background image

Man-1078_Sigma_CP_22 
 

     Page 24 of 24

 

 
 
 
 
 

 

 

 

CODE  

FUNCTION 

COMMENTS 

SET 

71* 

ZONE 1 SHORT CIRCUIT INDICATES ALARM 

Changes the trigger threshold of the 
zone so that the control panel can be 
used on older systems that had no short 

circuit monitoring. 

 

72* 

ZONE 2 SHORT CIRCUIT INDICATES ALARM

 

 

73* 

ZONE 3 SHORT CIRCUIT INDICATES ALARM

 

 

74* 

ZONE 4 SHORT CIRCUIT INDICATES ALARM

 

 

75* 

ZONE 5 SHORT CIRCUIT INDICATES ALARM

 

 

76* 

ZONE 6 SHORT CIRCUIT INDICATES ALARM

 

 

77* 

ZONE 7 SHORT CIRCUIT INDICATES ALARM

 

 

78* 

ZONE 8 SHORT CIRCUIT INDICATES ALARM

 

 

 

 

 

 

81* 

ZONE 1 NON-LATCHING 

Renders the zone self-resetting so that 
it can be used to receive signals from  
other systems and will reset when the 
input is removed. 
Note: It can take up to 20 seconds for zone to reset itself when 
sounders are operating 

 

82* 

ZONE 2 NON-LATCHING 

 

83* 

ZONE 3 NON-LATCHING 

 

84* 

ZONE 4 NON-LATCHING 

 

85* 

ZONE 5 NON-LATCHING 

 

86* 

ZONE 6 NON-LATCHING 

 

87* 

ZONE 7 NON-LATCHING 

 

88* 

ZONE 8 NON-LATCHING 

 

 

 

 

 

91 

ZONE 1 DOES NOT SOUND ALARMS 

Prevents  the  zone  from  operating  the  two  common  sounder 

outputs 
 

 

92 

ZONE 2 DOES NOT SOUND ALARMS

 

 

93 

ZONE 3 DOES NOT SOUND ALARMS

 

 

94 

ZONE 4 DOES NOT SOUND ALARMS

 

 

95 

ZONE 5 DOES NOT SOUND ALARMS

 

 

96 

ZONE 6 DOES NOT SOUND ALARMS

 

 

97 

ZONE 7 DOES NOT SOUND ALARMS

 

 

98 

ZONE 8 DOES NOT SOUND ALARMS

 

 

99 

 

 

 

A1* 

ZONE 1 ANY ALARM DELAYED 

Zone needs to be triggered for 30 seconds continuously 
before an alarm is generated.  

 

A2* 

ZONE 2 ANY ALARM DELAYED 

 

A3* 

ZONE 3 ANY ALARM DELAYED 

 

A4* 

ZONE 4 ANY ALARM DELAYED 

 

A5* 

ZONE 5 ANY ALARM DELAYED 

 

A6* 

ZONE 6 ANY ALARM DELAYED 

 

A7* 

ZONE 7 ANY ALARM  DELAYED 

 

A8* 

ZONE 8 ANY ALARM DELAYED 

 

 

 

 

 

C1 

ZONE 1 SOUNDERS INHIBITED 

Enables  individual  zones  to  be  configured  not  to  operate  zonal 
sounders. 
On  2  wire  “T”  series  panels  this  enables  individual  zones  to  be 
configured  for  use  with  conventional  (non-savwire)  detector 
bases. 
 
 
SOFTWARE VERSIONS SIGMA242.HEX hex and above only 

 

C2 

ZONE 2 SOUNDERS INHIBITED

 

 

C3 

ZONE 3 SOUNDERS INHIBITED

 

 

C4 

ZONE 4 SOUNDERS INHIBITED

 

 

C5 

ZONE 5 SOUNDERS INHIBITED

 

 

C6 

ZONE 6 SOUNDERS INHIBITED

 

 

C7 

ZONE 7 SOUNDERS INHIBITED

 

 

C8 

ZONE 8 SOUNDERS INHIBITED

 

 

 

 

 

 

E1* 

ZONE 1 WILL NOT OPERATE FIRE RELAY 

Enables  individual  zones  to  be  selected  to  not  operate  the  fire 
relay. This is sometimes combined with the non-latching function 
to prevent ring around on interconnected panels. 
 
 
 

 
SOFTWARE VERSIONS SIGMA242.HEX hex and above only 

 

E2* 

ZONE 2 WILL NOT OPERATE FIRE RELAY

 

 

E3* 

ZONE 3 WILL NOT OPERATE FIRE RELAY

 

 

E4* 

ZONE 4 WILL NOT OPERATE FIRE RELAY

 

 

E5* 

ZONE 5 WILL NOT OPERATE FIRE RELAY

 

 

E6* 

ZONE 6 WILL NOT OPERATE FIRE RELAY

 

 

E7* 

ZONE 7 WILL NOT OPERATE FIRE RELAY

 

 

E8* 

ZONE 8 WILL NOT OPERATE FIRE RELAY

 

 

 

 

 

 

 

 

 

 

 

NOTE: Setting the options marked with asterisks does not comply with EN54-2 

 
 

Summary of Contents for Sigma CP K Series

Page 1: ......

Page 2: ...contacts 13 12B13 Connection to Repeater panels 13 13B14 Connection to Ancillary boards 14 14B15 Connection to 8 way Sounder boards 14 15B16 Panel operation 15 16B17 Configuration options 16 17B18 Wa...

Page 3: ...operate upon fire condition These are to be used for local control and signalling 1B2 Safety and mounting Suppliers of articles for use at work are required under section 6 of the Health and Safety a...

Page 4: ...t with electronic fuse Dedicated sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp total load over UallU circuits Zonal sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp to...

Page 5: ...IONISATION Apollo 32 55000 217 SERIES 65 IONISATION Apollo 32 55000 218 SERIES 65 IONISATION Apollo 32 55000 219 SERIES 65 IONISATION Apollo 32 55000 220 SERIES 65 IONISATION Apollo 32 55000 315 SERI...

Page 6: ...connected to a zone this number should be limited to 32 to ensure that a short or open circuit on the wiring does not prevent the indication of a fire alarm from more than 32 fire detectors and or cal...

Page 7: ...470R KC For standard 4 wire systems CX 470 OHM CALL POINT Fulleon NCP T CALL POINT Nittan ELECTRONICS FREE BASES ALL Note LCMU Line Continuity Monitoring Device part number K1406 allows call points mo...

Page 8: ...system diagram which should be supplied by the detector manufacturer The power rating of the end of line resistor will be dependent upon the Zone classification rating Gas class this will be specified...

Page 9: ...the three way terminal block on the left hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box t...

Page 10: ...ntrol panels from time to time and when this is done the operating software of the unit is updated The software revision can be located on the main processor by removing the plate holding the PCB from...

Page 11: ...pplied fitted to the control panels terminals and placing them across the last device that is wired to the zone circuit Detection zone circuits must be wired as a single radial circuit with no spurs o...

Page 12: ...n any one circuit 9B10 Connection to remote control terminals Some functions of the control panel can be controlled externally from the panel if required Operation of these inputs must be restricted b...

Page 13: ...of a fire condition on any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not o...

Page 14: ...s containing boards labelled S4XXA or above They will not work with panels containing boards without an alpha suffix 14B15 Connection to 8 way Sounder boards Sounder boards connect via a 2 core cable...

Page 15: ...to light indicating a fault on the wiring to the sounder circuits 30B16 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the charging circuit will cau...

Page 16: ...mber appears Pressing the Enter button will cause the Test and Zone Fault LEDs to illuminate indicating the zones which are in test mode Disablements and zone tests are cleared by repeating the sequen...

Page 17: ...r will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM ANOTHER ZONE Silenced sounders will not re sound upon further zone activations 2A TRE...

Page 18: ...NOT SOUND ALARMS 94 ZONE 4 DOES NOT SOUND ALARMS 95 ZONE 5 DOES NOT SOUND ALARMS 96 ZONE 6 DOES NOT SOUND ALARMS 97 ZONE 7 DOES NOT SOUND ALARMS 98 ZONE 8 DOES NOT SOUND ALARMS A1 ZONE 1 ANY ALARM DEL...

Page 19: ...the control panel a number of internal indicators are visible with the front cover removed as follows 39B20 1 Mains fail Indicates that the 230V AC supply is not present and the system is running on s...

Page 20: ...ime until over rated circuit trips fuse to identify troublesome circuit 46B20 8 S1 fault and S2 fault Indicates a short or open circuit on sounder outputs Remove wiring and refit end of line resistors...

Page 21: ...panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity see table 2 for battery size required for each model The maximum current drawn from the batteries when the main...

Page 22: ...ire alarm system in accordance with BS5839 Part 1 2002 will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately Shoul...

Page 23: ...by a flashing zone indicator and Pu on the 7 segment display Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM...

Page 24: ...DOES NOT SOUND ALARMS 99 A1 ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously before an alarm is generated A2 ZONE 2 ANY ALARM DELAYED A3 ZONE 3 ANY ALARM DELAYED A4 ZON...

Reviews: