16.35 OMRON CS/CJ [PDS]
16.35.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
Notes
PLC Type
OMRON CS/CJ Ver 1.01b
OmronCS_CJ.pds
driver must be present in
\drivers
folder
Serial I/F port
RS-232, RS485 2W
Options: RS-232, RS-485 default/2W/4W – Dependant on PLC
hardware
Baud rate
9600
Options: 9600, 19200 - Must match PLC port setting
Parity
Even
Options: Odd, Even, None - Must match PLC port setting
Data bits
7
Options: 7, 8 - Must match PLC port setting
Stop bits
2
Options: 1, 2 - Must match PLC port setting
HMI station No.
0
Not used
PLC station No.
0
Not used
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
Parameter 6
0
Error Report Register
This Parameter is the LW register number to hold any returned errors
from the OMRON CS/CJ controller. (For example: Setting this
parameter to 100, activates LW0100 as the error code register.)
Note:
Setting this parameter to 0 disables error reporting.
16.35.2 PLC Setting
Host Link Protocol Communication parameters must be the same as those of the HMI
Compatible with:
CS1Series: CS1G-CPU42EV1, 43EV1, 44EV1, 45EV1; CS1H-CPU63EV1, 64EV1, 65EV1, 66EV1, and 67EV1
CS1H Series: CS1G-CPU42H, 43H, 44H, 45H; CS1H-CPU63H, 64H, 65H, 66H, and 67H
CJ1 Series: CJ1G-CPU42, 43, 44, 45; CJ1H-CPU65, 66; CJ1W-SCU41
16.35.3 Wiring
16.35.3.1
Wiring for cable connections using
OMRON CS1 and CJ1 Series CPUs
with RS-232 Host Link D-
Sub 9 Female Plug ports.
KEP Part#:
SMICOMCQM-05
(D-Sub 9 Male Socket to D-Sub 9 Male Socket Cable)
HMI PLC[RS-232]
Connect to OMRON CS1 or CJ1 CPU RS-232 Host Link port
2 TD
Æ
3 RD
3 RD
Æ
2 TD
5 GND
Æ
9
Æ
9 GND
7 RTS
Æ
8 CTS
4 RS
Æ
5 CS
1
Æ
Shield
Æ
Earth Ground