background image

30

5.4. 

How to replace a faulty UPS in a 

parallel system

 

ˆ

Press over the key   in any UPS for more than 3 seconds to 
shutdown all the inverters. The acoustic alarm will beep for 3 
seconds. The equipments that belong to the current parallel 
system will transfer to "bypass mode".

 

ˆ

Put all the equipments on manual bypass. To do it remove 
the cover from manual bypass switch, which is located at the 
back of each equipment and turn all the switches to position 
"byPASS".

 

ˆ

 

Keep in mind that on "bypass mode" or with the 
switch on position "byPASS", the loads will be ex-

posed to fluctuations of voltage, frequency and mains faults 
or blackouts, so in case it is possible choose one day with the 
lowest probability of faults (days without fluctuations, days 
without storms,... ) and do it as fast as possible.

 

ˆ

Turn "off" the input, output and bypass circuit breaker pro-
tections (this last one when it is available) from the protection 
panel and corresponding to the equipment to replace.

 

ˆ

Disconnect the communication bus and all power connec-
tions, and remove it. in equipments installed as rack, remove 
the screws  that fix it to the cabinet previously.

 

ˆ

Put the manual bypass switch of the new UPS, to position 
"byPASS". To do it remove the protection cover of the manual 
bypass located in the rear side and act over itself.

 

ˆ

Put the new equipment that replaces the faulty one and re-
connect it. Follow the instructions stated in section 4.3.9.2, to 
connect them in parallel.
For equipments installed as rack, put the screws that fix it to 
the cabinet previously.

•  Turn "on" the input and bypass circuit breakers (this last one, if 

it is available) from protection panel, and corresponding to the 
new UPS.
UPSs supply output voltage from bypass. Check the lCD from 
control panel in case there were any warning or error information.
Measure the output voltage of the new UPS, check the voltage 
difference is below 1 V. in case the difference were higher than 1 
V, double check the wiring and associated instructions.

•  Put back the cover of the manual bypass of each UPS.
•  Press over the start up key   for more than 3 sec. in any of the 

UPSs and all of them will start up. All UPSs will transfer to "normal 
mode”.
Measure the output voltage in the power blocks of the parallel 
system and the output terminals of the new UPS, to check the 
voltage difference is under 0,5 V. in case the difference were 
higher than 1 V, the UPSs have to be set (contact the KESS Sup-
port-Team).

•  Press over the shutdown key   in any UPS for more than 3 sec-

onds and each one will be shutdown, supplying output voltage 
through the bypass.
Turn “on” the output circuit breaker switch of the distribution 
panel, corresponding to the new integrated equipment. The 
complete parallel system will supply output voltage, through the 
bypass.

•  Remove the cover of the manual bypass in each UPS.
•  Transfer the equipments with the manual bypass ("byPASS" po-

sition) to position "UPS". Do it in the switches of all equipments.

•  Put back the protection cover of the manual bypass switch of all 

equipments, also check the torque of the fixing screws, otherwise 
any of the limit contacts of this cover could be activated and the 
manual bypass too.

•  Press over the start up key   for more than 3 sec. in any of the 

UPSs and all of them will start up, finally the parallel system will 
be working on "normal mode”.
load/s are running and protected by the parallel system again.

5.5.  Manual bypass Switch (maintenance)

5.5.1. 

operating principle

integrated manual bypass in all UPS from KESSUPS 91RT from 4 to 
10kVA is available, but a wrong use can cause irreversible conse-
quences for both the UPS and connected loads at its output. There-
fore, it is important to respect the manoeuvring of the switch as it is 
stated in the following sections.

5.5.2.  Transference to maintenance bypass

•  The procedure to transfer from normal mode to maintenance by-

pass is the same for a single equipment or a parallel system, less 
the quantity of actions:

 

ˆ

For a single equipment.

 

– Press over the key   of the UPS for more than 3 seconds 

to shutdown the inverter. The acoustic alarm will beep for 
3 seconds. The equipment will transfer to "bypass mode".

 

ˆ

For a parallel system.

 

– Press over the key   in any UPS for more than 3 seconds 

to shutdown all the inverters. The acoustic alarm will 
beep for 3 seconds. The equipments that belong to the 
current parallel system will transfer to "bypass mode".

 

ˆ

Put all the equipment/s on manual bypass. To do it remove 
the cover from manual bypass switch, which is located at the 
back of each equipment and turn all the switch to position 
"byPASS.
in parallel systems, proceed in the same way in each equip-
ment.

