background image

Man-1078_Sigma_CP_22 
 

     Page 4 of 24

 

Mounting

 

The  control  panel  should  be  mounted  on  a  dry,  flat  surface,  at  eye  height  to  the  display  and  in  a  level 

position such that the enclosure is not distorted.  
Screws or bolts of a minimum of 5mm diameter must be used to mount the enclosure in all three mounting 

positions. 
It should be positioned in an accessible position as agreed with the end user.  
Suitable fixings should be used at all fixing points such that the control panel is securely mounted and is not 

liable to move once fixed. 
The control panel should not be mounted in another enclosure or near sources of excessive heat.  
Cables should be connected using suitable cable glands fitted to the knockouts provided. If additional cable 

entry points are required, all swarf and debris caused by drilling of additional cable entries must be cleared 

before power is applied to the panel. 

2B

3. Technical specification 

Table 1 - Electrical specifications 

Mains supply 

230V AC  +10% - 15%  (100 Watts maximum) 

 

Mains supply fuse 

1.6Amp (F1.6A L250V) 

Replace only with similar type 

Power supply rating 

3 Amps total including battery charge 28V +/ 2V 

 

Maximum ripple current 

1.5 Volts 

 

Output voltage 

18.5 to 29V DC +/- 2% 

 

Imax a 

400 milliamps 

 

Imax b 

2.3 Amps 

 

Imin 

0.065A 

 

Battery type (Yuasa NP) 

Two 12 Volt sealed lead acid (7Ah maximum)  
Flame retardant UL94:V-0 

See table 2 for capacities 

Battery charge voltage 

27.6VDC nominal (temperature compensated) 

See table 3  

Battery charge current 

0.7A maximum 

 

Battery lead fuse 

20mm, 3.15A glass 

Replace only with the same type 

Battery high impedance warning 
(Rimax) 

1.35 ohms max 

 

Low battery voltage indication 

21V +/- 2% 

 

Low battery shut off voltage 

18.5V +/- 2% 

 

Maximum current draw from batteries 

3 Amps 

With main power source disconnected 

R0V output 

Fused at  with electronic fuse 

 

Dedicated sounder outputs 

24V Fused at 500mA with electronic fuse 

1.6 Amp total load over 

U

all

U

 circuits 

Zonal sounder outputs 

24V Fused at 500mA with electronic fuse 

1.6 Amp total load over 

U

all

U

 circuits 

Fault relay contact rating 

30VDC 1A Amp maximum for each 

Maximum ratings not to be exceeded 

Fire relay contact rating 

30VDC 1A Amp maximum for each 

Maximum ratings not to be exceeded 

Local fire relay contact rating 

30VDC 1A Amp maximum for each 

Maximum ratings not to be exceeded 

Zone quiescent current 

1.6mA maximum 

See table 4 for detector types 

Terminal capacity 

0.5mm

2

 to 2.5mm

2  

solid or stranded wire 

 

Number of detectors per zone 

> 20  

Dependent on type 

Number of sounders per circuit 

Dependent on type and current consumption 

See table 6 for sounder types 

Detection circuit end of line 

6K8 5% ½ Watt resistor 

Supplied in terminals 

Sounder circuit end of line 

10K 5% ¼ Watt resistor 

Supplied in terminals 

No. of detection circuits 

 (see table 2 for number of zones for each model) 

Dependent on model 

No. of sounder outputs 

2 (plus one per zone on T models) 

 

SIL, AL, FLT, RST inputs 

Switched -ve, max resistance 100 Ohms 

 

Zone normal threshold 

8K ohm TO 1K ohm 

 

Detector alarm threshold 

999 ohms to 400 ohms 

 

Call point alarm threshold 

399 ohms to 100 ohms 

 

Short circuit threshold 

99 ohms to 0 ohms 

 

Head removal condition 

15.5 to 17.5 volts 

Zener clamp detector base to be used 

Cabling 

FP200 or equivalent (maximum capacitance 1uF 
maximum inductance 1 millihenry) 

Metal  cable glands must be used 

 

Table 2 - Standby battery capacity required for fully loaded system 

Panel model 

24 hours 
standby 

48 hours standby 

72 hours 
standby 

Standby current 

Max panel alarm 
current 

K11020 (2 Zones) 

3Ah 

4.6Ah 

6.2Ah 

0.065 

0.10A 

K11040 (4 Zones) 

3.3Ah 

5.1Ah 

6.9Ah 

0.075 

0.21A 

K11080 (8 Zones) 

3.75Ah 

5.95Ah 

8.2Ah 

0.093A 

0.55A 

T11020 (2 Zones) 

3Ah 

4.6Ah 

6.2Ah 

0.065 

0.15A 

T11040 (4 Zones) 

3.3Ah 

5.1Ah 

6.9Ah 

0.075 

0.30A 

T11080 (8 Zones) 

3.75Ah 

5.95Ah 

8.2Ah 

0.093A 

0.63A 

 

Summary of Contents for Sigma CP K Series

Page 1: ......

