220
16.8 FACON FB
16.8.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
Notes
Serial I/F port
RS-232
Options: RS232, RS485 – Dependant on PLC hardware
Baud rate
9600
Must match PLC setting
Parity
Even
Must match PLC setting
Data bits
7
Must match PLC setting
Stop bits
1
Options: 1, 2 - Must match PLC setting
HMI station No.
0
Not used
PLC station No.
1
The Station number must match the PLC Station Number (0-255)
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
This driver supports Extended Address mode.
16.8.2 PLC Setting
Communication parameters must be set the same as those of the HMI (RS-232 port, 9600, Even parity, 7 data bits and
1 stop bit).
Compatible with:
FACON FB MC Series and FB MA Series with FB-DTBR converter.
16.8.3 Wiring
16.8.3.1
Wiring for cable connections using
FACON CPU’s
or FB-DTBR/DTBR-E
with RS232 D-Sub 15 Male
Socket ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to D-Sub 15 Female Plug Cable)
HMI PLC[RS-232]
Connect to FACON CPU’s RS-232 Port
2 TD
Æ
1 RX
3 RD
Æ
2 TX
5 GND
Æ
9
Æ
6 GND
3 RTS
Æ
4 CTS
Shield
Æ
Earth Ground
16.8.3.2
Wiring for cable connections using
FACON CPU’s
with RS485 D-Sub 15 Male Socket ports.
KEP Part#: (Not Available) (D-Sub 9 Female Socket to D-Sub 15 Female Plug Cable)
HMI PLC[RS-485]
Connect to FACON CPU
with RS485 Port
1 RXD-
Æ
7 D-
2 RXD+
Æ
5 D+
5 GND
Æ
6 GND
Shield
Æ
Earth Ground