8.3. Kentix Power-Adapter (KIO1) with digital input clips
The Kentix I/O Power-Adapter is used to expand your Kentix-solution to include the additional functions:
• Power supply for up to two MultiSensors-RF via an AC adapter
• Connecting of up to two external alarms via dry contacts to a MultiSensor
The adapter is connected directly to the Kentix system jack and offers the possibility to power the MultiSensor
with a power plug or a permanently connected AC adapter.
The cable length between MultiSensor and the KIO1 adapter should not exceed the following lengths:
• Power supply only: up to 50m
• Power supply with digital inputs: up to 10m
Figure 1: Back of Kentix Power-Adapter (KIO1)
Figure 2: Circuit diagram with external alarms
Page
(07-2018, subject to change)
kentix.com
45
Important!
When using the input clips for external alarms and simultaneous power supply of two MultiSensors remove the
jumpers. Otherwise the external alarms will be indicated on both sensors.
L
e
a
ka
g
e
se
n
so
r
Accessories