16.16 Keyence KV/Visual KV [PDS]
16.16.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
Notes
PLC type
KEYENCE KV/Visual KV
[PDS V2.00]
Keyv_16DT.pds
driver must be present in
\drivers
folder
Serial I/F port
RS232
Baud rate
9600
Must match PLC port setting
Parity
Even
Options: Odd, Even, None - Must match PLC port setting
Data bits
8
Must match PLC port setting
Stop bits
1
Must match PLC port setting
HMI station No.
0
Not used
PLC station No.
0
Not used
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
16.16.2 PLC Setting
Communication parameters must be the same as those of the MMI.
Compatible PLCs
KV series PLC: KV-10, KV-16, KV-24 and KV-40
16.16.3 Wiring
16.16.3.1
Wiring for cable connections using
Keyence KV Series
with RS232 RJ-12 Socket ports.
KEP Part#: SMICKEY-05 (D-Sub 9 Male Socket to RJ-12 Male Cable)
HMI PLC[RS-232]
Connect to Keyence KV Series
CPU
with RS232 Port
2 TXD
Æ
4 RXD
3 RXD
Æ
3 TXD
5 GND
Æ
9
Æ
2 GND
Shield
Æ
Earth Ground