Page 2: ...contacts 13 12B13 Connection to Repeater panels 13 13B14 Connection to Ancillary boards 14 14B15 Connection to 8 way Sounder boards 14 15B16 Panel operation 15 16B17 Configuration options 16 17B18 Wa...

Page 3: ...operate upon fire condition These are to be used for local control and signalling 1B2 Safety and mounting Suppliers of articles for use at work are required under section 6 of the Health and Safety a...

Page 4: ...t with electronic fuse Dedicated sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp total load over UallU circuits Zonal sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp to...

Page 5: ...IONISATION Apollo 32 55000 217 SERIES 65 IONISATION Apollo 32 55000 218 SERIES 65 IONISATION Apollo 32 55000 219 SERIES 65 IONISATION Apollo 32 55000 220 SERIES 65 IONISATION Apollo 32 55000 315 SERI...

Page 6: ...connected to a zone this number should be limited to 32 to ensure that a short or open circuit on the wiring does not prevent the indication of a fire alarm from more than 32 fire detectors and or cal...

Page 7: ...470R KC For standard 4 wire systems CX 470 OHM CALL POINT Fulleon NCP T CALL POINT Nittan ELECTRONICS FREE BASES ALL Note LCMU Line Continuity Monitoring Device part number K1406 allows call points mo...

Page 8: ...system diagram which should be supplied by the detector manufacturer The power rating of the end of line resistor will be dependent upon the Zone classification rating Gas class this will be specified...

Page 9: ...the three way terminal block on the left hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box t...

Page 10: ...ntrol panels from time to time and when this is done the operating software of the unit is updated The software revision can be located on the main processor by removing the plate holding the PCB from...

Page 11: ...pplied fitted to the control panels terminals and placing them across the last device that is wired to the zone circuit Detection zone circuits must be wired as a single radial circuit with no spurs o...

Page 12: ...n any one circuit 9B10 Connection to remote control terminals Some functions of the control panel can be controlled externally from the panel if required Operation of these inputs must be restricted b...

Page 13: ...of a fire condition on any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not o...

Page 14: ...s containing boards labelled S4XXA or above They will not work with panels containing boards without an alpha suffix 14B15 Connection to 8 way Sounder boards Sounder boards connect via a 2 core cable...

Page 15: ...to light indicating a fault on the wiring to the sounder circuits 30B16 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the charging circuit will cau...

Page 16: ...mber appears Pressing the Enter button will cause the Test and Zone Fault LEDs to illuminate indicating the zones which are in test mode Disablements and zone tests are cleared by repeating the sequen...

Page 17: ...r will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM ANOTHER ZONE Silenced sounders will not re sound upon further zone activations 2A TRE...

Page 18: ...NOT SOUND ALARMS 94 ZONE 4 DOES NOT SOUND ALARMS 95 ZONE 5 DOES NOT SOUND ALARMS 96 ZONE 6 DOES NOT SOUND ALARMS 97 ZONE 7 DOES NOT SOUND ALARMS 98 ZONE 8 DOES NOT SOUND ALARMS A1 ZONE 1 ANY ALARM DEL...

Page 19: ...the control panel a number of internal indicators are visible with the front cover removed as follows 39B20 1 Mains fail Indicates that the 230V AC supply is not present and the system is running on s...

Page 20: ...ime until over rated circuit trips fuse to identify troublesome circuit 46B20 8 S1 fault and S2 fault Indicates a short or open circuit on sounder outputs Remove wiring and refit end of line resistors...

Page 21: ...panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity see table 2 for battery size required for each model The maximum current drawn from the batteries when the main...

Page 22: ...ire alarm system in accordance with BS5839 Part 1 2002 will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately Shoul...

Page 23: ...by a flashing zone indicator and Pu on the 7 segment display Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM...

Page 24: ...DOES NOT SOUND ALARMS 99 A1 ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously before an alarm is generated A2 ZONE 2 ANY ALARM DELAYED A3 ZONE 3 ANY ALARM DELAYED A4 ZON...

Reviews: