KD GEMINI – INSTALLATION/OPERATION MANUAL 

 

KD Gemini

 

 

 

May-06 

14

Using too much oil 

Oil leak in line or tank 

Check fittings for tightness.  Inspect tank and replace 
if necessary. 

Draft regulator set high 

Adjust regulator for  -0.04” wc draft pressure at 
breech. 

Nozzle too large  

 

 

Replace nozzle to lower input. 

 

Burner reset cuts out 

No oil 

 

 

 

Call oil supplier. 

Frozen oil line 

 

 

 

Call technician or oil supplier. 

Dirty oil filter 

 

 

 

Replace filter. 

Dirty nozzle, smoky fire 

 

Replace nozzle, adjust burner air. 

Faulty oil pump   

 

 

Have pump replaced, adjust burner air. 

Faulty or dirty electrodes   

Have technician clean or replace. 

 

Warm air register blowing cold air 

Basement cooling ducts 

Insulate and seal ductwork to maintain duct 
temperature. 

Ducts running through  

 

Change or insulate ductwork. 

Unheated spaces 
Low speed switch is on 

Switch off blower low speed. 

“FAN OFF” set low 

Fan control – Set “FAN OFF” higher. 

Motor speed set too high   

Reset motor speed to slow blower. 

 

Warm air registers blowing too hot 

Blower running slow  

 

Speed blower up. 

Return air restricted 

Open up return air ductwork to ensure adequate 
airflow. 

Nozzle too large  

Lower nozzle size to suit ductwork. 

 

All rooms at different temperatures 

Supply air not regulated    

Adjust warm air regulators to suit each room. 

Return air not regulated    

Check for sufficient return air. 

 

Noisy operation 

Loose blower wheel  

 

Tighten wheel set screw or replace. 

Blower wheel hitting housing 

Center wheel in housing. 

Damaged motor bearings   

Replace blower motor. 

Faulty oil pump   

Repair or replace oil pump. Reset to correct pressure.  

Air leak in oil line 

 

 

Tighten all connections. 

Vacuum too high on pump 

Check pump vacuum.  Check filters and pump 
screen. 

 
 
 
 
 
 
 
 
 
 

Summary of Contents for KD Gemini

Page 1: ...AT MAY DIFFER FROM THIS MANUAL Please read this complete manual before beginning installation These instructions must be kept with the furnace for future reference CERTIFIED TO CAN CSA Std B140 0 Std...

Page 2: ...ement Venting Ventilation 5 3 5 Installation 5 3 6 Assemble Install Burner 6 3 7 Changing Nozzle 6 3 8 Set Up Burner For Efficient Operation 7 3 9 Blower Settings 8 3 10 Cooling AC Models 8 3 11 Humid...

Page 3: ...se new approved disposable filters of the same size and type or clean permanent filters according to manufacturer s instructions Replace the filters or clean the filters more often if dusty conditions...

Page 4: ...hat has been shut down for an extended period of time INSPECTION Have the furnace system serviced and inspected by a qualified technician CHECK Furnace system has not been tampered with FUEL ON Turn o...

Page 5: ...ANY OTHER APPLIANCE 3 3 INSTALLATION CODES INSTALLATION MUST COMPLY WITH THE REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION All local and national codes governing the installation of oil burning equ...

Page 6: ...g decal for approved vent flue pipe sizes Maximum flue gas temperature is 575 F THROUGH THE This Furnace is approved for Kerr Direct Vent WALL VENTING COMBUSTION Install openings and ductwork to the f...

Page 7: ...heck for clean seating and tighten in nozzle adaptor CHECK See burner manufacturer s instructions for correct setting ELECTRODES INSERTION See GENERAL SPECIFICATIONS or diagram Figure 1 LENGTH MOUNT B...

Page 8: ...a stable symmetrical flame After 15 minutes of normal operation check SMOKE for 0 trace reading and measure CO2 Re adjust the burner controls as required When the burner is set lock the adjustments wi...

Page 9: ...nty 3 12 THERMOSTAT ANTICIPATOR SETTING Thermostat anticipator setting should be 0 2 amps for any burner Check that the thermostat anticipator setting matches the primary control circuit current draw...

Page 10: ...struction and the heating system tested on a long burn cycle 7 If the block vent switch shuts down the system check to ensure there is enough draft in the chimney and venting pipes 3 14 FAN CONTROL LI...

Page 11: ...tight as possible Use a pipe joint compound suitable for oil on all pipe threads To reduce possibility of air leaks tighten stem packing gland nut on any valves installed in the suction line Also be s...

Page 12: ...5 2 84 0 60 60B 3 5 0 0 88 000 26 850 950 4 3 0 92 3 48 0 75 60W 150 5 0 1 5 105 000 31 1080 1200 3 2 KDF R E 115 A3 Riello 40 F3 1 00 3 81 0 75 60W 175 5 0 1 5 116 000 34 1080 1300 3 1 KDF R E 130 A3...

Page 13: ...2 wc External static AC 0 5 wc Cooling Air Flow 3 tons Maximum air temperature rise 85 F Fan Control 130 F ON 100 F OFF High Limit max design outlet temp 200 F 1 3 hp 1 speed 0 50 static 1300 CFM MOT...

Page 14: ...fied for use with Kerr Direct Vent Certified for use with Kerr KPV SS1C through the wall mechanical vent system 10 0 TROUBLE SHOOTING GUIDE Furnace will not start Tripped blocked vent switch Clear ven...

Page 15: ...hrough Change or insulate ductwork Unheated spaces Low speed switch is on Switch off blower low speed FAN OFF set low Fan control Set FAN OFF higher Motor speed set too high Reset motor speed to slow...

Page 16: ...__________________________ START UP TEST RESULTS Nozzle ________________________________________ Pressure _______________________________________________ Air __________________________________________...

Page 17: ......

Page 18: ...KDF 14A Filter Frame Assembly K00 CB 0025 00 KDF 15 Rear Cabinet Top KD KC KD0 CB 0020 00 KDF 16 Blower Door 3BU 10 00DD 00 KDF 17 Delhi GT10 DD Blower 4CA 00 505M 23 KDF 18A Motor Run Capacitor 5 mi...

Page 19: ......

Page 20: ...KDR 14A Filter Frame Assembly K00 CB 0024 00 KDR 15 Rear Cabinet Top KD0 CB 0020 00 KDR 16 Blower Door K00 CB 0103 00 KDR 17 5 Flue Pipe Collar 3BU 10 00DD 00 KDR 18 Delhi GT10 DD Blower 4CA 00 505M 2...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Reviews: