250
16.24.3.3
Wiring for cable connections using
Matsushita FP1, FP2, FP2SH, FPM CPU’s
with RS232 D-Sub 9
Female Plug ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to D-Sub 9 Male Socket Cable)
HMI PLC[RS-232]
Connect to Matsushita FP1, FP2, FP2SH or FPM CPU
Port
2 TXD
Æ
3 RXD
3 RXD
Æ
2 TXD
5 GND
Æ
7 GND
4 RTS
Æ
5 CTS
8 CD
Æ
9 ER
Shield
Æ
Earth Ground
16.24.3.4
Wiring for cable connections using
MATSUSHITA FP0 CPU’s
with RS232 Screw Terminal ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to Flying leads Cable)
HMI PLC[RS-232]
Connect to Matsushita FP0 Screw Terminal
Port
2 TXD
Æ
Æ
1 R
3 RXD
Æ
Æ
2 S
5 GND
Æ
Æ
3 G
Shield
Æ
Earth Ground
16.24.3.1
Wiring for cable connections using
Matsushita FP3 CPU’s
with RS422 D-Sub 15 Male Socket ports.
KEP Part#: (Not Available) (D-Sub 9 Female Plug to D-Sub 15 Female Plug Cable)
HMI PLC[RS-485]
Connect to Matsushita FP3 CPU Port
1 RXD-
Æ
9 TXA-
2 RXD+
Æ
2 TXB+
3 TXD-
Æ
10 RXA-
4 TXD+
Æ
3 RXB+
5 GND
Æ
7 GND
4 RTS+
Æ
5 CTS+
11 RTS-
Æ
12 CTS-
Shield
Æ
Earth Ground
Note:
Graphic representation may not reflect the actual appearance of the finished cable.
Summary of Contents for MMI-1500
Page 2: ...ii...