16.44 Toshiba T Serial
16.44.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting Notes
Serial I/F port
RS-232, RS-485(4W)
Options: RS-232, RS-485 default/2W/4W – Dependant on PLC hardware
Baud rate
9600
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC port
setting
Parity
Odd
Options: Odd, Even, None - Must match PLC port setting
Data bits
8
Must match PLC port setting
Stop bits
1
Options: 1, 2 - Must match PLC port setting
HMI station No.
0
Not Used
PLC station No.
1
Must match PLC port setting (0~255)
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
This driver supports Extended Address mode.
16.44.2 PLC Setting
Communication parameters must be the same as those of the MMI. Set PLC node ID.
Compatible with:
Toshiba T Series: T1, T2, T2E, T2N, T3, T3H, S2T
16.44.3 Wiring
16.44.3.1
Wiring for cable connections using
Toshiba T1 Series CPU’s
with RS232 Round 8 pin MiniDIN
ports.
KEP Part#:
SMICTSBT1-05
(D-Sub 9 Male Socket to 8 pin MiniDIN Male Plug Cable)
HMI PLC[RS-232]
Connect to Toshiba T1 Series CPU’s with RS232 Port
2 TXD
Æ
8 RXD
3 RXD
Æ
6 TXD
5 GND
Æ
9
Æ
3 GND
4 RTS
Æ
7 CTS
Shield
Æ
Earth Ground
16.44.3.2
Wiring for connections using
Toshiba T2/T3 Series CPU’s
with RS232 D-Sub 9 Female Plug ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to D-Sub 9 Male Cable)
HMI PLC[RS-232]
Connect to Toshiba T2/T3 Series CPU’s with RS232 Port
2 TD
Æ
2 RD
3 RD
Æ
3 TD
5 GND
Æ
5 GND
7 RTS
Æ
8 CTS
Shield
Æ
Earth Ground