16.4 A-B Logix DF1 [PDS]
16.4.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
Notes
PLC type
AB Logix DF1 [PDS V2.00]
ablogix.pds
driver must be present in
\drivers
folder
Serial I/F port
RS-232
Baud rate
19200*
Options: 9600, 19200- Must match PLC channel setting
Parity
None*
Options: Odd, Even, None - Must match PLC channel setting
Data bits
8*
Options: 7, 8 - Must match PLC channel setting
Stop bits
1*
Options: 1, 2 - Must match PLC channel setting
HMI station No.
0
HMI station No. must be 0
PLC station No.
1
The Station number must match the PLC Node Number (1-31)
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires
a delay between requests. Not implemented in simulation mode.
*Settings given are the default.
16.4.2 PLC Settings
Communication parameters must be the same as those of the MMI.
Full Duplex Operation must be set.
No Hardware Handshaking must be set.
Error checking must be set to CRC.
Tag structure must be set as specified below (16.4.5).
Compatible PLCs
CompactLogix
TM
, ControlLogix
TM
, FlexLogix 1794-L33A
16.4.3 Wiring
16.4.3.1
Wiring for cable connections using
AB CompactLogix or ControlLogix
CPU’s
with RS232 D-Sub
9 Male Socket ports.
KEP Part#:
SMICABDF1-05
(D-Sub 9 Male Socket to D-Sub 9 Female Plug Cable)
HMI PLC[RS-232]
Connect to AB CompactLogix or ControlLogix CPU RS-232 port Channel 0 or 1
2 TD
Æ
2 RD
3 RD
Æ
3 TD
5 GND
Æ
9
Æ
5 GND
7 RTS
Æ
8 CTS
Shield
Æ
Earth Ground
Note:
Graphic representation may not reflect the actual appearance of the finished cable.