background image

Man-1078_Sigma_CP_22 
 

     Page 19 of 24

 

Once  the  required  configuration  options  have  been  set,  the  Write  enable  switch 

must

  be  returned  to  its 

normal position to the right. The General fault indicator will remain lit if the Write enable switch is not turned 

off. 

17B

18. Watchdog reset switch 

If  for  any  reason  the  microprocessor  in  the  control  panel  fails  to  carry  out  its  operation  correctly  it  will 

attempt to restart itself. This process is called a “watchdog” and the control panel must record and indicate 

these events. 

If a watchdog event occurs, the control panel will show the FAULT and SYSTEM FAULT LEDs on the front 
panel, the CPU fault LED inside the panel.  

This  fault  can  only  be  cleared  by  pressing  the  WATCHDOG  RESET  button  on  the  PCB  inside  the  control 

panel. The control panel buzzer can not be silenced and will continue to sound until the watchdog activation 

is reset. 

 

18

19. Processor reset switch 

Once  started,  the  microprocessor  controlling  the  panel  should  continue  to  run  continuously  without 

interruption. If the microprocessor fails to run correctly it can be reset by pressing the PROCESSOR RESET 

button on the PCB inside the control panel. 
This should not normally be necessary but should be done as a matter of course if the system is behaving 

abnormally.  The  system  should  resume  normal  operation  within  a  couple  of  seconds  of  pressing  the 

processor reset button. 

19B

20. Internal indications – troubleshooting 

To assist in identifying fault conditions which are not detailed on the front of the control panel, a number of 

internal indicators are visible with the front cover removed as follows: 

 

39B

20.1 Mains fail 

Indicates that the 230V AC supply is not present and the system is running on standby batteries. 
If there is not a power cut, check the panels mains fuse. 

 

40B

20.2 Batt fail 

Indicates that the standby battery has become disconnected or that the charging circuit of the control panel 

has a high resistance or has failed. Check that both batteries are connected and linked together. Test 

battery. Disconnect battery and ensure that 28 Volts can be measured on battery charger leads. 

 

41B

20.3 CPU fault 

Indicates that the central processor unit has failed to correctly execute code and has been re-started by the 
system watchdog. The watchdog reset switch must be pressed to clear the CPU fault condition. 

Press watchdog reset. If system does not return to normal then the panel is probably damaged and needs 

the circuit board replacing. (See maintenance section). 

 

42B

20.4 Aux 24V fault 

The Aux 24V and R0V terminals provide a 500 milliamp, 24V DC power supply for power fire alarm ancillary 
equipment. This LED indicates that fuse protecting the R0V output has operated and the rating of this output 

has been exceeded. The fuse is a self resetting type and the supply will resume when the fault condition is 

removed. 

 

43B

20.5 Batt low 

Illuminates when the system is running on batteries and the battery voltage is lower than 21V +/-2% (the 
minimum battery voltage). 

 

44B

20.6 Earth fault 

Indicates that part of the system wiring is connected to earth. Remove all system wiring and re-connect 

cables one at a time until the earth fault returns. This will indicate which cable the earth fault is present on. 

 

Summary of Contents for Sigma CP K Series

Page 1: ......

Page 2: ...contacts 13 12B13 Connection to Repeater panels 13 13B14 Connection to Ancillary boards 14 14B15 Connection to 8 way Sounder boards 14 15B16 Panel operation 15 16B17 Configuration options 16 17B18 Wa...

Page 3: ...operate upon fire condition These are to be used for local control and signalling 1B2 Safety and mounting Suppliers of articles for use at work are required under section 6 of the Health and Safety a...

Page 4: ...t with electronic fuse Dedicated sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp total load over UallU circuits Zonal sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp to...

Page 5: ...IONISATION Apollo 32 55000 217 SERIES 65 IONISATION Apollo 32 55000 218 SERIES 65 IONISATION Apollo 32 55000 219 SERIES 65 IONISATION Apollo 32 55000 220 SERIES 65 IONISATION Apollo 32 55000 315 SERI...

Page 6: ...connected to a zone this number should be limited to 32 to ensure that a short or open circuit on the wiring does not prevent the indication of a fire alarm from more than 32 fire detectors and or cal...

Page 7: ...470R KC For standard 4 wire systems CX 470 OHM CALL POINT Fulleon NCP T CALL POINT Nittan ELECTRONICS FREE BASES ALL Note LCMU Line Continuity Monitoring Device part number K1406 allows call points mo...

Page 8: ...system diagram which should be supplied by the detector manufacturer The power rating of the end of line resistor will be dependent upon the Zone classification rating Gas class this will be specified...

Page 9: ...the three way terminal block on the left hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box t...

Page 10: ...ntrol panels from time to time and when this is done the operating software of the unit is updated The software revision can be located on the main processor by removing the plate holding the PCB from...

Page 11: ...pplied fitted to the control panels terminals and placing them across the last device that is wired to the zone circuit Detection zone circuits must be wired as a single radial circuit with no spurs o...

Page 12: ...n any one circuit 9B10 Connection to remote control terminals Some functions of the control panel can be controlled externally from the panel if required Operation of these inputs must be restricted b...

Page 13: ...of a fire condition on any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not o...

Page 14: ...s containing boards labelled S4XXA or above They will not work with panels containing boards without an alpha suffix 14B15 Connection to 8 way Sounder boards Sounder boards connect via a 2 core cable...

Page 15: ...to light indicating a fault on the wiring to the sounder circuits 30B16 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the charging circuit will cau...

Page 16: ...mber appears Pressing the Enter button will cause the Test and Zone Fault LEDs to illuminate indicating the zones which are in test mode Disablements and zone tests are cleared by repeating the sequen...

Page 17: ...r will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM ANOTHER ZONE Silenced sounders will not re sound upon further zone activations 2A TRE...

Page 18: ...NOT SOUND ALARMS 94 ZONE 4 DOES NOT SOUND ALARMS 95 ZONE 5 DOES NOT SOUND ALARMS 96 ZONE 6 DOES NOT SOUND ALARMS 97 ZONE 7 DOES NOT SOUND ALARMS 98 ZONE 8 DOES NOT SOUND ALARMS A1 ZONE 1 ANY ALARM DEL...

Page 19: ...the control panel a number of internal indicators are visible with the front cover removed as follows 39B20 1 Mains fail Indicates that the 230V AC supply is not present and the system is running on s...

Page 20: ...ime until over rated circuit trips fuse to identify troublesome circuit 46B20 8 S1 fault and S2 fault Indicates a short or open circuit on sounder outputs Remove wiring and refit end of line resistors...

Page 21: ...panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity see table 2 for battery size required for each model The maximum current drawn from the batteries when the main...

Page 22: ...ire alarm system in accordance with BS5839 Part 1 2002 will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately Shoul...

Page 23: ...by a flashing zone indicator and Pu on the 7 segment display Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM...

Page 24: ...DOES NOT SOUND ALARMS 99 A1 ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously before an alarm is generated A2 ZONE 2 ANY ALARM DELAYED A3 ZONE 3 ANY ALARM DELAYED A4 ZON...

Reviews: