3.
Installation and startup
When you received the luminaire, please remove the packaging and check whether the luminaire
is intact and complete, without any detectable injuries. Please follow the installation instructions
provided with due care, to ensure proper operations. Please do not make any alterations to the
Product, as any alteration made will result in the Warranty provided being terminated, or lead to
hazard! The Manufacturer or Distributor refuses to take any liability for any appliance being tampered
with, or incorrectly installed!
Steps of installation:
1.
The weight of the luminaire is 5 kg, the overall dimensions are shown on Figure 3. To serve
its core function, the luminaire is to be mounted on the ceiling, with the optical part of the
luminaire (see Figure 2/8: “glass optical lens”) facing downward, vertically. With various
attachments the luminaire could be mounted on side walls, light poles or pipe bridges. Once
you removed the packaging, please protect the glass optics (Figure 2/8) from any mechanical
injury, and avoid touching it with bare hands. If you see any pollution on the glass, please
clean it with a soft, absorbent piece of cloth, or detergent!
2.
Please untighten the “fixture-fixing screws” shown on Figure 1, then pull the luminaire from
the “fixture-hanging bracket”, to the direction shown on Figure 1.
3.
Mount the “fixture-hanging bracket” to the ceiling, or to a stand already created for such
purposes. The fixture-hanging bracket is made of stainless steel of 1.4301 material quality,
being 1.5 mm thick. The fixture-hanging bracket has two bore-holes of 8.5 mm diameter
each, with the dimensions shown on Figure 3. Please use both mounting bore-holes to fix the
plate properly! The plate can be fixed into place with the use of either screws, a wire or chain.
Optionally, other attachments can also be fixed to the fixture-holder bracket, such as a pipe
cluminaire, which enables fixing to pipe bridges, or to light poles. If you fix it with a screw,
please use 6 or 8 mm diameter fasteners, of A2 or A4 material quality, which are suitable for
bear the weight of the luminaire in the given ceiling or wall material. If you use a wire, please
use a minimum 2 mm diameter stainless steel wire. If you use a chain, please use hot dip
galvanized or stainless chain, of at least 4 mm wire diameter. If you wish to mount any other
fixtures or appliances to the luminaire, please always consult with the Manufacturer or
Distributor of the luminaire. Please always make sure that the “fixture-holding bracket” is
properly and securely fixed to the given surface. The manufacturer of the luminaire refuses
to take any liability for any potential financial or personal damages arising due to a loose or
improper mounting or fixing of the luminaire!
4.
Once the “fixture-holding bracket” is in place, mounted to the ceiling or the wall, please check
whether it is safe enough to hold the weight of the fixture, at the desired place. Slide the
luminaire back onto the “fixture holding bracket”, keeping the “fixture-fixing screws” on it.
Please check whether the positioning of the 2 “fixture-fixing screws” are ok, and how they
are fixed is appropriate, on the “fixture-holding bracket”. Securely tighten the 2 “fixture-
fixing screws”, manually. Check whether the luminaire is properly attached and fixed onto
the “fixture-holding bracket”.
5.
Connect the 3x1.5 mm2 diameter electric power cord coming out from the cable gland to the
electrical network, in line with the applicable standards and environmental conditions. The
luminaire shall be connected to a 230V AC, 50Hz electrical network. The luminaire has a