Installing Windows OS 

1. 

Read the Windows installation disc by connecting a USB CD-ROM drive. 
(Or, burn the Windows ISO image to a USB drive, and then insert the USB drive into HMI.) 

2. 

Press and hold on the center of the screen and then select the device. 
(Or, connect a USB keyboard, and press F5 key at startup.) 

 

Turning ON/OFF the HMI 

ON: 

To turn on the HMI, go to BIOS and set whether to automatically turn on, or press the power button to turn 
on, when the HMI is connected to power supply.

 

 

Go to BIOS \ Advanced \ South Cluster Configuration \ Miscellaneous Configuration \ State After G3: 
S0 State: Automatically turn on when connected to power supply. 
S5 State: Press the power button to turn on when connected to power supply. 

 

OFF: 

To turn off the HMI, you can either turn off in Windows, or set the function of the power button in Windows 
Control Panel \ System and Security \ Power Options \ Change what the power buttons do, and press the 
power button when HMI is ON.   

Unplugging power cord directly can cause stop error and lead to data loss. 

Driver 

After installing Windows OS, install the required software / hardware drivers, in the same order as listed in 
the following link. 
Download Link:

 

http://www.weintek.com/Download/cMT/cMT_iPC10/driver/cMT_iPC10_driver.htm

 

 

Touchscreen Calibration 

To do touchscreen calibration, run HIDeGalaxTouch Tool. 

 

 

Limited Warranty                                                                                                         

 

This product is limited warranted against defects in design and manufacture.   

The proven defective product will either be repaired or replaced, at Weintek’s discretion.   

This warranty shall not cover any product which is   

(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products. 
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.   
(c) Product has been repaired or taken apart by unauthorized technicians.   
(d) Products whose identification markings have been removed or damaged.

 

 

Power 

The unit can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with 

most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a 

switching power supply. The peak starting current can be as high as 4A.

 

Fusing 
Require- 
ments 

If the display does not come on within 5 seconds of power up, remove power. A resettable fuse will 

protect against overcurrent faults in DC circuit and the resetting will take place after a period of 

time. Check wiring for proper connections and try to power up again. 

High 
Voltage 

A resettable fuse will prevent damage for overcurrent 

condition however it isn’t guaranteed. DC 

voltage sources should provide proper isolation from main AC power and similar hazards. 

Emergency 
Stop 

A Hard-wired EMERGENCY STOP should be fitted in any system using a HMI to comply with ICS 

Safety Recommendations. 

Supply 
Voltage 
Condition 

Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same 

power supply. Note: The 24 VDC output from some controllers may not have enough current to 

power the unit. 

Wire 
Routing 

a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded). 

b. Please use twisted pair cables for power wire and signal wire and conform to the impedance 

matching. 

c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices. 

d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires. 

e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power 

supply and the frame ground. This provides a path for static and high frequency dissipation. 

Typical values to use are 1M Ohm and 4700pF. 

 

 

 

CAUTION 

NOTE: 

Make sure that all local and national electrical standards are met when 

installing the unit. Contact your local authorities to determine which codes apply. 

Hardware 
Considerations 

The system designer should be aware that devices in Controller systems could fail and thereby 

create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to 

equipment start-up, which could result in property damage and/or physical injury to the operator. 

If you use any programmable control systems that require an operator, be aware that this potential 

safety hazard exists and take appropriate precautions. Although the specific design steps depend on 

your particular application, the following precautions generally apply to installation of solid-state 

programmable control devices, and conform to the guidelines for installation of Controllers 

recommended in NEMA ICS 3-304 Control Standards.

 

Programming 
Considerations 

To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure 

that all writable registers that control critical parts of plant or machinery have limit checks built into 

the program, with an out-of-limit safe shut down procedure to ensure safety of personnel. 

GMECMI100_cMT_iPC10_Installation_161018 

 

DANGER 