285
16.38 Sharp JW Series [PDS]
16.38.1 HMI Setting -- SharpJW.pds driver must be present
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting Notes
PLC Type
SHARP JW Series [PDS
V1.00]
SharpJW.pds
driver must be present in
\drivers
folder
Serial I/F port
RS485 2W
Baud rate
19200
Must match PLC port setting
Parity
None
Options: Odd, Even, None - Must match PLC port setting
Data bits
7
Must match PLC port setting
Stop bits
1
Options: 1, 2 - Must match PLC port setting
HMI station No.
0
Not used
PLC station No.
1
Options: 0-255 - As per PLC setting, PLC default is 1
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
16.38.2 PLC Setting
Communication parameters must be the same as those of the MMI. PLC ID number must match setting in MMI.
Compatible with:
Sharp JW Series: JW10, JW-32CV1, JW-32CV2, JW-32CV3
16.38.3 Wiring
16.38.3.1
Wiring for cable connections using
Sharp JW Series CPUs
with RS485 Screw Terminal ports.
KEP Part#: (Not Available) (D-Sub 9 Female Plug to Flying Leads Cable)
HMI PLC[RS-485]
Connect to Sharp JW Series CPU General Purpose Communication Port
1 RXD- / TXD-
Æ
Æ
L2 RXD-
2 RXD+ / TXD+
Æ
Æ
L1 RXD+
Shield
Æ
Earth Ground
Note:
Graphic representation may not reflect the actual appearance of the finished cable.
16.38.4 Device address
Bit/Word Type Address Format
Range
PLC Mapping and Example
B
R
oooo(o) octal
oooo: 0~1577
o: 0~7
(A0000-A1577) R15777 is mapped to (A1577) bit 7
W
TC
ooo
ooo: 0~776
(B000-B0777)
TC2 is mapped to (b0002~b0003)
W
DM
ooo
oooo: 0~776
(09000-09777) D10 is mapped to (09010~09011)
oooo
oooo: 1000~1776
(19000-19777) D1006 is mapped to (19006~19007)
oooo
oooo: 2000~2776
(29000-29777) D2552 is mapped to (29552~29553)
oooo
oooo: 3000~3776
(39000-39777) D3776 is mapped to (39776~39777)
TC and DM addresses must be even numbers.