Although the current consumption of many detection devices would allow more than 32 to be connected to a
zone, this number should be limited to 32 to ensure that a short or open circuit on the wiring does not
prevent the indication of a fire alarm from more than 32 fire detectors and/or call points as required by
European standard EN54-2.
No more than 32 detectors and call points should be fitted to any one zone.