background image

4

can cause damages to the equipment and/or to the loads and installa-
tion.

• 

The local electrical regulations and the different restric-
tions of the client's site, they can invalidate some recom-

mendations included in the manuals. when discrepancies exist, 
the user has to comply the local regulations.

• 

The equipments provided with power cord with plug and 
outlets, can be connected and used by personnel without 

any kind of experience.
The equipments with power blocks have to be installed by quali-
fied personnel and can be used by personnel with no specific 
training, just with only help of this manual.
A person is defined as qualified, if it has experience of assem-
bling, commissioning and perfect control operating of the equip-
ment, if he has the requirements to do the job and if has read and 
understand all the things described in this manual, in particular 
the safety indications. Such preparation is considered only valid if 
it is certified by our KESS Support-Team.

•  Place the equipment the closest to the power supply and loads 

to be supplied, leaving an easy access if it were needed an urgent 
disconnection.
in the hardwired equipments and due to the impossibility of fast 
disconnection, a disconnection device (switch) with easy access 
and close to the equipment will be installed.

•  warning labels should be placed on all primary power switches 

installed in places away from the equipment to alert the electrical 
maintenance personnel of the presence of a UPS in the circuit 
The label will bear the following text or an equivalent one:

before working in this circuit.

•  isolate the Uninterruptible Power System (UPS).
•  Check the voltage between all terminals including the 

protective earth.

Risk of voltage feedback from UPS.

1.2.3.1.  General safety warnings

•  All connections and disconnections of the cables from the equip-

ment, including the control ones, will be done with no power 
supply and the switches on rest, position «on» or «off».

•  Shutdown the equipment completely by switching «off» the 

button of the control panel first. next disconnect the cable from 
the wall outlet for standard equipments up to 3 kVA or by switching 
«off» the input circuit breaker and disconnect the power supply ca-
bles in models with higher power rate.

The indiscriminate manoeuvring of the switches may in-
volve production losses and/or equipment damages. 

Consult the documentation before doing any action 

• 

Pay special attention to the labelling of the equipment 
that warns about the «Electrical shock hazard». inside the 

equipment there are dangerous voltages, never open the enclo-
sure, the access has to be done by qualified staff. in case of main-
tenance or fault, contact the KESS Support-Team.

•  Cross cable sections used to supply the equipment and loads, will 

be according to the nominal current stated in the nameplate label 
of the equipment, and respecting the low Voltage Electrotechnical 
Regulations or standards of the country.
Use approved cables only.

• 

Protection Earth cable of the UPS drives the leakage current of 

the load devices. An isolated earth cable has to be installed as 

part of the circuit that supplies the equipment. Cross cable section 
and its features will be same as the power supply cables and have  
to have an protection earth cable. 

 

All outlets of the UPS has an earth bonding, duly connected and 
those equipments with power blocks there is an exclusive ter-
minal for the load earth connection. when an outgoing distribu-
tion is done, i.e power strips, it is essential that they have an earth 
terminal connected to each one of them.
it is essential that the cables that supplies the loads have the 
earth connection cable. 

The protection earth must be connected to the frame or 
metallic chassis of any electrical equipment (in our case to 

the UPS, battery cabinet or case and loads), assuring that it is done 
before connecting the input voltage.
Check the quality and availability of the earth, it has to be be-
tween the defined parameters by the local or national regula-
tions.

•  in small equipments (the ones connected with the foreseen 

power cord with plug), the user has to check the wall outlet cor-
responds with the type of supplied plug, with earth duly installed 
and connected to the local protection earth.

• 

During the normal UPS operation, in equipments up to 
3kVA the power cord cable can't be disconnected from 

wall outlet, because the protection earth of the own UPS would 
be disconnected and also the earth from the loads connected to 
the output.
For this reason, the general protection earth cable of the 
building or switchgear panel that supplies the UPS will not be 
disconnected.

•  in small UPS (the ones connected with the foreseen power cord 

with plug), check that the sum of the leakage currents of the UPS 
and connected load/s do not exceed over 3,5mA.

•  The installation will have input protections sized to the currents 

of the equipment and stated in the nameplate label (RCD de-
vices type b and circuit breakers with C characteristic or any other 
equivalent one).
overload conditions are considered as a nonpermanent an ex-
ceptional operating mode, so these currents will not be kept in 
mind when sizing the protections.

•  Do not overload the UPS by connecting loads with inrush con-

sumptions at its output, like laser printers.

•  output protection will be done with a circuit breaker of C charac-

teristic or an equivalent one.
it is recommended to distribute the output power, into four lines 
as minimum. Each one of them will have a protection circuit 
breaker sized to the quarter of the nominal power. This kind of 
outgoing distributions will allow that any fault in any device con-
nected to the equipment, that makes a short-circuit, will affect 
to the line with the faulty device only. An uninterruptible power 
supply will be guaranteed to the rest of connected loads, due to 
the protection tripping of the affected line by the short-circuit 
only.

•  when replacing a fuse, do it for another of the same type, character-

istics format and size.

•  Under any concept the input power cord will be connected to the 

output of the equipment, either directly or through other ways.

Summary of Contents for KESSUPS 91RT

Page 1: ...UPSseriesKESSUPS91RT 700VA 10kVA Uninterruptible Power Supply User s manual...

Page 2: ...3kVAequipmentsonly 4 3 8 Dry_out terminals drycontactforalarm 0 7to3kVAequipmentsonly 4 3 9 Connectioninparallel 4 3 9 1 Introductiontotheredundancy 4 3 9 2 Installationandparalleloperating 4to10kVAeq...

Page 3: ...amage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic instructionsandfeaturesfortheequipmentsafety Tonotrespect these indications can c...

Page 4: ...UPSdrivestheleakagecurrentof theloaddevices Anisolatedearthcablehastobeinstalledas part of the circuit that supplies the equipment Cross cable section and its features will be same as the power supply...

Page 5: ...art from the implicit stated risks any action that make the modification internal or external of the equipment or just only the simple intervention inside of itself which is not stated in this documen...

Page 6: ...y from the equip ment in another cabinet case or rack with the interlink cables among them Do not modify its length In those equipments requested without batteries their acquisi tion installation and...

Page 7: ...the event of any modification or intervention in the product by the cus tomer s side This is a product for its use in commercial and industrial ap plications so restrictions and additional measures c...

Page 8: ...91RT models from 4 to 6 kVA 3HE from 8 to 10 kVA 5HE Battery module from 0 7 to 3 kVA Battery module from 4 to 6 kVA 3HE from 8 to 10 kVA 5HE Fixing screws Front cover Fixing screws Front cover Fixing...

Page 9: ...put terminals IEC AC outlets LS2 Modelsfrom0 7to2kVAstandard USB COM port RS232 COM port IEC inlet for AC power supply Main earth for battery module Connectorfor remoteON OFF Auxiliary contact connect...

Page 10: ...other module Battery module for equipments from 0 7 to 3 kVA Earth bonding terminal to be connected to the equipment and with other module Battery module for equipments from4 to 6 kVA The connection o...

Page 11: ...rface or SNMP for controlling the equipment via Internet Intranet Models from 4 to 10 kVA allow the parallel connection of a second equipment of the same features for a redundant configuration or to i...

Page 12: ...SNMP adapter The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of control ling and management at the manager system disposal Th...

Page 13: ...ing C characteristic for circuit breaker Regardingthesize theywillbeasminimumtothecurrentsstated in the nameplate of each UPS In the nameplate of the equipment there are only printed the nominal curre...

Page 14: ...only 1 metallic piece and bolt to joint the battery module with the equipment on tower format Once the reception is finished it is advisable to pack the UPS and the battery module s again till its com...

Page 15: ...nofthispowerrangeintherackcabinetwhenthemanipula tionsaredonebyhand thebatteryblockhastoberemovedfrom the equipment Proceedasfollowstoremovethebatteryblockorpack basedon one pack for 4 to 6 kVA models...

Page 16: ...r side of the equipment see figure 11 All the instructions relating to connections will detailed later on less those ones regarding the battery connection Therefore this section will only describe the...

Page 17: ...ment vertical There are no supports or stabilizers A A B Fig 7 Vertical tower type assembling 4 2 5 3 Vertical tower type assembling with extended back up time battery module The description of this s...

Page 18: ...8 Model in vertical tower type assembling with extended back up time battery module Regarding the connections of the UPS with the battery module in models up to 6 kVA make the following steps but rea...

Page 19: ...frame of the cabinet by means of the screws B 4 2 5 5 19 rack cabinet assembling with extended back up time battery module This section describes a single equipment with only one battery module see fi...

Page 20: ...seconnectortoconnectitwith anotherbatterymodule Socketforbattery module Wireofbatterymodule Fig 11 Batterymoduleconnectionfor8and10kVAequipments 4 3 Connection Cross cable section used in the power su...

Page 21: ...t the circuit diagram of the particular Backfeed protection for the equipment without bypass line There can be no derivation in the line that goes from the Backfeed protection to the UPS as the safety...

Page 22: ...2 and respect the circuit diagram of the par ticular Backfeedprotection fortheequipmentwithbypassline There can be no derivation in the line that goes from the Backfeed protection to the UPS as the sa...

Page 23: ...the load connected to the respective outlet has to be checked otherwise the protection will be activated and deactivated cyclically and therefore the loads will suffer the consequences For hardwired...

Page 24: ...ting the power supply to the input power block Make sure that all the loads connected to the UPS are only con nectedtotheprotectiveearthbondingterminal Thefactof not restricting the earthing of the lo...

Page 25: ...3 9 2 Installationandparalleloperating 4to10kVA equipmentsonly Communication line COM is a very low voltage circuit of safety Topreservethequality ithastobeinstalledseparate from other lines that have...

Page 26: ...s the difference in the length between the input and output cables of the equipments has to be lower than 10 Input circuit breakers Output circuit breakers Manual bypass UPS nr 1 Input To loads UPS nr...

Page 27: ...other machines or devices through the 5 dry contacts supplied in the terminal strip included in the same card and to each one of them an alarm of the 8 available can be as signed see table 6 Also the...

Page 28: ...of the monitoring software 4 3 12 Considerations before starting up the connected loads It is recommended to charge the batteries for 2 hours as minimum before using the UPS for first time When sup p...

Page 29: ...3 seconds to shut down the inverter The acoustic alarm will beep for 3 sec The equipment will be established on Bypass mode When finishing the previous action there is still voltage at the UPS output...

Page 30: ...hrough the bypass Turn On the output circuit breaker switch of the distribution panel corresponding to the new integrated equipment The complete parallel system will supply output voltage through the...

Page 31: ...tem again 6 Control panel with LCD 6 1 Control panel Fig 20 Control panel view Button Function Description Inverter start up With no AC power supply and battery connected to the equipment press the bu...

Page 32: ...te In ECO mode Blue 65 State In converter mode Blue 71 Warning EPO active Blue 72 Warning On maintain Bypass only models of 4 10 kVA Blue 81 Fault Heatsink over temperature Red 82 Warning Ambient over...

Page 33: ...passwithoutputvoltagescreen Bypass without output voltage The UPS is running on bypass mode without output voltage Fig 25 Bypasswithoutoutputvoltagescreen ECO mode Once the UPS is started up the energ...

Page 34: ...se the UPS could fail Fig 28 Warningscreen Fault When a fault occurs it reveals that some serious problems have happened the UPS will break the output voltage or will transfertobypassandthealarmwillbe...

Page 35: ...ame main screen when pressing the key for more than 1 sec the Structure of the main menu will be displayed see figure 33 Todisplaythedifferentsubmenus pressthekeys or forless than 1 sec considering th...

Page 36: ...see figure 34 Whenpressingthekey formorethan1sec theLCDwillshow the UPS status screen of the main menu structure again Press 1 sec Press o 1 sec Event logger structure menu Main menu structure Press...

Page 37: ...ter When pressing the key for more than 1 sec the LCD panel will display the screen Event log from the main menu structure again Control submenu for 0 7 to 3 kVA models 6 3 4 Measurement submenu When...

Page 38: ...is single or it is parallel and power supply to load s is broken To restore the normal condition the EPO button has to be de activated previously close the circuit again and enter into the ClearEPOsta...

Page 39: ...ctions that could satisfy a special ap plication of the user In case you require any of these special functionalists contact the KESS Support Team to change the standard configuration from fac tory 6...

Page 40: ...as battery has to be charged every 2 months The charging time has to be 12 hours as minimum Under normal conditions the battery lifetime is from 3 to 5 years at20 C Eurobat Ahighertemperaturecancaused...

Page 41: ...ment is too high Check the UPS cooling and ambient temperature of the room 93 Back Feed only 3 kVA On battery mode bypass has voltage Transfer to manual bypass and consult our KESS Support Team Do not...

Page 42: ...9 Troubleshooting guide Warning indications 7 2 3 Troubleshooting guide Other circumstances Circumstance or condition Possible cause Solution Code DescriptionintheLCDpanel 01 Bypass Abnormal Bypass p...

Page 43: ...ered product UPS KESSUPS 91RT series 7 4 Description of the available maintenance and service contracts For the UPS series KESSUPS 91RT additional warranty services are available as an option Also pre...

Page 44: ...62040 3 non linear load Transient recover time of the output voltage with load step 0 100 0 9 Transient recover time of output voltage with load step 20 100 20 6 Frequency With mains present synchron...

Page 45: ...emperature 15 50 C Storage temperature without batteries 20 70 C Operating altitude 1000 m a s l for high altitude correct it according to table 14 Relative humidity 0 95 non condensing Protection deg...

Page 46: ...KESS Power Solutions GmbH Gentzgasse 55 A 1180 Wien T 43 0 1 4704731 0 info kess at www kess at MA_16_03_KESSUPS_91RT_E...

Reviews: