9
†®TEFLON is a registered trademark of E.I. Dupont De Nemours and Company.
■
1/2" IPS pipe is recommended.
■
3/8" approved aluminum or copper tubing is acceptable for
lengths under 20 ft. (6.1 m) if local codes and gas supplier
permit.
■
If you are using Natural gas, do not use copper tubing.
■
Lengths over 20 ft. (6.1 m) should use larger tubing and
a different size adapter fitting.
■
If your dryer has been converted to use LP gas, 3/8" LP
compatible copper tubing can be used. If the total length of
the supply line is more than 20 ft. (6.1 m), use larger pipe.
NOTE:
Pipe-joint compounds that resist the action of LP gas
must be used. Do not use TEFLON
®†
tape.
■
Must include shut-off valve
In the U.S.A.:
An individual manual shut-off valve must be installed within
six (6) ft. (1.8 m) of the dryer in accordance with the National
Fuel Gas Code, ANSI Z223.1. The location should be easy to
reach for opening and closing.
In Canada:
An individual manual shut-off valve must be installed in
accordance with the B149.1, Natural Gas and Propane
Installation Code. It is recommended that an individual
manual shutoff valve be installed within six (6) ft. (1.8 m) of
the dryer. The location should be easy to reach for opening
and closing.
GAS SUPPLY CONNECTION REQUIREMENTS
■
Use an elbow and a 3/8" flare x 3/8" NPT adapter fitting
between the flexible gas connector and the dryer gas pipe,
as needed to avoid kinking.
■
Use only pipe-joint compound. Do not use TEFLON
®†
tape.
■
This dryer must be connected to the gas supply line with a
listed flexible gas connector that complies with the standard
for connectors for gas appliances, ANSI Z21.24.
BURNER INPUT REQUIREMENTS
Elevations above 10,000 ft. (3,048 m):
■
When installed above 10,000 ft. (3,048 m) a 4% reduction of
the burner Btu rating shown on the model/serial number plate
is required for each 1,000 ft. (305 m) increase in elevation.
Gas supply pressure testing
■
The dryer must be disconnected from the gas supply piping
system during pressure testing at pressures greater than 1/2 psi.
DRYER GAS PIPE
■
The gas pipe that comes out through the rear of your dryer
has a 3/8" male pipe thread.
A. 1/2" NPT gas supply line
B. 3/8" NPT dryer pipe
NOTE:
If the dryer is mounted on a pedestal, the gas pipe height
must be an additional 10" (254 mm) or 15.5" (394 mm) from the
floor, depending on the pedestal model. For a garage installation,
the gas pipe height must be an additional 18" (460 mm) from
the floor.
4"
(102 mm)
A
B
1"
(25 mm)
INSTALL LEVELING LEGS
Prepare dryer for leveling legs
1.
To avoid damaging floor, use a large flat piece of cardboard from
dryer carton; place under entire dryer. Firmly grasp dryer body
(not console panel) and gently lay dryer down on cardboard.
IMPORTANT:
If laying dryer on its back, use the cardboard
corner posts the dryer was packed with to avoid damaging the
back of the dryer. Lay the dryer on its side if you do not have the
cardboard corner posts the dryer was packed with.
2.
Screw in leveling legs
Models with riser:
Using a wrench, screw legs into cabinet until foot flange touches
the riser. Foot is fully installed when bottom of foot
is approximately 1/2" (13 mm) from bottom of the riser.
Models without riser:
Using a wrench and tape measure, screw legs into leg holes
until bottom of foot is approximately 1
3
/
8
" (35 mm) from
bottom of dryer.
Now stand the dryer on its legs. Slide the dryer until it is
close to its final location. Leave enough room for electrical
connection and to connect the exhaust vent.
NOTE:
Refer to Dryer Dimensions in the Location Requirements.
Flange
Models with riser
Models without riser
Flange
Summary of Contents for W10562379A
Page 2: ...2 DRYER SAFETY ...
Page 3: ...3 IMPORTANT When discarding or storing your old clothes dryer remove the door ...
Page 18: ...18 SEGURIDAD DE LA SECADORA ...
Page 19: ...19 IMPORTANTE Cuando descarte o guarde su vieja secadora de ropa quítele la puerta ...
Page 36: ...36 ...
Page 51: ...NOTES ...