Kermann Technical Developer and Consulting Ltd.
Phone:
(+36) 1 445 1670
E-mail:
6
CLASS 1 electric protection (protected earth), and its nominal power consumption is 55W, at
maximum output level. The size and type of cable coming out of the electrical cable gland:
H05VV-F, 3x1.5 mm2 x 3m flexible PVC cable. Please lead the electrical power supply cable
leading out of the luminaire taking into account the specific environmental conditions, and
protect it from mechanical impacts.
6.
The electrical power cord of the dimmable version is: H05VV-F 5x1 mm2 x 3m flexible PVC
coated cable. The dimming signal must be connected to the 2 dedicated dimming wires of
the cable. If the dimming signal is produced in the hazardous area, the dimming system must
be designed and installed in accordance with the standards of the hazardous area.
7.
When connecting and installing the luminaire, make sure that the electric power cord, and
the LED cable is not too tight, no load is placed on it, and that it is not broken. The minimum
bending radius shall be 6 times the cable sheath diameter.
8.
Once the luminaire is connected to the electrical network - and once the electrical network
is under 230VAC electrical voltage - the luminaire is switched on, and the light source will
emit a consistent level of light, subject to the radiation angle, depending on the type of optics
used. If any vibration or flashing is experienced, please check the electric power cord
connection. If the defect does not stop, and you did not find any contact problem in the
connection, please unplug the luminaire from the electrical network, and call our technical
department!
9.
The luminaire inrush current is 55A, for a duration of 270 µs at the maximal output power.
Please take that into due consideration when installing your electric network. The luminaire
shall solely be installed and connected into the electrical network by a properly trained and
authorised specialist!
Figure 3.: Key geometric dimensions of the luminaire