KD GEMINI – INSTALLATION/OPERATION MANUAL
KD Gemini
May-06
13
OPENING HEIGHTS
from floor
Burner c/l
11 5/8” (295 mm)
Smoke pipe c/l
39 3/16” (995 mm)
SMOKE/VENT PIPE CONNECTIONS
5”
Chimney
4”
Direct Vent
CLEANOUTS
View port, Front Cleanout, Smoke pipe and Burner opening
AIR FILTERS
20” x 24” x 1”
FUEL
not heavier than No. 2 furnace oil.
ELECTRICAL
120 Volts, 60 Hz
Canada
Less than 12 amps.
USA
13.3 amp, circuit protection 20 amps.
This furnace has been tested to and meets the requirements of B212-93 Seasonal
Energy Utilization Efficiencies of Oil-Fired Furnaces & Boilers & the Energy-Efficient
Appliances Act of 1991.
Certified for use with Type “A” or Type “L” vent – maximum flue gas temperature 575°F.
Certified for use with Kerr Direct Vent.
Certified for use with Kerr KPV-SS1C through-the-wall mechanical vent system.
10.0 TROUBLE SHOOTING GUIDE
Furnace will not start
Tripped blocked vent switch
Clear vent, reset switch.
Tripped breaker
Determine cause, reset breaker.
Blown fuse
Replace fuse.
No oil
Check tank for leaks and call oil supplier.
Oil burner keeps turning off
Dirty air filter
Change air filter.
Restricted air supply/return
Check all air return/supply registers.
Limit control
Check ductwork for blockage.
Motor over heating
Check motor speed for correct nozzle on furnace
label settings.
Dirty nozzle
Call technician to replace nozzle.
Sooty flame
Wrong pump pressure
Increase or decrease pressure to correct setting.
Dirty nozzle
Replace nozzle.
Improper burner setting
See “BURNER SPECIFICATIONS”
.
Barometric draft wrong
Adjust barometric regulator for -0.04” wc draft
pressure at breech.