204
16.1 AB DF1
16.1.1 HMI Settings
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
Notes
Serial I/F port
RS-232
Options: RS232, RS485 – Dependant on PLC hardware
Baud rate
19200
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC channel
setting
Parity
None
Options: Odd, Even, None - Must match PLC channel setting
Data bits
8
Options: 7, 8 - Must match PLC channel setting
Stop bits
1
Options: 1, 2 - Must match PLC channel setting
HMI station No.
0
HMI station No. must be 0
PLC station No.
1
The Station number must match the PLC Node Number (0-31)
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
16.1.2 PLC Setting
Supports all SLC Series PLC’s that have DF1 ports.
Communication parameters must be the same as those of the MMI.
Full Duplex Operation must be set.
No Hardware Handshaking must be set.
16.1.3 Wiring
16.1.3.1
Wiring for cable connections using
AB
Micrologix CPU’s
with RS232 Round 8 pin MiniDIN ports.
KEP Part#:
SMICABMICRO-05
(D-Sub 9 Male Socket to 8 pin MiniDIN Male Plug Cable)
HMI PLC[RS-232]
Connect to AB Micrologix 1000, 1200, 1500 CPU’s RS-232 Port
2 TD
Æ
4 RX
3 RD
Æ
7 TX
5 GND
Æ
9
Æ
2 GND
Shield
Æ
Earth Ground
16.1.3.2
Wiring for cable connections using
AB CompactLogix or ControlLogix
CPU’s
with RS232 D-Sub
9 Male Socket ports.
KEP Part#:
SMICABDF1-05
(D-Sub 9 Male Socket to D-Sub 9 Female Plug Cable)
HMI PLC[RS-232]
Connect to AB Micrologix 1500, SLC5/03 or SLC5/04 CPU RS-232 port
2 TD
Æ
2 RD
3 RD
Æ
3 TD
5 GND
Æ
9
Æ
5 GND
7 RTS
Æ
8 CTS
Shield
Æ
Earth Ground