7.2.1. 

Troubleshooting guide. Alarm or fault 

indications

Alarm or fault

Possible cause

Solution

Code

Description of the lCD panel

21

bus over Voltage

Fault due to positive DC bus overvoltage.

The UPS transfers the load over the inverter (battery mode).

22

bus Under Voltage

Fault due to positive DC bus undervoltage..

The UPS transfers the load over the inverter (battery mode).

23

bus Unbalance

Fault in the balancing of positive and negative 

bUS.

The UPS transfers the load over the inverter (battery mode).

24

bus Short

bUS voltage decreases very fast.

Consult our KESS Support-Team 

25

bus Softstart Fail

Fault of the DC bUS soft start.

Consult our KESS Support-Team

31

output Short Circuit

The UPS detects a wrong output imedance,  

considering a short-circuit.

The UPS will make a shutdown afger five voltage cycles.

32

inv over voltage

inverter fault due to overvoltage.

The UPS transfers the load over the bypass (bypass mode).

33

inv Under voltage

inverter fault due to undervoltage.

The UPS transfers the load over the bypass (bypass mode).

34

inv Softstart Fail

Fault of the inverter soft start.

Consult our KESS Support-Team

41

output overload

output overload.

Check the load and remove the non-critical ones or if any load has failed or 

it is damaged. The UPS is still working normally, but it can transfer to bypass 

mode in case the problem persists or the load is increased.

when this condition is finished the alarm is cancelled.

42

inv overload Fault

The UPS transfers the load over the bypass 

(bypass mode) due the inverter overload.

Check the load and remove the non-critical ones or if any load has failed 

or it is damaged. The UPS will transfer the load over the inverter (battery 

mode), when the load is the suitable. 

43

byp overload Fault

The UPS doesn't supply output voltage on 

bypass or ECo modes, due the overload.

Check the load and remove the non-critical ones or if any load has failed or 

it is damaged.

81

Heatsink over Temperature

Heatsink overtemperature inside the 

equipment is too high.

Check the UPS cooling and ambient temperature of the room.

93

back  Feed

(only > 3 kVA)

on battery mode, bypass has voltage. 

Transfer to manual bypass and consult our KESS Support-Team.

Do not touch the power supply terminals of the equipments that are 

connected to an electrical installation supplied by a UPS. Even, it is 

dangerous with no power supply, because the equipment is an energy 

genset.

 
Tab. 8          Troubleshooting guide. Alarm or fault indications.

7.2.2.  Troubleshooting guide. warning 

indications

warning

Possible cause

Solution

Code

Description in the lCD panel

02

Utility Abnormal

input power supply out of range.

Check the AC input mains status.

04

Site wiring Fault

neutral fault to earth detected. The alarm is 

triggered when there is  a voltage difference 

between the earth and neutral > 15V.

Reverse the polarity of the input cables 

(phase and neutral). by default the detector is activated. it can be 

deactivated through the control panel with lCD.

11

battery Disconnect

low battery voltage. it can be due a blown 

fuse, wrong connection of the battery module 

connector or fault in the connection among 

them, either in the UPS or in the module.

Check the connection of the battery module with the UPS, if any. For 

any other  different incident or if the problem persists, contact our KESS 

Support-Team.

12

battery low

The UPS works on battery mode and the 

batteries are depleted (low or very lows).

it is a warning indication, because the remaining back up time depends on 

the % of connected load. Depending on the load and quantity of external 

battery module (options), the warning can be activated when there is a 25% 

of their capacity.

13

Service battery

battery block voltage failure detected. The 

charger has been deactivated as caution 

measure.

Consult our KESS Support-Team.

15

Charger Fail

battery charge failure.

Charger is shutdown till the next charge cycle. Consult our KESS Support-

Team.

16

battery over Voltage

battery overvoltage.

Charger is shutdown till the next charge cycle. Consult our KESS Support-

Team.

71

EPo Active

EPo button open or close, depending ont he 

selection set in the control pane.  Factory preset 

is open.

Check the status or condition of the EPo button.

Summary of Contents for KESSUPS 91RT

Page 1: ...UPSseriesKESSUPS91RT 700VA 10kVA Uninterruptible Power Supply User s manual...

Page 2: ...3kVAequipmentsonly 4 3 8 Dry_out terminals drycontactforalarm 0 7to3kVAequipmentsonly 4 3 9 Connectioninparallel 4 3 9 1 Introductiontotheredundancy 4 3 9 2 Installationandparalleloperating 4to10kVAeq...

Page 3: ...amage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic instructionsandfeaturesfortheequipmentsafety Tonotrespect these indications can c...

Page 4: ...UPSdrivestheleakagecurrentof theloaddevices Anisolatedearthcablehastobeinstalledas part of the circuit that supplies the equipment Cross cable section and its features will be same as the power supply...

Page 5: ...art from the implicit stated risks any action that make the modification internal or external of the equipment or just only the simple intervention inside of itself which is not stated in this documen...

Page 6: ...y from the equip ment in another cabinet case or rack with the interlink cables among them Do not modify its length In those equipments requested without batteries their acquisi tion installation and...

Page 7: ...the event of any modification or intervention in the product by the cus tomer s side This is a product for its use in commercial and industrial ap plications so restrictions and additional measures c...

Page 8: ...91RT models from 4 to 6 kVA 3HE from 8 to 10 kVA 5HE Battery module from 0 7 to 3 kVA Battery module from 4 to 6 kVA 3HE from 8 to 10 kVA 5HE Fixing screws Front cover Fixing screws Front cover Fixing...

Page 9: ...put terminals IEC AC outlets LS2 Modelsfrom0 7to2kVAstandard USB COM port RS232 COM port IEC inlet for AC power supply Main earth for battery module Connectorfor remoteON OFF Auxiliary contact connect...

Page 10: ...other module Battery module for equipments from 0 7 to 3 kVA Earth bonding terminal to be connected to the equipment and with other module Battery module for equipments from4 to 6 kVA The connection o...

Page 11: ...rface or SNMP for controlling the equipment via Internet Intranet Models from 4 to 10 kVA allow the parallel connection of a second equipment of the same features for a redundant configuration or to i...

Page 12: ...SNMP adapter The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of control ling and management at the manager system disposal Th...

Page 13: ...ing C characteristic for circuit breaker Regardingthesize theywillbeasminimumtothecurrentsstated in the nameplate of each UPS In the nameplate of the equipment there are only printed the nominal curre...

Page 14: ...only 1 metallic piece and bolt to joint the battery module with the equipment on tower format Once the reception is finished it is advisable to pack the UPS and the battery module s again till its com...

Page 15: ...nofthispowerrangeintherackcabinetwhenthemanipula tionsaredonebyhand thebatteryblockhastoberemovedfrom the equipment Proceedasfollowstoremovethebatteryblockorpack basedon one pack for 4 to 6 kVA models...

Page 16: ...r side of the equipment see figure 11 All the instructions relating to connections will detailed later on less those ones regarding the battery connection Therefore this section will only describe the...

Page 17: ...ment vertical There are no supports or stabilizers A A B Fig 7 Vertical tower type assembling 4 2 5 3 Vertical tower type assembling with extended back up time battery module The description of this s...

Page 18: ...8 Model in vertical tower type assembling with extended back up time battery module Regarding the connections of the UPS with the battery module in models up to 6 kVA make the following steps but rea...

Page 19: ...frame of the cabinet by means of the screws B 4 2 5 5 19 rack cabinet assembling with extended back up time battery module This section describes a single equipment with only one battery module see fi...

Page 20: ...seconnectortoconnectitwith anotherbatterymodule Socketforbattery module Wireofbatterymodule Fig 11 Batterymoduleconnectionfor8and10kVAequipments 4 3 Connection Cross cable section used in the power su...

Page 21: ...t the circuit diagram of the particular Backfeed protection for the equipment without bypass line There can be no derivation in the line that goes from the Backfeed protection to the UPS as the safety...

Page 22: ...2 and respect the circuit diagram of the par ticular Backfeedprotection fortheequipmentwithbypassline There can be no derivation in the line that goes from the Backfeed protection to the UPS as the sa...

Page 23: ...the load connected to the respective outlet has to be checked otherwise the protection will be activated and deactivated cyclically and therefore the loads will suffer the consequences For hardwired...

Page 24: ...ting the power supply to the input power block Make sure that all the loads connected to the UPS are only con nectedtotheprotectiveearthbondingterminal Thefactof not restricting the earthing of the lo...

Page 25: ...3 9 2 Installationandparalleloperating 4to10kVA equipmentsonly Communication line COM is a very low voltage circuit of safety Topreservethequality ithastobeinstalledseparate from other lines that have...

Page 26: ...s the difference in the length between the input and output cables of the equipments has to be lower than 10 Input circuit breakers Output circuit breakers Manual bypass UPS nr 1 Input To loads UPS nr...

Page 27: ...other machines or devices through the 5 dry contacts supplied in the terminal strip included in the same card and to each one of them an alarm of the 8 available can be as signed see table 6 Also the...

Page 28: ...of the monitoring software 4 3 12 Considerations before starting up the connected loads It is recommended to charge the batteries for 2 hours as minimum before using the UPS for first time When sup p...

Page 29: ...3 seconds to shut down the inverter The acoustic alarm will beep for 3 sec The equipment will be established on Bypass mode When finishing the previous action there is still voltage at the UPS output...

Page 30: ...hrough the bypass Turn On the output circuit breaker switch of the distribution panel corresponding to the new integrated equipment The complete parallel system will supply output voltage through the...

Page 31: ...tem again 6 Control panel with LCD 6 1 Control panel Fig 20 Control panel view Button Function Description Inverter start up With no AC power supply and battery connected to the equipment press the bu...

Page 32: ...te In ECO mode Blue 65 State In converter mode Blue 71 Warning EPO active Blue 72 Warning On maintain Bypass only models of 4 10 kVA Blue 81 Fault Heatsink over temperature Red 82 Warning Ambient over...

Page 33: ...passwithoutputvoltagescreen Bypass without output voltage The UPS is running on bypass mode without output voltage Fig 25 Bypasswithoutoutputvoltagescreen ECO mode Once the UPS is started up the energ...

Page 34: ...se the UPS could fail Fig 28 Warningscreen Fault When a fault occurs it reveals that some serious problems have happened the UPS will break the output voltage or will transfertobypassandthealarmwillbe...

Page 35: ...ame main screen when pressing the key for more than 1 sec the Structure of the main menu will be displayed see figure 33 Todisplaythedifferentsubmenus pressthekeys or forless than 1 sec considering th...

Page 36: ...see figure 34 Whenpressingthekey formorethan1sec theLCDwillshow the UPS status screen of the main menu structure again Press 1 sec Press o 1 sec Event logger structure menu Main menu structure Press...

Page 37: ...ter When pressing the key for more than 1 sec the LCD panel will display the screen Event log from the main menu structure again Control submenu for 0 7 to 3 kVA models 6 3 4 Measurement submenu When...

Page 38: ...is single or it is parallel and power supply to load s is broken To restore the normal condition the EPO button has to be de activated previously close the circuit again and enter into the ClearEPOsta...

Page 39: ...ctions that could satisfy a special ap plication of the user In case you require any of these special functionalists contact the KESS Support Team to change the standard configuration from fac tory 6...

Page 40: ...as battery has to be charged every 2 months The charging time has to be 12 hours as minimum Under normal conditions the battery lifetime is from 3 to 5 years at20 C Eurobat Ahighertemperaturecancaused...

Page 41: ...ment is too high Check the UPS cooling and ambient temperature of the room 93 Back Feed only 3 kVA On battery mode bypass has voltage Transfer to manual bypass and consult our KESS Support Team Do not...

Page 42: ...9 Troubleshooting guide Warning indications 7 2 3 Troubleshooting guide Other circumstances Circumstance or condition Possible cause Solution Code DescriptionintheLCDpanel 01 Bypass Abnormal Bypass p...

Page 43: ...ered product UPS KESSUPS 91RT series 7 4 Description of the available maintenance and service contracts For the UPS series KESSUPS 91RT additional warranty services are available as an option Also pre...

Page 44: ...62040 3 non linear load Transient recover time of the output voltage with load step 0 100 0 9 Transient recover time of output voltage with load step 20 100 20 6 Frequency With mains present synchron...

Page 45: ...emperature 15 50 C Storage temperature without batteries 20 70 C Operating altitude 1000 m a s l for high altitude correct it according to table 14 Relative humidity 0 95 non condensing Protection deg...

Page 46: ...KESS Power Solutions GmbH Gentzgasse 55 A 1180 Wien T 43 0 1 4704731 0 info kess at www kess at MA_16_03_KESSUPS_91RT_E...

Reviews: