background image

25

4.3.7.  "Dry_in" terminals, remote on-oFF (0,7 

to 3 kVA equipments only)

•  The equipments from 0,7 to 3 kVA have a 4 pins connector, two 

for the EPo (see the description in the previous section) and two 
for remote start up or shutdown "Dry_in".

•  Through these terminals, an external button can be connected, 

with the same function that the own in the UPS.

•  when pressing, over it for 1 second, the circuit will activate the 

opposite order of the current status of the inverter, so, if it is shut-
down then it will be started up and vice versa, if the inverter is 
started up then it will be shutdown (see figure 14).

External button, normally open.
it is activated with an order of 1 
second pulsation.

1

4

+ VDC

EPo

Dry_in

Fig. 14.  button installation in the "Dry_in" terminals.

4.3.8.  "Dry_out" terminals, dry contact for 

alarm (0,7 to 3 kVA equipments only)

•  The equipments from 0,7 to 3 kVA are supplied with a normally 

open dry contact "Dry_out", which is closed when activating of 
any one or more associated alarms "Summary Alarm" from Table 
4.

• 

 Do not apply more than 30V AC 1A or 60V DC 2A. Dry 
contact, do not connect both phases between the con-

tacts, because there would be a short-circuit when triggering the 
alarm because the circuit is closed.

1

2

4

3

Dry contact, do not apply voltage 

Fig. 15.  Dry contact "Dry_out".

bUS over Voltage

inv Under Voltage

bUS Under Voltage

inv Softstart Fail

bUS Unbalance

output overload

bUS Short

inv overload Fault

bUS Softstart Fail

byp overload Fault

output Short Circuit

Heatsink over temperature

inv over Voltage

-

Tab. 2. 

Associated alarms to "Summary alarm" for Dry_out contact.

4.3.9.  Connection in parallel

4.3.9.1.  introduction to the redundancy

n+1 is usually a reliable power structure. n means the minimum quan-
tity of equipments that the total load needs, so 1, and 1 means the quan-
tity of redundant equipments, so it means, the quantity of faulty UPSs 
that the system can allow at the same time. 

KESSUPS 91RT series allows two equipment connected in parallel 
only, for those models with power rate between 4  and 10 kVA, in 
order to set a shared output and redundant in power.

4.3.9.2.  installation and parallel operating (4 to 10 kVA 

equipments only)

• 

 Communication line (CoM) is a very low voltage circuit of 

safety. To preserve the quality, it has to be installed separate 

from other lines that have dangerous voltages (energy distribution 
line).

•  Parallel connection bus. Use the bundle with 15 signal cables with 

mesh and HD15 connectors in the ends to joint up to 2 equip-
ments as maximum. Each bundle has a male and female con-
nector in the ends, which will have to be connected to joint both 
equipments. it is essential to close the loop of the parallel bus.
The length of the parallel cable has 3 metres and it can't be ex-
tended under any other concept due to the risk of interferences 
and communication failures that it could cause.

•  The installation of the parallel systems, has to be provided by a 

switchgear panel with individual protections for input, output 
and static bypass (this last one, in those installations that uses the 
second line only), also a manual bypass with mechanical lock, see 
figures 16 and 17.
This switchgear panel allows isolating only one equipment from the 
system, against any failure and feed the loads with the rest of equip-
ments during the preventive maintenance or its fixing. in the same 
way, it allows removing an equipment in parallel and replace it or put 
it in parallel again once it is fixed, but without breaking the power 
supply to the loads meanwhile the connected power can be sup-
ported by the operative equipment.
Under request a manual bypass panel can be supplied for a single 
equipment or a system of two equipments in parallel.

•  Respect the connection procedure for input and bypass described 

in the previous sections of this chapter.

•  Respect the established procedure to make the connection of the 

battery modules for those equipments with extended back up 
time, which has been described in the previous sections of this 
chapter.

•  Respect the established procedure to make the connection of the 

output (loads), which has been described in the previous sections 
of this chapter.

•  Respect the established procedure to make the connection of the 

output and batteries of the equipment, which has been described 
in the previous sections of this chapter.

• 

in parallel systems, the length and cross section of the ca-
bles that go from the switchgear panel till one of the UPSs 

and vice versa, will be the same for all of them without any excep-
tion.

Summary of Contents for KESSUPS 91RT

Page 1: ...UPSseriesKESSUPS91RT 700VA 10kVA Uninterruptible Power Supply User s manual...

Page 2: ...3kVAequipmentsonly 4 3 8 Dry_out terminals drycontactforalarm 0 7to3kVAequipmentsonly 4 3 9 Connectioninparallel 4 3 9 1 Introductiontotheredundancy 4 3 9 2 Installationandparalleloperating 4to10kVAeq...

Page 3: ...amage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic instructionsandfeaturesfortheequipmentsafety Tonotrespect these indications can c...

Page 4: ...UPSdrivestheleakagecurrentof theloaddevices Anisolatedearthcablehastobeinstalledas part of the circuit that supplies the equipment Cross cable section and its features will be same as the power supply...

Page 5: ...art from the implicit stated risks any action that make the modification internal or external of the equipment or just only the simple intervention inside of itself which is not stated in this documen...

Page 6: ...y from the equip ment in another cabinet case or rack with the interlink cables among them Do not modify its length In those equipments requested without batteries their acquisi tion installation and...

Page 7: ...the event of any modification or intervention in the product by the cus tomer s side This is a product for its use in commercial and industrial ap plications so restrictions and additional measures c...

Page 8: ...91RT models from 4 to 6 kVA 3HE from 8 to 10 kVA 5HE Battery module from 0 7 to 3 kVA Battery module from 4 to 6 kVA 3HE from 8 to 10 kVA 5HE Fixing screws Front cover Fixing screws Front cover Fixing...

Page 9: ...put terminals IEC AC outlets LS2 Modelsfrom0 7to2kVAstandard USB COM port RS232 COM port IEC inlet for AC power supply Main earth for battery module Connectorfor remoteON OFF Auxiliary contact connect...

Page 10: ...other module Battery module for equipments from 0 7 to 3 kVA Earth bonding terminal to be connected to the equipment and with other module Battery module for equipments from4 to 6 kVA The connection o...

Page 11: ...rface or SNMP for controlling the equipment via Internet Intranet Models from 4 to 10 kVA allow the parallel connection of a second equipment of the same features for a redundant configuration or to i...

Page 12: ...SNMP adapter The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of control ling and management at the manager system disposal Th...

Page 13: ...ing C characteristic for circuit breaker Regardingthesize theywillbeasminimumtothecurrentsstated in the nameplate of each UPS In the nameplate of the equipment there are only printed the nominal curre...

Page 14: ...only 1 metallic piece and bolt to joint the battery module with the equipment on tower format Once the reception is finished it is advisable to pack the UPS and the battery module s again till its com...

Page 15: ...nofthispowerrangeintherackcabinetwhenthemanipula tionsaredonebyhand thebatteryblockhastoberemovedfrom the equipment Proceedasfollowstoremovethebatteryblockorpack basedon one pack for 4 to 6 kVA models...

Page 16: ...r side of the equipment see figure 11 All the instructions relating to connections will detailed later on less those ones regarding the battery connection Therefore this section will only describe the...

Page 17: ...ment vertical There are no supports or stabilizers A A B Fig 7 Vertical tower type assembling 4 2 5 3 Vertical tower type assembling with extended back up time battery module The description of this s...

Page 18: ...8 Model in vertical tower type assembling with extended back up time battery module Regarding the connections of the UPS with the battery module in models up to 6 kVA make the following steps but rea...

Page 19: ...frame of the cabinet by means of the screws B 4 2 5 5 19 rack cabinet assembling with extended back up time battery module This section describes a single equipment with only one battery module see fi...

Page 20: ...seconnectortoconnectitwith anotherbatterymodule Socketforbattery module Wireofbatterymodule Fig 11 Batterymoduleconnectionfor8and10kVAequipments 4 3 Connection Cross cable section used in the power su...

Page 21: ...t the circuit diagram of the particular Backfeed protection for the equipment without bypass line There can be no derivation in the line that goes from the Backfeed protection to the UPS as the safety...

Page 22: ...2 and respect the circuit diagram of the par ticular Backfeedprotection fortheequipmentwithbypassline There can be no derivation in the line that goes from the Backfeed protection to the UPS as the sa...

Page 23: ...the load connected to the respective outlet has to be checked otherwise the protection will be activated and deactivated cyclically and therefore the loads will suffer the consequences For hardwired...

Page 24: ...ting the power supply to the input power block Make sure that all the loads connected to the UPS are only con nectedtotheprotectiveearthbondingterminal Thefactof not restricting the earthing of the lo...

