Man-1078_Sigma_CP_22
Page 15 of 24
15B
16. Panel operation
24B
16.1 Normal condition
Under normal conditions, control panels will have only the green,
Power On LED lit.
25B
16.2 Fire condition
Upon receipt of a fire condition by activation of a detector or call point, the
Common Fire indicator will light
and the zonal
Fire indicators will flash at around 2Hz.
The fire and local fire relays will also operate and signal any systems to which they are connected.
Any sounders connected to the sounder circuits will operate in common, zonal or 2-stage mode as selected
by configuration options 10 to 12 (see table 8).
26B
16.3 Silence/sound alarms
The
Silence/Sound alarm button can only be operated at access level two which means that the Enable
Control key must be inserted.
To silence the sounders, insert the Enable Control key and press the Silence/Sound alarm button.
When the sounders have been silenced, the Zone Fire LEDs will change from flashing to a steady state.
Pressing the
Silence/Sound alarm whilst the control panel is in this silenced condition, will cause the
sounders to operate again.
The sounders can be toggled on and off with the
Silence/Sound alarm button as required.
27B
16.4 Reset
To reset the panel, insert the Enable key then press the Reset button.
28B
16.5 Zone fault
Removal of a detector from its base or a fault on any of the zone wiring will cause the
Fault LED and Zone
Fault LEDs to light indicating the zone in which the fault has occurred.
29B
16.6 Sounder fault
A fault on the wiring to sounder circuits will cause the
Fault and Sounder Fault LEDs to light indicating a fault
on the wiring to the sounder circuits.
30B
16.7 Power fault
Failure of the mains power, disconnection of the standby battery or high impedance in the charging circuit
will cause the
Fault and Power Fault LEDs to light indicating an abnormality in the power supply to the
control panel.
31B
16.8 System fault
The
System Fault LED will light if the configuration memory has not been set or has become corrupt.
32B
16.9 Lamp test
All LED indicators can be tested at any time by pressing the
Lamp Test button. The Enable Control key does
not need to be inserted to test the indicators.
The buzzer can be silenced at any time by pressing the
Buzzer Silence button. The enable key does not need
to be inserted to silence the buzzer.
33B
16.10 Disablements
It is possible to disable parts of the system. This may be required if there are works going on in a building
which may cause the fire alarm system to operate in error.
34B
16.10.1 Disable zones
To disable zones, the
Enable Control key should be inserted and the mode button pressed until “d” appears
in the first of the two seven segment LED displays. The
Select button should then be pressed to select the
number of the zone which is to be disabled in the second of the two seven segment displays. Once the
desired zone is displayed, the enter button should be pressed to confirm the disablement.
The
Disable LED will light and the Zone Fault LED will light for each disabled zone.
A disabled zone is shown on the seven segment display as ‘dx.’ (where x is the zone number from 1-8).
If the ‘x’ is flashing, it means that there are activated devices in that zone and re-enabling it will put the
control panel into the fire condition.
The panel should be Reset before enabling any zone with a flashing “dx.” Indication
Summary of Contents for Sigma CP K Series
Page 1: ......