Configuration - Sensors and Alarm

In the following settings you can set the limit and action values for the alerting.
When an alarm is triggered, an e-mail will be sent to the configured persons and the internal buzzer is 
activated.

Device name

Configuration of the device name, this name can be chosen freely. 

Sensor-Temperature, Humidity, Dew-point

Set the alarm limit values. Alarm will be triggered when the measurements undershot or exceeded the limits.
The temperature hysteresis is set to 1°C or 1%.
The dew-point will be calculated with the current temperature and the relative humidity from the sensor.
If the room temperature approximates to the difference of the set dew-point hysteresis (2°C default) an alarm 
will be triggered. Systems and devices can lead to condensation, when the dewpoint temperature 
approximates the room temperature. The humidity has reached its saturation.

Sensor-Carbon Monoxide

Alarm settings for the Carbon Monoxide. The sensitivity can be set from 0% to 100% and will be triggered by 
exceeding. CO is measured from about 10ppm. There is no exact measurement of the CO content. The 
measurement is construed to the highest sensitivity and can be changed slightly in the adjustment.
Carbon Monoxide concentrations like they emerge in fires are detected even at 100% setting.
10%: Minimal concentration of around 10-50ppm lead to an alarm trigger.
100%: Concentrations of 200-400ppm lead to an alarm trigger. 

Sensor-Motion

Limit value for the integrated PIR (passive infra-rot) motion detection. It is triggered when exceeded. Objects 
which have a temperature difference of about 4°C to the environment temperature and which are bigger than 
250x400mm will be detected. For a safe detection of persons, the value should be in the range of 30-50%.
The detection range is about 100°.

Arm-Disarm time

Switching time for the time-controlled arming and disarming from the integrated motion detection.
To use it, a time server (NTP) must be set in the network settings. Pay attention, that the internal time base is 
UTC.

Ext. alarm input 1/2

The MultiSensor has two configureable  alarm inputs. At this alarm inputs external signaling devices can be 
plugged (e.g leakage sensors, door contacts or malfunction messages from external devices). The trigger is 
set by a potential free contact (opener). The trigger logic can be set to HI or LOW.

Page 7                                          

!

(09-2012, subject to change)

!

www.kentix.de

Summary of Contents for MultiSensor-LAN

Page 1: ...User Manual MultiSensor LAN From Firmware Version 2 xx xx...

Page 2: ...ation Network 6 2 6 Configuration Sensors and Alarm 7 2 7 User accounts and notification 8 2 8 Language 8 2 9 Software update MultiSensor LAN 9 2 10 Copy or save Configuration of MultiSensor LAN 9 2 1...

Page 3: ...actices Energy and water utility Safety note The installation of the MultiSensors must be run by an competent person In a power failure the settings are not lost Energized relays drop out and go back...

Page 4: ...t to the power supply over PoE power over ethernet So you can operate the device without another power supply direct by an PoE capable switch The market standard PoE injectors can also be used for pow...

Page 5: ...hot or exceeded NOK There is a measurement undershot or exceeded an alarm is triggered ON Function or input output status is switched on OFF Function or input output status is switched off Monitoring...

Page 6: ...larmManager and set the hook FTP server activation The integrated FTP server can be activated or deactivated The FTP access will be needed for a software update of the device Look up in the chapter so...

Page 7: ...he CO content The measurement is construed to the highest sensitivity and can be changed slightly in the adjustment Carbon Monoxide concentrations like they emerge in fires are detected even at 100 se...

Page 8: ...me when a triggered alarm shall be triggered The alarm will be sent to the entered e mail addresses until all values are in normal range again A value of 0 sets the alarm repeating to inactive User ac...

Page 9: ...ate file will be deleted from the filesystem of the MultiSensor IMPORTANT During the update procedure the power supply must not break 7 Now the MultiSensor is accessible and you can see the software v...

Page 10: ...minutes Current data http MultiSensorIP xml values xml Historical data http MultiSensorIP xml record xml Switch alarm output 2 In the category system you can find a way to turn on the alarm output 2...

Page 11: ...nsor there where is also the config ini file After a reboot the configured command sequence will send to the camera in case of an alarm Up to five cameras can be controlled create for each camera a ne...

Page 12: ...The alarm inputs of the device are only on System connector 1 of the terminal connection of the KIO1 adapter available Page 12 09 2012 subject to change www kentix de IMPORTANT The switching outputs 6...

Page 13: ...port side forward 3 Pull the lid at the sides apart sightly see picture 4 The lid will snap out from the surrounding groove with a clicking noise 5 Now you can pull up the lid Close the device lid 1 L...

Page 14: ...RM red RUN yellow LINK ACT at the LAN jack LAN 10 100 Mbit LAN connection integrated web server SNMP Simple Network Management Protocol SNMP V2 write read SNMP Traps XML Output Actual and historical v...

Page 15: ...facturers websites Copyright Notice All rights reserved Any text images graphics animations and videos as well as content and structure of this manual are protected by copyright and other laws protect...

Reviews: