a short section of 3 vent pipe needs ...

Page 18: ...s Required clearances from combustible materialsmustbeprovidedinaccordancewithinformationinthismanual under FACTS TO CONSIDER ABOUT THE LOCATION and VENT TERMINALINSTALLATIONS and with the National Fuel Gas Code and local codes VENT TERMINAL INSTALLATION 1 After the point of termination has been determined use the cover plate as a template to mark the hole for the vent pipe to insert throughthewal...

Page 19: ... wall flange is supplied for decorative purposes only and is not a requirement for the vent termination if not needed by the installer VERTICAL VENT THROUGH ROOF This unit is approved for venting through the roof with the type vent terminal that is included with the unit A proper flashing or BOOT should be used to seal the pipe where it exits the roof The total vent system should not exceed that w...

Page 20: ...hes 15 2 cm and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleaning PVC or CPVC surfaces Achemical cleaner such as MEK may be used CEMENT The cement should be a bodied cement of approximately 500 to 1600 centipoise viscosity containing 10 20 by weight vi...

Page 21: ...tance and make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristlebrush ThisprocesssoftensandpreparesthePVCorCPVCfor thesolventcementingstep Movequicklyandwithouthesitationtothe cementingprocedurewhilethesurfacesarestillwetwithprimer E Application of solvent cement Applythesolventcementeven...

Page 22: ...uttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off all electric power to the appliance if service is to be performed BEFORE OPERATING ENTIRE SYSTEM MUST BE FILLED WITH WATERANDAIR PURGED FROMALL LINES 1 STOP Read the safety information above on this label 2 Set...

Page 23: ...e shall be used at the hot water taps used by these people or at the water heater Mixing valves are available at plumbing supply or hardware stores see Figure 15 Follow manufacturer s instructions for installation of the valves Before changing the factory setting on the thermostat read the Temperature Regulation section in this manual see Figure 26 Never allow small children to use a hot water tap...

Page 24: ...ssure frequent cut offs the effects of water hammer among others have installed devices such as pressure reducing valves check valves back flow preventers etc to control these types of problems When these devices are not equipped with an internal by pass and no other measures are taken the devices cause the water system to be closed As water is heated it expands thermal expansion and closed system...

Page 25: ... faucet located farthest away be opened for several minutes before any electrical appliances which are connected to the hot water system are used such as a dishwasher or washing machine If hydrogen gas is present there will probably be an unusual sound similar to air escaping through the pipe as the hot water faucet is opened There must be no smoking or open flame near the faucet at the time it is...

Page 26: ...en that will filter and prevent lint build up on the bottom of the flame arrestor of this heater To prevent the lint build up on the arrestor the lint screen must be installed on the Base Pan with the arrows pointing upwards as shown in Figure 29 If theAir Intake Screen is missing from this heater please contact Sears Service Center for a replacement part FIGURE29 AT LEAST ONCE EVERY SIX MONTHS A ...

Page 27: ...ter inlet valve to the water heater 3 OPENanearbyhotwaterfaucetandleaveopentoallowfor draining 4 Connectahosetothedrainvalveandterminatetoanadequatedrain 5 OPEN the water heater drain valve to allow for tank draining NOTE If the water heater is going to be shut down and drained for an extended period the drain valve should be left open with hose connected allowing water to terminate to an adequate...

Page 28: ...valve may be leaking at the tank fitting H Combustion products contain water vapor which can condense on the cooler surfaces of the tank Droplets form and drip onto the burner or run on the floor This is common at the time of start up after installation and when incoming water is cold I Water in the water heater bottom or on the floor may be from condensation looseconnections orthereliefvalve DONO...

Page 29: ...ce ignitor not positioned correctly 3 Low voltage to the water heater 4 Electric polarity to unit is incorrect test and correct Problem in the gas valve driver circuit 1 Turn power to the water heater off for 10 seconds and the back on 2 Replace gas control valve Problem with the internal circuit 1 Turn power to the water heater off for 10 seconds and then back on 2 Replace gas control valve Probl...

Page 30: ...30 These guidelines should be utilized by a qualified service agent When calling for service notify the service agent that this is a Flammable Vapor Ignition Resistant Product TROUBLESHOOTING GUIDELINES ...

Page 31: ...4316 9004316 9004316 9004316 11 Air Intake Screen Base Pan 9003406 9003406 9003406 9003406 12 InletTube 9003447 9002547 9003447 9002547 13 Gas Control Valve 9005962 9005962 9005963 9005963 14 Drain Valve 9002402 9002402 9002402 9002402 15 Drain Valve Washer 9001584 9001584 9001584 9001584 16 Outer Door 9005966 9005966 9005966 9005966 17 Anode Rod 9003972 9003891 9003972 9003891 18 Temperature Pres...

Page 32: ...help prolong the life of your new purchase for years to come Purchase your Master Protection Agreement today Some limitations and exclusions apply For prices and additional information call 1 800 827 6655 SEARSINSTALLATIONSERVICE For Sears professional installation of home appliances garage door openers water heaters and other major home items in the U S A call 1 800 4 MY HOME For in home major br...

Reviews: