223
16.10 GE Fanuc SNP-X
16.10.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
Notes
Serial I/F port
RS-485
Options: RS232, RS485 – Dependant on PLC hardware
Baud rate
19200
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC port
setting
Parity
Odd
Options: Odd, Even, None - Must match PLC port setting
Data bits
8
8 - Must match PLC port setting
Stop bits
1
Options: 1, 2 - Must match PLC port setting
HMI station No.
0
Not used
PLC station No.
0
Not used
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires
a delay between requests. Not implemented in simulation mode.
16.10.2 PLC Setting
Communication parameters must be the same as those of the MMI. Protocol is SNP-X.
The Modem Turnaround Delay must be set to 0.
The Level 2 Password in the PLC must be set to NULL
Compatible PLCs
•
Series 90-30: 311, 313, 323, 331, 340, 341, 351, 363, 364, CMM311
•
Series 90-70: 731, 771, 772, 780, 781, 782, 788, 789, 790, 915, 925, CSE784, CSE924, CMM711
•
Series 90 Micro: IC693UDR001, IC693UDR002, IC693UAA003, IC693UDR005, IC693UAL006, IC693UAA007,
IC693UDR010
•
VersaMax: CPU001, CPU002, CPU005, CPU E05
NFORMATION
16.10.3 Wiring
16.10.3.1
Wiring for cable connections using
GE 90/30
Series and VersaMax CPU’s
with RS422 D-Sub 15
Female Plug ports.
KEP Part#:
SMIC15GE90-05
(D-Sub 9 Female Plug to D-Sub 15 Male Socket Cable)
HMI PLC[RS-485]
Connect to GE 90
Series CPU’s with RS422 Port
1 RXD-
Æ
12 SD(A)
2 RXD+
Æ
13 SD(B)
3 TXD-
Æ
10 RD(A)
4 TXD+
Æ
11 RD(B)
Æ
9 RT
5 GND
Æ
7 SG
6 RTS(A)
Æ
15 CTS(A)
14 RTS(B)
Æ
8 CTS(B)
1
Æ
Shield
Æ
Earth Ground