background image

Man-1078_Sigma_CP_22 
 

     Page 15 of 24

 

15B

16. Panel operation 

 

24B

16.1 Normal condition 

Under normal conditions, control panels will have only the green, 

Power On LED lit.  

 

25B

16.2 Fire condition 

Upon receipt of a fire condition by activation of a detector or call point, the 

Common Fire indicator will light 

and the zonal 

Fire indicators will flash at around 2Hz. 

The fire and local fire relays will also operate and signal any systems to which they are connected. 

Any sounders connected to the sounder circuits will operate in common, zonal or 2-stage mode as selected 

by configuration options 10 to 12 (see table 8). 

 

26B

16.3 Silence/sound alarms 

The 

Silence/Sound  alarm  button  can  only  be  operated  at  access  level  two  which  means  that  the  Enable 

Control key must be inserted.  

To silence the sounders, insert the Enable Control key and press the Silence/Sound alarm button.  

When the sounders have been silenced, the Zone Fire LEDs will change from flashing to a steady state. 

Pressing  the 

Silence/Sound  alarm  whilst  the  control  panel  is  in  this  silenced  condition,  will  cause  the 

sounders to operate again. 
The sounders can be toggled on and off with the 

Silence/Sound alarm button as required. 

 

27B

16.4 Reset 

To reset the panel, insert the Enable key then press the Reset button. 

 

28B

16.5 Zone fault 

Removal of a detector from its base or a fault on any of the zone wiring will cause the 

Fault LED and Zone 

Fault LEDs to light indicating the zone in which the fault has occurred. 

 

29B

16.6 Sounder fault 

A fault on the wiring to sounder circuits will cause the 

Fault and Sounder Fault LEDs to light indicating a fault 

on the wiring to the sounder circuits. 

 

30B

16.7 Power fault 

Failure of the mains power, disconnection of the standby battery or high impedance in the charging circuit 

will  cause  the 

Fault  and  Power  Fault  LEDs  to  light  indicating  an  abnormality  in  the  power  supply  to  the 

control panel. 
 

31B

16.8 System fault 

The 

System Fault LED will light if the configuration memory has not been set or has become corrupt.  

 

32B

16.9 Lamp test 

All LED indicators can be tested at any time by pressing the 

Lamp Test button. The Enable Control key does 

not need to be inserted to test the indicators. 

The buzzer can be silenced at any time by pressing the 

Buzzer Silence button. The enable key does not need 

to be inserted to silence the buzzer. 

 

33B

16.10 Disablements 

It is possible to disable parts of the system. This may be required if there are works going on in a building 
which may cause the fire alarm system to operate in error. 

 

34B

16.10.1 Disable zones 

To disable zones, the 

Enable Control key should be inserted and the mode button pressed until “d” appears 

in the first of the two seven segment LED displays. The 

Select button should then be pressed to select the 

number  of  the  zone  which  is  to  be  disabled  in  the  second  of  the  two  seven  segment  displays.  Once  the 
desired zone is displayed, the enter button should be pressed to confirm the disablement. 

The 

Disable LED will light and the Zone Fault LED will light for each disabled zone. 

 

A disabled zone is shown on the seven segment display as ‘dx.’ (where x is the zone number from 1-8).  

If the ‘x’ is flashing, it means that there are activated devices in that zone and re-enabling it will put the 

control panel into the fire condition.  
The panel should be Reset before enabling any zone with a flashing “dx.” Indication 

Summary of Contents for Sigma CP K Series

Page 1: ......

Page 2: ...contacts 13 12B13 Connection to Repeater panels 13 13B14 Connection to Ancillary boards 14 14B15 Connection to 8 way Sounder boards 14 15B16 Panel operation 15 16B17 Configuration options 16 17B18 Wa...

Page 3: ...operate upon fire condition These are to be used for local control and signalling 1B2 Safety and mounting Suppliers of articles for use at work are required under section 6 of the Health and Safety a...

Page 4: ...t with electronic fuse Dedicated sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp total load over UallU circuits Zonal sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp to...

Page 5: ...IONISATION Apollo 32 55000 217 SERIES 65 IONISATION Apollo 32 55000 218 SERIES 65 IONISATION Apollo 32 55000 219 SERIES 65 IONISATION Apollo 32 55000 220 SERIES 65 IONISATION Apollo 32 55000 315 SERI...

Page 6: ...connected to a zone this number should be limited to 32 to ensure that a short or open circuit on the wiring does not prevent the indication of a fire alarm from more than 32 fire detectors and or cal...

Page 7: ...470R KC For standard 4 wire systems CX 470 OHM CALL POINT Fulleon NCP T CALL POINT Nittan ELECTRONICS FREE BASES ALL Note LCMU Line Continuity Monitoring Device part number K1406 allows call points mo...

Page 8: ...system diagram which should be supplied by the detector manufacturer The power rating of the end of line resistor will be dependent upon the Zone classification rating Gas class this will be specified...

Page 9: ...the three way terminal block on the left hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box t...

Page 10: ...ntrol panels from time to time and when this is done the operating software of the unit is updated The software revision can be located on the main processor by removing the plate holding the PCB from...

Page 11: ...pplied fitted to the control panels terminals and placing them across the last device that is wired to the zone circuit Detection zone circuits must be wired as a single radial circuit with no spurs o...

Page 12: ...n any one circuit 9B10 Connection to remote control terminals Some functions of the control panel can be controlled externally from the panel if required Operation of these inputs must be restricted b...

Page 13: ...of a fire condition on any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not o...

Page 14: ...s containing boards labelled S4XXA or above They will not work with panels containing boards without an alpha suffix 14B15 Connection to 8 way Sounder boards Sounder boards connect via a 2 core cable...

Page 15: ...to light indicating a fault on the wiring to the sounder circuits 30B16 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the charging circuit will cau...

Page 16: ...mber appears Pressing the Enter button will cause the Test and Zone Fault LEDs to illuminate indicating the zones which are in test mode Disablements and zone tests are cleared by repeating the sequen...

Page 17: ...r will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM ANOTHER ZONE Silenced sounders will not re sound upon further zone activations 2A TRE...

Page 18: ...NOT SOUND ALARMS 94 ZONE 4 DOES NOT SOUND ALARMS 95 ZONE 5 DOES NOT SOUND ALARMS 96 ZONE 6 DOES NOT SOUND ALARMS 97 ZONE 7 DOES NOT SOUND ALARMS 98 ZONE 8 DOES NOT SOUND ALARMS A1 ZONE 1 ANY ALARM DEL...

Page 19: ...the control panel a number of internal indicators are visible with the front cover removed as follows 39B20 1 Mains fail Indicates that the 230V AC supply is not present and the system is running on s...

Page 20: ...ime until over rated circuit trips fuse to identify troublesome circuit 46B20 8 S1 fault and S2 fault Indicates a short or open circuit on sounder outputs Remove wiring and refit end of line resistors...

Page 21: ...panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity see table 2 for battery size required for each model The maximum current drawn from the batteries when the main...

Page 22: ...ire alarm system in accordance with BS5839 Part 1 2002 will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately Shoul...

Page 23: ...by a flashing zone indicator and Pu on the 7 segment display Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM...

Page 24: ...DOES NOT SOUND ALARMS 99 A1 ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously before an alarm is generated A2 ZONE 2 ANY ALARM DELAYED A3 ZONE 3 ANY ALARM DELAYED A4 ZON...

Reviews: