background image

Man-1078_Sigma_CP_22 
 

     Page 17 of 24

 

 

 

 

 

 

 

 

 

 
 
 

Table 8 – Configuration codes

 

 

CODE  

FUNCTION 

COMMENTS 

00 

SOUNDER DELAY TIME = 30 SECONDS 

Sets the time delay before sounders operate in combination with 
configuration codes 31 to 48 and access level 2 function AD. 
 

01 

SOUNDER DELAY TIME = 1 MINUTE 

02 

SOUNDER DELAY TIME = 2 MINUTES 

03 

SOUNDER DELAY TIME = 3 MINUTES 

04 

SOUNDER DELAY TIME = 4 MINUTES 

05 

SOUNDER DELAY TIME = 5 MINUTES 

06 

SOUNDER DELAY TIME = 6 MINUTES 

07 

SOUNDER DELAY TIME = 7 MINUTES 

08 

SOUNDER DELAY TIME = 8 MINUTES 

09 

SOUNDER DELAY TIME = 9 MINUTES 

10 

COMMON ALARM MODE (default) 

All sounders operate upon any fire condition 

11 

TWO-STAGE ALARM MODE 

Continuous sounders in activated zone, pulsing elsewhere 

12 

ZONED ALARM MODE 

Only sounders connected to zone in alarm operate 

 

 

 

21* 

DISABLE FIRE BUZZER 

Buzzer will not operate on fire condition 

22* 

DISABLE FAULT OUTPUT 

Fault relay will not operate except upon total power failure 

23 

DISABLE EARTH FAULT MONITORING 

Connection of fire alarm wiring will not announce a fault  

24 

PULSED REMOTE CONTROL OUTPUT 

Aux 24V supply pulses 1 sec on/1 sec off 

25 

ENABLE SOUNDERS ON DETECTION CIRCUITS 

Set as default if panel is two wire “T” series (detectors and call 
points on same cables) 

26 

DISABLE FIRE OUTPUT 

Fire relay will not operate upon any alarm 

27 

REMOVE AUX 24 UPON PANEL RESET 

24V supply switches off for about 5 seconds when panel is reset 

28 

INDICATE CALL POINT ACTIVATION 

Activation  of  a  call  point  with  a  270R  resistance  fitted  is 
indicated  by  a  flashing  zone  indicator  and  “Pu”  on  the  7 
segment display. Activation of a detector will be indicated by a 
steady zone indicator and nothing on the 7 segment display. 

29 

DO NOT RE-SOUND ALARMS FROM ANOTHER ZONE 

Silenced  sounders  will  not  re-sound  upon  further  zone 
activations 

2A 

TREAT CALL POINT ALARM AS DETECTOR ALARM 

When  this  option  is  active,  the  panel  does  not  distinguish 
between detector alarms and call point alarms (v215 onward) 

 

 

 

31 

ZONE 1 ALARM FROM DETECTOR DELAYED 

Sounder outputs will be delayed by time set at options 
0-9 when selected zone(s) triggered by detector only. 
Note:  Access  level  2  function  Ad  must  be  set  for  this  to  take 
effect. 

32 

ZONE 2 ALARM FROM DETECTOR DELAYED

 

33 

ZONE 3 ALARM FROM DETECTOR DELAYED

 

34 

ZONE 4 ALARM FROM DETECTOR DELAYED

 

35 

ZONE 5 ALARM FROM DETECTOR DELAYED

 

36 

ZONE 6 ALARM FROM DETECTOR DELAYED

 

37 

ZONE 7 ALARM FROM DETECTOR DELAYED

 

38 

ZONE 8 ALARM FROM DETECTOR DELAYED

 

 

 

 

41 

ZONE 1 ALARM FROM CALL POINT DELAYED 

Sounder outputs will be delayed by time set at options 
0-9 when selected zone(s) triggered by call point only. 
Note  access  level  2  function  Ad  must  be  set  for  this  to  take 
effect. 

42 

ZONE 2 ALARM FROM CALL POINT DELAYED

 

43 

ZONE 3 ALARM FROM CALL POINT DELAYED

 

44 

ZONE 4 ALARM FROM CALL POINT DELAYED

 

45 

ZONE 5 ALARM FROM CALL POINT DELAYED

 

46 

ZONE 6 ALARM FROM CALL POINT DELAYED

 

47 

ZONE 7 ALARM FROM CALL POINT DELAYED

 

48 

ZONE 8 ALARM FROM CALL POINT DELAYED

 

 

 

 

51 

COINCIDENCE ZONE 1 

Zone  contributes  to  ancillary  board  coincidence  O/P.  Any 
number of zones can be selected to contribute. 

52 

COINCIDENCE ZONE 2 

53 

COINCIDENCE ZONE 3 

54 

COINCIDENCE ZONE 4 

55 

COINCIDENCE ZONE 5 

56 

COINCIDENCE ZONE 6 

57 

COINCIDENCE ZONE 7 

58 

COINCIDENCE ZONE 8 

 

 

 

DOT 

FLASHING

NO DOT

ZONE 1 I.S. BARRIER 

OPTION SET

ZONE 1 I.S. BARRIER 

OPTION NOT SET

Figure 9 – Example display showing option set and not set. 

 

Summary of Contents for Sigma CP K Series

Page 1: ......

Page 2: ...contacts 13 12B13 Connection to Repeater panels 13 13B14 Connection to Ancillary boards 14 14B15 Connection to 8 way Sounder boards 14 15B16 Panel operation 15 16B17 Configuration options 16 17B18 Wa...

Page 3: ...operate upon fire condition These are to be used for local control and signalling 1B2 Safety and mounting Suppliers of articles for use at work are required under section 6 of the Health and Safety a...

Page 4: ...t with electronic fuse Dedicated sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp total load over UallU circuits Zonal sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp to...

Page 5: ...IONISATION Apollo 32 55000 217 SERIES 65 IONISATION Apollo 32 55000 218 SERIES 65 IONISATION Apollo 32 55000 219 SERIES 65 IONISATION Apollo 32 55000 220 SERIES 65 IONISATION Apollo 32 55000 315 SERI...

Page 6: ...connected to a zone this number should be limited to 32 to ensure that a short or open circuit on the wiring does not prevent the indication of a fire alarm from more than 32 fire detectors and or cal...

Page 7: ...470R KC For standard 4 wire systems CX 470 OHM CALL POINT Fulleon NCP T CALL POINT Nittan ELECTRONICS FREE BASES ALL Note LCMU Line Continuity Monitoring Device part number K1406 allows call points mo...

Page 8: ...system diagram which should be supplied by the detector manufacturer The power rating of the end of line resistor will be dependent upon the Zone classification rating Gas class this will be specified...

Page 9: ...the three way terminal block on the left hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box t...

Page 10: ...ntrol panels from time to time and when this is done the operating software of the unit is updated The software revision can be located on the main processor by removing the plate holding the PCB from...

Page 11: ...pplied fitted to the control panels terminals and placing them across the last device that is wired to the zone circuit Detection zone circuits must be wired as a single radial circuit with no spurs o...

Page 12: ...n any one circuit 9B10 Connection to remote control terminals Some functions of the control panel can be controlled externally from the panel if required Operation of these inputs must be restricted b...

Page 13: ...of a fire condition on any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not o...

Page 14: ...s containing boards labelled S4XXA or above They will not work with panels containing boards without an alpha suffix 14B15 Connection to 8 way Sounder boards Sounder boards connect via a 2 core cable...

Page 15: ...to light indicating a fault on the wiring to the sounder circuits 30B16 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the charging circuit will cau...

Page 16: ...mber appears Pressing the Enter button will cause the Test and Zone Fault LEDs to illuminate indicating the zones which are in test mode Disablements and zone tests are cleared by repeating the sequen...

Page 17: ...r will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM ANOTHER ZONE Silenced sounders will not re sound upon further zone activations 2A TRE...

Page 18: ...NOT SOUND ALARMS 94 ZONE 4 DOES NOT SOUND ALARMS 95 ZONE 5 DOES NOT SOUND ALARMS 96 ZONE 6 DOES NOT SOUND ALARMS 97 ZONE 7 DOES NOT SOUND ALARMS 98 ZONE 8 DOES NOT SOUND ALARMS A1 ZONE 1 ANY ALARM DEL...

Page 19: ...the control panel a number of internal indicators are visible with the front cover removed as follows 39B20 1 Mains fail Indicates that the 230V AC supply is not present and the system is running on s...

Page 20: ...ime until over rated circuit trips fuse to identify troublesome circuit 46B20 8 S1 fault and S2 fault Indicates a short or open circuit on sounder outputs Remove wiring and refit end of line resistors...

Page 21: ...panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity see table 2 for battery size required for each model The maximum current drawn from the batteries when the main...

Page 22: ...ire alarm system in accordance with BS5839 Part 1 2002 will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately Shoul...

Page 23: ...by a flashing zone indicator and Pu on the 7 segment display Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM...

Page 24: ...DOES NOT SOUND ALARMS 99 A1 ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously before an alarm is generated A2 ZONE 2 ANY ALARM DELAYED A3 ZONE 3 ANY ALARM DELAYED A4 ZON...

Reviews: