16.29 MITSUBISHI J2-S100
16.29.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting Notes
Serial I/F port
RS485 4W
Options: RS232, RS485 4W – Dependant on PLC hardware
Baud rate
9600
Options: 9600, 19200 - Must match PLC port setting
Parity
Even
Options: Odd, Even, None - Must match PLC port setting
Data bits
8
Must match PLC port setting
Stop bits
1
Must match PLC port setting
HMI station No.
0
Not used
PLC station No.
0
Options: 0~15 - Must match PLC port setting
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
16.29.2 J2-S100 Setting
Communication parameters must be the same as those of HMI (See recommendation above).
Compatible with:
MITSUBISHI J2-S100(MR-J2-10C) Servo
16.29.3 Wiring
16.29.3.1
Wiring for cable connections using
MITSUBISHI J2-S100
with RS422 MicroD 20 Socket ports.
KEP Part#: (Not Available) (D-Sub 9 Female Plug to MicroD Plug Cable)
HMI PLC[RS-485]
Connect to MITSUBISHI J2-S100 CN3 RS422 Port
2 RxD+
Æ
19 SDN-
1 RxD-
Æ
9 SDP+
4 TxD+
Æ
15 RDN-
3 TxD-
Æ
5 RDP+
5 GND
11 LG
Shield
Æ
Earth Ground
16.29.3.2
Wiring for cable connections using
MITSUBISHI J2-S100
with RS232 MicroD 20 Socket ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to MicroD Plug Cable)
HMI PLC[RS-232]
Connect to MITSUBISHI J2-S100 CN3 RS232 Port
2 TxD
Æ
2 RxD
3 RxD
Æ
12 TxD
5 GND
11 LG
Shield
Æ
Earth Ground
Note:
Graphic representation may not reflect the actual appearance of the finished cable.