16.46 Yokogawa PLC Series [PDS]
16.46.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting Notes
PLC Type
YOKOKAWA Series
[PDS V1.04]
Yokogawa.pds
driver must be present in
\drivers
folder
Serial I/F port
RS-232
Options: RS-232, RS-485 default/2W/4W – Dependant on PLC
hardware
Baud rate
19200
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC port
setting
Parity
Even
Options: Odd, Even, None - Must match PLC port setting
Data bits
8
Options: 7, 8 - Must match PLC port setting
Stop bits
1
Options: 1, 2 - Must match PLC port setting
HMI station No.
0
Not Used
PLC station No.
1
Options: 0~255 - Must match PLC setting
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
16.46.2 PLC Setting
Communication parameters must be the same as those of the MMI. Additionally, Select Use Personal Communication
Link, Use checksum, and Use End Character.
Compatible with:
Yokogawa: FA-M3 series
16.46.3 Wiring
16.46.3.1
Wiring for cable connections using
FA-M3 series CPUs
with RS232 D-Sub 9 Male Socket ports.
KEP Part#:
ZA9M9F
(D-Sub 9 Male Socket to D-Sub 9 Female Plug Cable)
HMI PLC[RS-232]
Connect to VIGOR: M Series, V Series, VB Series CPU
RS-232 port
2 TD
Æ
2 RD
3 RD
Æ
3 TD
5 GND
Æ
5 GND
Shield
Æ
Earth Ground
Note:
Graphic representation may not reflect the actual appearance of the finished cable.