232
16.14 IIS ESC (INDUSTRIAL INDEXING SYSTEMS)
16.14.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
Notes
Serial I/F port
RS232
Options: RS232, RS485 – Dependant on PLC hardware
Baud rate
19200
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC port
setting
Parity
None
Options: Odd, Even, None - Must match PLC port setting
Data bits
8
Options: 7, 8 - Must match PLC port setting
Stop bits
1
Options: 1, 2 - Must match PLC port setting
HMI station No.
0
Not used
PLC station No.
255
Not used
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
16.14.2 Controller Setting
Communication parameters must be the same as those of the MMI.
App Port set Mode: ESC Packet Protocol 19200, None, 8, 1
Compatible PLC
Emerald EMC-2000 controller
16.14.3 Wiring
16.14.3.1
Wiring for cable connections using
Emerald EMC-2000 Controllers
with RS232 RJ-12 socket ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to RJ-12 Male Cable)
HMI PLC[RS-232]
Connect to Emerald EMC-2000 Controller
with RS232 Port
2 TXD
Æ
3 RXD
3 RXD
Æ
5 TXD
5 GND
Æ
4 GND
Shield
Æ
Earth Ground
Note:
Graphic representation may not reflect the actual appearance of the finished cable.
Summary of Contents for MMI-1500
Page 2: ...ii...