 

ˆ

 

Keep in mind that on "bypass mode" or with the switch 
on "byPASS" position, the loads will be exposed to fluc-

tuations of voltage, frequency and mains faults or blackouts, so 
in case it is possible, choose one day with the lowest probability 
of faults (days without fluctuations, days without storms,... ) and 
do it as fast as possible.
The UPS still supplies output voltage, from mains directly or 
through the static bypass line (in those installations that it is 
available), through the manual bypass of the equipment.

 

ˆ

Also, if the protection panel has manual bypass switch, re-
move the mechanical lock and turn the switch "on" (byPASS).
in this case and in this case only, turn the output switch/es 
from distribution panel to "off", depending if there is only 

Summary of Contents for KESSUPS 91RT

Page 1: ...UPSseriesKESSUPS91RT 700VA 10kVA Uninterruptible Power Supply User s manual...

Page 2: ...3kVAequipmentsonly 4 3 8 Dry_out terminals drycontactforalarm 0 7to3kVAequipmentsonly 4 3 9 Connectioninparallel 4 3 9 1 Introductiontotheredundancy 4 3 9 2 Installationandparalleloperating 4to10kVAeq...

Page 3: ...amage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic instructionsandfeaturesfortheequipmentsafety Tonotrespect these indications can c...

Page 4: ...UPSdrivestheleakagecurrentof theloaddevices Anisolatedearthcablehastobeinstalledas part of the circuit that supplies the equipment Cross cable section and its features will be same as the power supply...

Page 5: ...art from the implicit stated risks any action that make the modification internal or external of the equipment or just only the simple intervention inside of itself which is not stated in this documen...

Page 6: ...y from the equip ment in another cabinet case or rack with the interlink cables among them Do not modify its length In those equipments requested without batteries their acquisi tion installation and...

Page 7: ...the event of any modification or intervention in the product by the cus tomer s side This is a product for its use in commercial and industrial ap plications so restrictions and additional measures c...

Page 8: ...91RT models from 4 to 6 kVA 3HE from 8 to 10 kVA 5HE Battery module from 0 7 to 3 kVA Battery module from 4 to 6 kVA 3HE from 8 to 10 kVA 5HE Fixing screws Front cover Fixing screws Front cover Fixing...

Page 9: ...put terminals IEC AC outlets LS2 Modelsfrom0 7to2kVAstandard USB COM port RS232 COM port IEC inlet for AC power supply Main earth for battery module Connectorfor remoteON OFF Auxiliary contact connect...

Page 10: ...other module Battery module for equipments from 0 7 to 3 kVA Earth bonding terminal to be connected to the equipment and with other module Battery module for equipments from4 to 6 kVA The connection o...

Page 11: ...rface or SNMP for controlling the equipment via Internet Intranet Models from 4 to 10 kVA allow the parallel connection of a second equipment of the same features for a redundant configuration or to i...

Page 12: ...SNMP adapter The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of control ling and management at the manager system disposal Th...

Page 13: ...ing C characteristic for circuit breaker Regardingthesize theywillbeasminimumtothecurrentsstated in the nameplate of each UPS In the nameplate of the equipment there are only printed the nominal curre...

Page 14: ...only 1 metallic piece and bolt to joint the battery module with the equipment on tower format Once the reception is finished it is advisable to pack the UPS and the battery module s again till its com...

Page 15: ...nofthispowerrangeintherackcabinetwhenthemanipula tionsaredonebyhand thebatteryblockhastoberemovedfrom the equipment Proceedasfollowstoremovethebatteryblockorpack basedon one pack for 4 to 6 kVA models...

Page 16: ...r side of the equipment see figure 11 All the instructions relating to connections will detailed later on less those ones regarding the battery connection Therefore this section will only describe the...

Page 17: ...ment vertical There are no supports or stabilizers A A B Fig 7 Vertical tower type assembling 4 2 5 3 Vertical tower type assembling with extended back up time battery module The description of this s...

Page 18: ...8 Model in vertical tower type assembling with extended back up time battery module Regarding the connections of the UPS with the battery module in models up to 6 kVA make the following steps but rea...

Page 19: ...frame of the cabinet by means of the screws B 4 2 5 5 19 rack cabinet assembling with extended back up time battery module This section describes a single equipment with only one battery module see fi...

Page 20: ...seconnectortoconnectitwith anotherbatterymodule Socketforbattery module Wireofbatterymodule Fig 11 Batterymoduleconnectionfor8and10kVAequipments 4 3 Connection Cross cable section used in the power su...

Page 21: ...t the circuit diagram of the particular Backfeed protection for the equipment without bypass line There can be no derivation in the line that goes from the Backfeed protection to the UPS as the safety...

Page 22: ...2 and respect the circuit diagram of the par ticular Backfeedprotection fortheequipmentwithbypassline There can be no derivation in the line that goes from the Backfeed protection to the UPS as the sa...

Page 23: ...the load connected to the respective outlet has to be checked otherwise the protection will be activated and deactivated cyclically and therefore the loads will suffer the consequences For hardwired...

Page 24: ...ting the power supply to the input power block Make sure that all the loads connected to the UPS are only con nectedtotheprotectiveearthbondingterminal Thefactof not restricting the earthing of the lo...

Page 25: ...3 9 2 Installationandparalleloperating 4to10kVA equipmentsonly Communication line COM is a very low voltage circuit of safety Topreservethequality ithastobeinstalledseparate from other lines that have...

Page 26: ...s the difference in the length between the input and output cables of the equipments has to be lower than 10 Input circuit breakers Output circuit breakers Manual bypass UPS nr 1 Input To loads UPS nr...

Page 27: ...other machines or devices through the 5 dry contacts supplied in the terminal strip included in the same card and to each one of them an alarm of the 8 available can be as signed see table 6 Also the...

Page 28: ...of the monitoring software 4 3 12 Considerations before starting up the connected loads It is recommended to charge the batteries for 2 hours as minimum before using the UPS for first time When sup p...

Page 29: ...3 seconds to shut down the inverter The acoustic alarm will beep for 3 sec The equipment will be established on Bypass mode When finishing the previous action there is still voltage at the UPS output...

Page 30: ...hrough the bypass Turn On the output circuit breaker switch of the distribution panel corresponding to the new integrated equipment The complete parallel system will supply output voltage through the...

Page 31: ...tem again 6 Control panel with LCD 6 1 Control panel Fig 20 Control panel view Button Function Description Inverter start up With no AC power supply and battery connected to the equipment press the bu...

Page 32: ...te In ECO mode Blue 65 State In converter mode Blue 71 Warning EPO active Blue 72 Warning On maintain Bypass only models of 4 10 kVA Blue 81 Fault Heatsink over temperature Red 82 Warning Ambient over...

Page 33: ...passwithoutputvoltagescreen Bypass without output voltage The UPS is running on bypass mode without output voltage Fig 25 Bypasswithoutoutputvoltagescreen ECO mode Once the UPS is started up the energ...

Page 34: ...se the UPS could fail Fig 28 Warningscreen Fault When a fault occurs it reveals that some serious problems have happened the UPS will break the output voltage or will transfertobypassandthealarmwillbe...

Page 35: ...ame main screen when pressing the key for more than 1 sec the Structure of the main menu will be displayed see figure 33 Todisplaythedifferentsubmenus pressthekeys or forless than 1 sec considering th...

Page 36: ...see figure 34 Whenpressingthekey formorethan1sec theLCDwillshow the UPS status screen of the main menu structure again Press 1 sec Press o 1 sec Event logger structure menu Main menu structure Press...

Page 37: ...ter When pressing the key for more than 1 sec the LCD panel will display the screen Event log from the main menu structure again Control submenu for 0 7 to 3 kVA models 6 3 4 Measurement submenu When...

Page 38: ...is single or it is parallel and power supply to load s is broken To restore the normal condition the EPO button has to be de activated previously close the circuit again and enter into the ClearEPOsta...

Page 39: ...ctions that could satisfy a special ap plication of the user In case you require any of these special functionalists contact the KESS Support Team to change the standard configuration from fac tory 6...

Page 40: ...as battery has to be charged every 2 months The charging time has to be 12 hours as minimum Under normal conditions the battery lifetime is from 3 to 5 years at20 C Eurobat Ahighertemperaturecancaused...

Page 41: ...ment is too high Check the UPS cooling and ambient temperature of the room 93 Back Feed only 3 kVA On battery mode bypass has voltage Transfer to manual bypass and consult our KESS Support Team Do not...

Page 42: ...9 Troubleshooting guide Warning indications 7 2 3 Troubleshooting guide Other circumstances Circumstance or condition Possible cause Solution Code DescriptionintheLCDpanel 01 Bypass Abnormal Bypass p...

Page 43: ...ered product UPS KESSUPS 91RT series 7 4 Description of the available maintenance and service contracts For the UPS series KESSUPS 91RT additional warranty services are available as an option Also pre...

Page 44: ...62040 3 non linear load Transient recover time of the output voltage with load step 0 100 0 9 Transient recover time of output voltage with load step 20 100 20 6 Frequency With mains present synchron...

Page 45: ...emperature 15 50 C Storage temperature without batteries 20 70 C Operating altitude 1000 m a s l for high altitude correct it according to table 14 Relative humidity 0 95 non condensing Protection deg...

Page 46: ...KESS Power Solutions GmbH Gentzgasse 55 A 1180 Wien T 43 0 1 4704731 0 info kess at www kess at MA_16_03_KESSUPS_91RT_E...

Reviews: