CODE
FUNCTION
COMMENTS
SET
71*
ZONE 1 SHORT CIRCUIT INDICATES ALARM
Changes the trigger threshold of the
zone so that the control panel can be
used on older systems that had no short
circuit monitoring.
72*
ZONE 2 SHORT CIRCUIT INDICATES ALARM
73*
ZONE 3 SHORT CIRCUIT INDICATES ALARM
74*
ZONE 4 SHORT CIRCUIT INDICATES ALARM
75*
ZONE 5 SHORT CIRCUIT INDICATES ALARM
76*
ZONE 6 SHORT CIRCUIT INDICATES ALARM
77*
ZONE 7 SHORT CIRCUIT INDICATES ALARM
78*
ZONE 8 SHORT CIRCUIT INDICATES ALARM
81*
ZONE 1 NON-LATCHING
Renders the zone self-resetting so that
it can be used to receive signals from
other systems and will reset when the
input is removed.
Note: It can take up to 20 seconds for zone to reset itself when
sounders are operating
82*
ZONE 2 NON-LATCHING
83*
ZONE 3 NON-LATCHING
84*
ZONE 4 NON-LATCHING
85*
ZONE 5 NON-LATCHING
86*
ZONE 6 NON-LATCHING
87*
ZONE 7 NON-LATCHING
88*
ZONE 8 NON-LATCHING
91
ZONE 1 DOES NOT SOUND ALARMS
Prevents the zone from operating the two common sounder
outputs
92
ZONE 2 DOES NOT SOUND ALARMS
93
ZONE 3 DOES NOT SOUND ALARMS
94
ZONE 4 DOES NOT SOUND ALARMS
95
ZONE 5 DOES NOT SOUND ALARMS
96
ZONE 6 DOES NOT SOUND ALARMS
97
ZONE 7 DOES NOT SOUND ALARMS
98
ZONE 8 DOES NOT SOUND ALARMS
99
A1*
ZONE 1 ANY ALARM DELAYED
Zone needs to be triggered for 30 seconds continuously
before an alarm is generated.
A2*
ZONE 2 ANY ALARM DELAYED
A3*
ZONE 3 ANY ALARM DELAYED
A4*
ZONE 4 ANY ALARM DELAYED
A5*
ZONE 5 ANY ALARM DELAYED
A6*
ZONE 6 ANY ALARM DELAYED
A7*
ZONE 7 ANY ALARM DELAYED
A8*
ZONE 8 ANY ALARM DELAYED
C1
ZONE 1 SOUNDERS INHIBITED
Enables individual zones to be configured not to operate zonal
sounders.
On 2 wire “T” series panels this enables individual zones to be
configured for use with conventional (non-savwire) detector
bases.
SOFTWARE VERSIONS SIGMA242.HEX hex and above only
C2
ZONE 2 SOUNDERS INHIBITED
C3
ZONE 3 SOUNDERS INHIBITED
C4
ZONE 4 SOUNDERS INHIBITED
C5
ZONE 5 SOUNDERS INHIBITED
C6
ZONE 6 SOUNDERS INHIBITED
C7
ZONE 7 SOUNDERS INHIBITED
C8
ZONE 8 SOUNDERS INHIBITED
E1*
ZONE 1 WILL NOT OPERATE FIRE RELAY
Enables individual zones to be selected to not operate the fire
relay. This is sometimes combined with the non-latching function
to prevent ring around on interconnected panels.
SOFTWARE VERSIONS SIGMA242.HEX hex and above only
E2*
ZONE 2 WILL NOT OPERATE FIRE RELAY
E3*
ZONE 3 WILL NOT OPERATE FIRE RELAY
E4*
ZONE 4 WILL NOT OPERATE FIRE RELAY
E5*
ZONE 5 WILL NOT OPERATE FIRE RELAY
E6*
ZONE 6 WILL NOT OPERATE FIRE RELAY
E7*
ZONE 7 WILL NOT OPERATE FIRE RELAY
E8*
ZONE 8 WILL NOT OPERATE FIRE RELAY
NOTE: Setting the options marked with asterisks does not comply with EN54-2