Page 25: ...3 9 2 Installationandparalleloperating 4to10kVA equipmentsonly Communication line COM is a very low voltage circuit of safety Topreservethequality ithastobeinstalledseparate from other lines that have...

Page 26: ...s the difference in the length between the input and output cables of the equipments has to be lower than 10 Input circuit breakers Output circuit breakers Manual bypass UPS nr 1 Input To loads UPS nr...

Page 27: ...other machines or devices through the 5 dry contacts supplied in the terminal strip included in the same card and to each one of them an alarm of the 8 available can be as signed see table 6 Also the...

Page 28: ...of the monitoring software 4 3 12 Considerations before starting up the connected loads It is recommended to charge the batteries for 2 hours as minimum before using the UPS for first time When sup p...

Page 29: ...3 seconds to shut down the inverter The acoustic alarm will beep for 3 sec The equipment will be established on Bypass mode When finishing the previous action there is still voltage at the UPS output...

Page 30: ...hrough the bypass Turn On the output circuit breaker switch of the distribution panel corresponding to the new integrated equipment The complete parallel system will supply output voltage through the...

Page 31: ...tem again 6 Control panel with LCD 6 1 Control panel Fig 20 Control panel view Button Function Description Inverter start up With no AC power supply and battery connected to the equipment press the bu...

Page 32: ...te In ECO mode Blue 65 State In converter mode Blue 71 Warning EPO active Blue 72 Warning On maintain Bypass only models of 4 10 kVA Blue 81 Fault Heatsink over temperature Red 82 Warning Ambient over...

Page 33: ...passwithoutputvoltagescreen Bypass without output voltage The UPS is running on bypass mode without output voltage Fig 25 Bypasswithoutoutputvoltagescreen ECO mode Once the UPS is started up the energ...

Page 34: ...se the UPS could fail Fig 28 Warningscreen Fault When a fault occurs it reveals that some serious problems have happened the UPS will break the output voltage or will transfertobypassandthealarmwillbe...

Page 35: ...ame main screen when pressing the key for more than 1 sec the Structure of the main menu will be displayed see figure 33 Todisplaythedifferentsubmenus pressthekeys or forless than 1 sec considering th...

Page 36: ...see figure 34 Whenpressingthekey formorethan1sec theLCDwillshow the UPS status screen of the main menu structure again Press 1 sec Press o 1 sec Event logger structure menu Main menu structure Press...

Page 37: ...ter When pressing the key for more than 1 sec the LCD panel will display the screen Event log from the main menu structure again Control submenu for 0 7 to 3 kVA models 6 3 4 Measurement submenu When...

Page 38: ...is single or it is parallel and power supply to load s is broken To restore the normal condition the EPO button has to be de activated previously close the circuit again and enter into the ClearEPOsta...

Page 39: ...ctions that could satisfy a special ap plication of the user In case you require any of these special functionalists contact the KESS Support Team to change the standard configuration from fac tory 6...

Page 40: ...as battery has to be charged every 2 months The charging time has to be 12 hours as minimum Under normal conditions the battery lifetime is from 3 to 5 years at20 C Eurobat Ahighertemperaturecancaused...

Page 41: ...ment is too high Check the UPS cooling and ambient temperature of the room 93 Back Feed only 3 kVA On battery mode bypass has voltage Transfer to manual bypass and consult our KESS Support Team Do not...

Page 42: ...9 Troubleshooting guide Warning indications 7 2 3 Troubleshooting guide Other circumstances Circumstance or condition Possible cause Solution Code DescriptionintheLCDpanel 01 Bypass Abnormal Bypass p...

Page 43: ...ered product UPS KESSUPS 91RT series 7 4 Description of the available maintenance and service contracts For the UPS series KESSUPS 91RT additional warranty services are available as an option Also pre...

Page 44: ...62040 3 non linear load Transient recover time of the output voltage with load step 0 100 0 9 Transient recover time of output voltage with load step 20 100 20 6 Frequency With mains present synchron...

Page 45: ...emperature 15 50 C Storage temperature without batteries 20 70 C Operating altitude 1000 m a s l for high altitude correct it according to table 14 Relative humidity 0 95 non condensing Protection deg...

Page 46: ...KESS Power Solutions GmbH Gentzgasse 55 A 1180 Wien T 43 0 1 4704731 0 info kess at www kess at MA_16_03_KESSUPS_91RT_E...

Reviews: