265
16.30.3.3
Wiring for cable connections using
Entertron or Giddings & Lewis PiC9, PiC90, PiC900
CPU’s
with screw
terminal ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to Flying Leads Cable)
HMI PLC[RS-232]
Connect to Entertron or Giddings & Lewis
CPU with RS232 Port
2 TD
Æ
Æ
1 RD
3 RD
Æ
Æ
2 TD
5 GND
Æ
Æ
3 GND
Shield
Æ
Earth Ground
16.30.3.4
Wiring for cable connections using
Industrial Control Links ICL Series, SIXNET SIXTRAK
Gateway and VersaTrak RTU Controllers Compatible CPU’s
with RS-232 D-Sub 9 pin ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to D-Sub 9 Male Socket Cable)
HMI PLC[RS-232]
MODBUS COMPATIBLE CPU RS-232 port
2 TD
Æ
3 RD
3 RD
Æ
2 TD
5 GND
Æ
5 GND
4 DTR
Æ
6 DSR
7 RTS
Æ
8 CTS
Shield
Æ
Earth Ground
16.30.3.5
Wiring for cable connections using
International Parallel Machines CPU’s
with RS-232 D-Sub 9
Male Socket ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to D-Sub 9 Female Plug Cable)
HMI PLC[RS-232]
Connect to International Parallel Machines CPU with RS232 Port
2 TD
Æ
1 RD
3 RD
Æ
2 TD
5 GND
Æ
3 GND
7 RTS
Æ
8 CTS
Shield
Æ
Earth Ground
Summary of Contents for MMI-1500