Man-1078_Sigma_CP_22
Page 12 of 24
8B
9. Sounder circuit wiring
Whether using standard or T series control panels, all sounders must be of the polarised type. If non-
polarised sounders are used the control panel will permanently show a fault condition. See table 6 on page 7
for a list of compatible sounder types.
Sounder circuits are monitored for open and short circuit faults by placing a 10K end of line monitoring
resistor across the last device on the circuit.
Sounder circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the
monitoring circuit to work correctly.
A maximum of 1.6 Amps is available for powering sounders with a maximum load of 0.41 Amps on any one
circuit.
9B
10. Connection to remote control terminals
Some functions of the control panel can be controlled externally from the panel if required. Operation of
these inputs
must be restricted by an access level 2 control
as defined in EN54-2 These are
abbreviated at the terminals block as follows:
a)
Remote 0 V supply - ROV
b)
Silence Alarm – SIL
c)
Sound Alarm – AL
d)
Fault – FLT
e)
Reset – RST
To activate these inputs, the remote 0 Volt (R0V) supply must be connected to the input via a normally open
switch or contact and via a resistance of no greater than 100 ohms.
All of the remote control inputs are non-latching.
R
O
V
S
IL
A
L
F
L
T
R
S
T
TOTAL RESISTANCE LESS THAN 100 OHMS
SILENCE ALARM SWITCH
SOUND ALARM SWITCH
Figure 7 -
Example connections to remote control inputs
+
-
S
1
Figure 6 . - Sounder circuit wiring
10K end of line
resistor
POLARISED
SOUNDER
IN
OUT
+
IN
+
OUT
_
_
POLARISED
SOUNDER
IN
OUT
+
IN
+
OUT
_
_
Summary of Contents for Sigma CP K Series
Page 1: ......