background image

Man-1078_Sigma_CP_22 
 

     Page 16 of 24

 

Note: The flashing “dx” indicator will only appear on panels with software version 

sigma_CP 214.hex

 and 

higher produced after July 2012.

 

 
 

35B

16.10.2 Disable sounders 

To disable sounder outputs, press the mode button to select “db” on the  seven segment display. Pressing 

enter will disable all sounders and cause the 

Disable and Sounder Fault LEDs to light. 

 

 
 

36B

16.10.3 Activate delays 

To activate delays on zones as set in configuration options 31 to 48, press the mode button until Ad appears 

on the seven segment LED display. When the enter button is pressed any zones that are set as delayed will 

have their alarm outputs delayed by the time set in configuration options 00 to 09. 

 

37B

16.10.4 Disable fault contact 

The fault relay can be disabled by selecting configuration option 22.  

 

38B

16.11 Test mode 

Fire  alarm  systems  must  be  tested  regularly  to  ensure  that  they  are  functioning  correctly.  The  Sigma  CP 

range of panels enable the system to be tested single handed  by using a test mode. When in test mode, 
activation of a fire alarm will be automatically reset after a few seconds to eliminate the need to return to 

the control panel to reset after every activation. 

Test mode is entered in a similar way to disablements. With the 

Enable Control key inserted, press the Mode 

button until “t” appears in the first of the seven segment displays. Then press the 

Select button until the 

required  zone  number  appears.  Pressing  the 

Enter  button  will  cause  the  Test  and  Zone  Fault  LEDs  to 

illuminate indicating the zones which are in test mode. 
Disablements and zone tests are cleared by repeating the sequence that is used to select them, i.e. the "db" 

function (for example) toggles between sounders disabled and sounders enabled. 

16B

17. Configuration options 

The  Sigma  CP  range  of  control  panels  has  many  configuration  options  which  can  be  set  at  the  time  of 
commissioning  to  suit  the  requirements  of  the  installation.  These  options  are  normally  set  once  and  will 

rarely  need  to  change.  The  configuration  options  are  only  available  at  access  level  3.  To  access  level  3, 

CAREFULLY  slide  the  Write  Enable  switch  (located  behind  the  aperture  in  the  panel  plate)  to  the  right 

position using a small screwdriver or similar. When the panel is at access level 3, the buzzer will “pip” three 

times every few seconds as an indication that it is at this access level. 

 
 

 

 

 

 

 

 

 

 
 

 
 

 
Configuration  options  are  simple  to  enter  using  the  codes  in  table  8  below.  When  the  control  panel  is  at 
access level 3, the sub-text of the 

Mode and Select buttons is used to enter a number using tens (+10) and 

units (+1).  
When  the  required  code  number  is  displayed,  pressing  the  enter  button  will  cause  the  dot  on  the  units, 

seven segment display to flash. This indicates that a configuration option has been set.  
To review which configuration options have been set previously, simply scroll through numbers 1 to 99, A1 

to A8, C1 to C8 and E1 to E8 and those with a flashing dot indicate which options have been set. 

Figure 8 – Access level 3 (Write enable) enable switch location 

WRITE ENABLE SWITCH

Summary of Contents for Sigma CP K Series

Page 1: ......

Page 2: ...contacts 13 12B13 Connection to Repeater panels 13 13B14 Connection to Ancillary boards 14 14B15 Connection to 8 way Sounder boards 14 15B16 Panel operation 15 16B17 Configuration options 16 17B18 Wa...

Page 3: ...operate upon fire condition These are to be used for local control and signalling 1B2 Safety and mounting Suppliers of articles for use at work are required under section 6 of the Health and Safety a...

Page 4: ...t with electronic fuse Dedicated sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp total load over UallU circuits Zonal sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp to...

Page 5: ...IONISATION Apollo 32 55000 217 SERIES 65 IONISATION Apollo 32 55000 218 SERIES 65 IONISATION Apollo 32 55000 219 SERIES 65 IONISATION Apollo 32 55000 220 SERIES 65 IONISATION Apollo 32 55000 315 SERI...

Page 6: ...connected to a zone this number should be limited to 32 to ensure that a short or open circuit on the wiring does not prevent the indication of a fire alarm from more than 32 fire detectors and or cal...

Page 7: ...470R KC For standard 4 wire systems CX 470 OHM CALL POINT Fulleon NCP T CALL POINT Nittan ELECTRONICS FREE BASES ALL Note LCMU Line Continuity Monitoring Device part number K1406 allows call points mo...

Page 8: ...system diagram which should be supplied by the detector manufacturer The power rating of the end of line resistor will be dependent upon the Zone classification rating Gas class this will be specified...

Page 9: ...the three way terminal block on the left hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box t...

Page 10: ...ntrol panels from time to time and when this is done the operating software of the unit is updated The software revision can be located on the main processor by removing the plate holding the PCB from...

Page 11: ...pplied fitted to the control panels terminals and placing them across the last device that is wired to the zone circuit Detection zone circuits must be wired as a single radial circuit with no spurs o...

Page 12: ...n any one circuit 9B10 Connection to remote control terminals Some functions of the control panel can be controlled externally from the panel if required Operation of these inputs must be restricted b...

Page 13: ...of a fire condition on any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not o...

Page 14: ...s containing boards labelled S4XXA or above They will not work with panels containing boards without an alpha suffix 14B15 Connection to 8 way Sounder boards Sounder boards connect via a 2 core cable...

Page 15: ...to light indicating a fault on the wiring to the sounder circuits 30B16 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the charging circuit will cau...

Page 16: ...mber appears Pressing the Enter button will cause the Test and Zone Fault LEDs to illuminate indicating the zones which are in test mode Disablements and zone tests are cleared by repeating the sequen...

Page 17: ...r will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM ANOTHER ZONE Silenced sounders will not re sound upon further zone activations 2A TRE...

Page 18: ...NOT SOUND ALARMS 94 ZONE 4 DOES NOT SOUND ALARMS 95 ZONE 5 DOES NOT SOUND ALARMS 96 ZONE 6 DOES NOT SOUND ALARMS 97 ZONE 7 DOES NOT SOUND ALARMS 98 ZONE 8 DOES NOT SOUND ALARMS A1 ZONE 1 ANY ALARM DEL...

Page 19: ...the control panel a number of internal indicators are visible with the front cover removed as follows 39B20 1 Mains fail Indicates that the 230V AC supply is not present and the system is running on s...

Page 20: ...ime until over rated circuit trips fuse to identify troublesome circuit 46B20 8 S1 fault and S2 fault Indicates a short or open circuit on sounder outputs Remove wiring and refit end of line resistors...

Page 21: ...panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity see table 2 for battery size required for each model The maximum current drawn from the batteries when the main...

Page 22: ...ire alarm system in accordance with BS5839 Part 1 2002 will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately Shoul...

Page 23: ...by a flashing zone indicator and Pu on the 7 segment display Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM...

Page 24: ...DOES NOT SOUND ALARMS 99 A1 ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously before an alarm is generated A2 ZONE 2 ANY ALARM DELAYED A3 ZONE 3 ANY ALARM DELAYED A4 ZON...

Reviews: