16.28 MITSUBISHI FX0n/2/2n COM, FX0n/FX2, FX2n, FX2n D(bit) [PDS]
16.28.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
Notes
PLC Type
MITSUBISHI FX0n/2/2n COM
MITSUBISHI FX0n/FX2
MITSUBISHI FX2n
MITSUBISHI FX2n D9bit0
[PDS V1.00]
Use with BD Communication Modules
mitsubishi(D_bit).pds
driver must be present in
\drivers
folder
Serial I/F port
RS485 4W
Options: RS232, RS485 2W, RS485 4W – Dependant on PLC
hardware
Baud rate
9600
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC
port setting
Parity
Even
Options: Odd, Even, None - Must match PLC port setting
Data bits
7
Options: 7, 8 - Must match PLC port setting
Stop bits
1
Options: 1, 2 - Must match PLC port setting
HMI station No.
0
Not used
PLC station No.
0
Options: 0-255
Note:
Must set PLC station when using a BD
Module
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC
requires a delay between requests. Not implemented in simulation
mode.
This driver supports Extended Address mode.
16.28.2 PLC Setting
Communication parameters must be the same as those of HMI (See recommendation above).
Compatible with:
Mitsubishi Models
Touchscreen Driver
FX0S FX0S-10 ~ FX0S-24
FXon/FX2
FX0N Series FX0N-24 ~ FX0N-60
FXon/FX2
FX0 Series FX0-14 ~ FX0-30Fxon
FXon/FX2
FX1S Supermicro FX1S-10 ~ FX1S-30
FXon/FX2
FX1N Supermicro FX1N-14 ~ FX1N-60
FXon/FX2
FX, FX2 & FX2C Series FX-16 ~ FX-128
FXon/FX2
FX2N Series FX2N-16 ~ FX2N-128
FX2n / FX2n D(bit)
FX2NC Supermicro FX2NC-16 ~ FX2NC-96
FX2n / FX2n D(bit)
BD Communication Module: FX2N-485-BD, FX2N-232-BD, FX1N-
485-BD and FX1N-232-BD
Note:
PLC station number (0~15) must be set when using the BD
Module.
Register D8120 setting: Set bit 9 and bit 8 of BFM#0 as 0
FX0n/2/2n COM