255
16.26 MITSUBISHI A1S, A2A, A2US, A3N/A1SH
16.26.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting Notes
PLC Type
MITSUBISHI A1S
MITSUBISHI A2A
MITSUBISHI A2US
MITSUBISHI A3n/A1SH
Serial I/F port
RS232
Baud rate
9600
Must match PLC port setting
Parity
Odd
Options: Odd, Even, None - Must match PLC port setting
Data bits
8
Options: 7, 8 - Must match PLC port setting
Stop bits
1
Options: 1, 2 - Must match PLC port setting
HMI station No.
0
Not used
PLC station No.
0
Not used
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
16.26.2 PLC Settings
Communication parameters must be the same as those of the MMI.
Compatible with:
Mitsubishi A Series: A1S, A2A, A2US and A3N/A1SH
16.26.3 Wiring
Use KEP Part#:
500_AnS
cable to connect HMI RS-232 port with Mitsubishi A Series CPU port.
Cable wiring not available.
16.26.4 Device address
Bit/Word
Type
Address Format
Range
Notes
B
X
hhhh
hhh: 0~FFFF
Input Relays, Addresses are in hexadecimal
B
Y
hhhh
hhh: 0~FFFF
Output Relays, Addresses are in hexadecimal
B
M
ddddd
ddddd: 0~65535
Auxiliary Relays
B
B
hhhh
hhhh: 0~ FFFF
Addresses are in hexadecimal
Note:
Not Available for A2US
B
F
ddddd
ddddd: 0~65535
Note:
Not Available for A2US
W
TV
ddddd
ddd: 0~65535
Timer Accumulator
W
CV
ddddd
ddd: 0~65535
Counter Accumulator
W
D
ddddd
dddd: 0~65535
Data Registers
W
W
hhhh
hhhh: FFFF
Addresses are in hexadecimal.
Note:
Not Available for A2US
W
R
ddddd
ddd: 0~65535
Note:
Not Available for A2US
Note:
The PLC’s memory range may vary within the range supported by the driver. Use appropriate addresses.