background image

Man-1078_Sigma_CP_22 
 

     Page 12 of 24

 

 
 

8B

9. Sounder circuit wiring 

Whether  using  standard  or  T  series  control  panels,  all  sounders  must  be  of  the  polarised  type.  If  non-
polarised sounders are used the control panel will permanently show a fault condition. See table 6 on page 7 

for a list of compatible sounder types. 

Sounder  circuits  are  monitored  for  open  and  short  circuit  faults  by  placing  a  10K  end  of  line  monitoring 

resistor across the last device on the circuit. 

 

Sounder  circuits  must  be  wired  as  a  single,  radial  circuit  with  no  spurs  or  T  junctions  to  enable  the 
monitoring circuit to work correctly. 

A maximum of 1.6 Amps is available for powering sounders with a maximum load of 0.41 Amps on any one 

circuit. 

 

 

 

 

 
 
 
 
 
 

9B

10. Connection to remote control terminals 

Some  functions  of  the  control  panel  can  be  controlled  externally  from  the  panel  if  required.  Operation  of 

these  inputs 

must  be  restricted  by  an  access  level  2  control

  as  defined  in  EN54-2  These  are 

abbreviated at the terminals block as follows: 

 

a)

 

Remote 0 V supply - ROV 

b)

 

Silence Alarm – SIL 

c)

 

Sound Alarm – AL 

d)

 

Fault – FLT 

e)

 

Reset – RST 

 

To activate these inputs, the remote 0 Volt (R0V) supply must be connected to the input via a normally open 

switch or contact and via a resistance of no greater than 100 ohms. 

All of the remote control inputs are non-latching. 

 

 

 
 

 

 

 

 
 

 

 
 
 

 

R

O

V

   S

IL

   A

L

   F

L

T

   R

S

T

TOTAL RESISTANCE LESS THAN 100 OHMS

SILENCE ALARM SWITCH

SOUND ALARM SWITCH

Figure 7 -  

Example connections to remote control inputs

+

   

   

 

-

S

1

Figure 6 . -   Sounder circuit wiring

10K end of line 

resistor

POLARISED

SOUNDER

IN

OUT

+

IN

+

OUT

_

_

POLARISED

SOUNDER

IN

OUT

+

IN

+

OUT

_

_

Summary of Contents for Sigma CP K Series

Page 1: ......

Page 2: ...contacts 13 12B13 Connection to Repeater panels 13 13B14 Connection to Ancillary boards 14 14B15 Connection to 8 way Sounder boards 14 15B16 Panel operation 15 16B17 Configuration options 16 17B18 Wa...

Page 3: ...operate upon fire condition These are to be used for local control and signalling 1B2 Safety and mounting Suppliers of articles for use at work are required under section 6 of the Health and Safety a...

Page 4: ...t with electronic fuse Dedicated sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp total load over UallU circuits Zonal sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp to...

Page 5: ...IONISATION Apollo 32 55000 217 SERIES 65 IONISATION Apollo 32 55000 218 SERIES 65 IONISATION Apollo 32 55000 219 SERIES 65 IONISATION Apollo 32 55000 220 SERIES 65 IONISATION Apollo 32 55000 315 SERI...

Page 6: ...connected to a zone this number should be limited to 32 to ensure that a short or open circuit on the wiring does not prevent the indication of a fire alarm from more than 32 fire detectors and or cal...

Page 7: ...470R KC For standard 4 wire systems CX 470 OHM CALL POINT Fulleon NCP T CALL POINT Nittan ELECTRONICS FREE BASES ALL Note LCMU Line Continuity Monitoring Device part number K1406 allows call points mo...

Page 8: ...system diagram which should be supplied by the detector manufacturer The power rating of the end of line resistor will be dependent upon the Zone classification rating Gas class this will be specified...

Page 9: ...the three way terminal block on the left hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box t...

Page 10: ...ntrol panels from time to time and when this is done the operating software of the unit is updated The software revision can be located on the main processor by removing the plate holding the PCB from...

Page 11: ...pplied fitted to the control panels terminals and placing them across the last device that is wired to the zone circuit Detection zone circuits must be wired as a single radial circuit with no spurs o...

Page 12: ...n any one circuit 9B10 Connection to remote control terminals Some functions of the control panel can be controlled externally from the panel if required Operation of these inputs must be restricted b...

Page 13: ...of a fire condition on any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not o...

Page 14: ...s containing boards labelled S4XXA or above They will not work with panels containing boards without an alpha suffix 14B15 Connection to 8 way Sounder boards Sounder boards connect via a 2 core cable...

Page 15: ...to light indicating a fault on the wiring to the sounder circuits 30B16 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the charging circuit will cau...

Page 16: ...mber appears Pressing the Enter button will cause the Test and Zone Fault LEDs to illuminate indicating the zones which are in test mode Disablements and zone tests are cleared by repeating the sequen...

Page 17: ...r will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM ANOTHER ZONE Silenced sounders will not re sound upon further zone activations 2A TRE...

Page 18: ...NOT SOUND ALARMS 94 ZONE 4 DOES NOT SOUND ALARMS 95 ZONE 5 DOES NOT SOUND ALARMS 96 ZONE 6 DOES NOT SOUND ALARMS 97 ZONE 7 DOES NOT SOUND ALARMS 98 ZONE 8 DOES NOT SOUND ALARMS A1 ZONE 1 ANY ALARM DEL...

Page 19: ...the control panel a number of internal indicators are visible with the front cover removed as follows 39B20 1 Mains fail Indicates that the 230V AC supply is not present and the system is running on s...

Page 20: ...ime until over rated circuit trips fuse to identify troublesome circuit 46B20 8 S1 fault and S2 fault Indicates a short or open circuit on sounder outputs Remove wiring and refit end of line resistors...

Page 21: ...panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity see table 2 for battery size required for each model The maximum current drawn from the batteries when the main...

Page 22: ...ire alarm system in accordance with BS5839 Part 1 2002 will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately Shoul...

Page 23: ...by a flashing zone indicator and Pu on the 7 segment display Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM...

Page 24: ...DOES NOT SOUND ALARMS 99 A1 ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously before an alarm is generated A2 ZONE 2 ANY ALARM DELAYED A3 ZONE 3 ANY ALARM DELAYED A4 ZON...

Reviews: