Man-1078_Sigma_CP_22
Page 22 of 24
22. Maintenance
Sigma CP control panels do not require any specific maintenance but should the control panel become dirty
it can be wiped over with a damp cloth and should then be dried with a dry, lint free cloth. Detergents or
solvents should not be used to clean the panel and care must be taken that water does not enter the
enclosure.
The control panel contains sealed lead acid batteries to provide standby power in the event of a mains
failure.
These batteries have a life expectancy of around 4 years. It is recommended that these batteries be tested
in accordance with the battery manufacturer’s recommendations annually to determine their suitability for
continued standby applications.
Routine testing of the fire alarm system in accordance with BS5839: Part 1: 2002 will identify any
malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance
company immediately.
Should the control panel become faulty the complete electronic assembly can be replaced.
To do this, any configured options should be noted then both mains and battery power should be removed
before the work is started.
The field wiring should be carefully labelled and removed from the terminals.
The PCB can now be taken out of the panel by removing the 2 holding the plate in position.
Fitting the new PCB is the reverse of the procedure for removing the board.
22B
23. Zone designation label
All Sigma CP control panels are supplied with a zone designation label onto which zone designations can be
written.
This enables each zone to be given a text description allowing easier identification of any zones showing an
abnormal condition.
ZONE DESIGNATION LABEL
Summary of Contents for Sigma CP K Series
Page 1: ......