293
16.44.3.3 Wiring for cable connections using
Toshiba T Series CPU’s
with RS422 D-Sub 15 Female Plug Link
ports.
KEP Part#: (Not Available) (D-Sub 9 Female Plug to D-Sub 15 Male Socket Cable)
HMI PLC[RS-485]
Connect to Toshiba T Series CPU’s with RS422 Port
1 RXD-
Æ
11 TXA
2 RXD+
Æ
3 TXB
3 TXD-
Æ
10 RXA
4 TXD+
Æ
2 RXB
5 GND
Æ
7 SG
5 RTSA
Æ
4 CTSA
13 RTSB
Æ
12 CTSB
Shield
Æ
Earth Ground
16.44.3.3 Wiring for cable connections using
Toshiba S2T Series CPU’s
with RS485 Screw Terminal Link
ports.
KEP Part#: (Not Available) (D-Sub 9 Female Plug to flying leads Cable)
HMI PLC[RS-485]
Connect to Toshiba S2T Series CPU’s with RS422 Port
1 RXD-
Æ
2 TXB
2 RXD+
Æ
1 TXA
3 TXD-
Æ
5 RXB
4 TXD+
Æ
3 RXA
5 GND
Æ
6 SG
Shield
Æ
Earth Ground
Note:
Graphic representation may not reflect the actual appearance of the finished cable.
16.44.4 Device address
Bit/Word Type
Address Format
Range
Notes
B
X
ddddh
ddd: 0~9999 h: 0~F
Input Relays, Word portion is decimal, bit portion is
hexadecimal
B
Y
ddddh
ddd: 0~9999 h: 0~F
Output Relays, Word portion is decimal, bit portion is
hexadecimal
B
R
ddddh
ddd: 0~9999 h: 0~F
Internal Relays, Word portion is decimal, bit portion is
hexadecimal
B
S
ddddh
ddd: 0~9999 h: 0~F
Special Relays, Word portion is decimal, bit portion is
hexadecimal
W
T
dddd
ddd: 0~9999
Timer Registers
W
C
dddd
ddd: 0~9999
Counter Registers
W
D
ddddd
dddd: 0~9999
Data Registers
W
SW dddd
ddd: 0~9999
Special Bits as Words