14.15. Data sheet digital I/O expansion-module (KIO7052)
Description
Expansion module for connection to the AlarmManager-PRO.
This module extends the external inputs and outputs of AlarmManager
on additional 8 digital inputs and 8 digital outputs. Communication is
via Ethernet, so the module can be mounted anywhere. The
configuration is done in the software interface of the
AlarmManager-PRO. The module provides a build in web-server with
for simple IP configuration and testing of the inputs and outputs
without any additional software.
Connectivity
Connection to Kentix AlarmManager-PRO
External Alarms of existing system equipment
(HVAC, UPS systems, generators, alarm systems, etc.)
Configuration
Build in Web-Server (HTTP), Default IP:
192.168.255.1
(Admin/Admin)
Protocols
KAM-IO communication via IP-PORT: 502 (Default)
Security
ID, Password and IP-Filter
Terminals
Plug-able screw-terminal for cables up to 1mm
²
Inputs
Digital wet inputs
ON: +10–50VDC, OFF: +4DC
Input impedance: 10kOHM
Over voltage protection: 70VDC
Outputs
Open-Collector outputs 10–40VDC
Current 650mA (bis 1.1A Over current protection)
Over voltage protection: 47VDC
Fixed output assignment
DO1-DO8: Armed-Active, Always-Active, Sabotage, General-Alarm,
Arm-Zone1, Arm-Zone2, Arm-Zone3, Arm-General
Isolation
Ethernet 1,5kVDC, I/O 3,7kVrms
Environment
Operation temperature 0°C to +45°C, Rel. humidity 10–90%
Network
LAN 10/100 Base-TX
Power supply
PoE (Class 1) or external power supply 12–30VDC, 4.3Watt
Chassis
72 x 123 x 35 mm (DIN-rail mounting)
Content of delivery
KIO7052, 3m patch-cable, power-cable, manual
Approvals
CE
Page
(07-2018, subject to change)
kentix.com
122
INPUT sink signal (High=1)
INPUT sink signal (Low=0)
INPUT sink signal (High=1)
INPUT source signal (Low=0)
OUTPUT relay
OUTPUT sink (resistive)
Pin assignment KIO7052
Front
Back