background image

5

• 

Models with separate bypass line, a galvanic isolation 
transformer has to be installed in any of the two lines that 

supply the UPS (rectifier input or static bypass), to avoid the direct 
union of the neutral of both lines through the internal wiring of 
the equipment.
This is applicable when the two lines are supplied from different 
mains, i.e.:

 

ˆ

Two different electrical companies.

 

ˆ

An electrical company and genset, ...

•  All the equipments have an auxiliary terminal strip to install an 

external emergency power off button (EPo).
The type of circuit is selectable through the lCD panel of the 
equipment. The contact is preset from factory as normally open, 
so the button must be switched to close the circuit and the 
voltage to the loads is broken. To establish the power supply to 
the loads again, the EPo button must be deactivated.
EPo doesn't affect to the power supply of the equipment, it only 
breaks the power supply to the loads as a safety measure.

• 

when supplying input voltage to a UPS with fitted in or 
separate static bypass, although the inverter is still turned 

«off» (deactivated) it doesn't mean that at the output there will 
not be voltage.
So, to do it, the input and static bypass switches will have to be 
turned «off».
Put warnings of danger and/or emergency switches if the safety 
Standards require it in your particular installation.

• 

it is possible that the UPS supplies output voltage through 
the manual bypass to those equipments that incorporate 

it either standard or optional, so it will have to be considered as 
regards to safety. if it were necessary to break the output supply of 
the equipment in this situation, deactivate the outgoing distribu-
tion protection or in case of lack of it the general protection of the 
distribution panel that feeds the UPS. 

•  All power supply electrical cables have to be fixed to the equip-

ments and loads, interfaces, etc..., to unmovable parts and in the 
way to avoid treads, trips on them or fortuitous pulls.

•  Phase equipments in the foreseen terminal for that purpose.
•  CHASSiS or RACK mounted equipments are destined to be installed 

in a predetermined set to be done by professionals.

 

ˆ

The installation has to be designed and executed by quali-
fied personnel, who will be the responsible to apply the 
safety and EMC regulations and standards that controls the 
particular installations where the product is destined.

 

ˆ

The equipments assembled in CHASSiS do not have enclo-
sure protection, even the power blocks are unprotected.

 

ˆ

Some RACK mounted equipments do not have the power 
blocks protected.

•  never manipulate the equipment with wet hands.

1.2.3.2.  To keep in mind

• 

Do not try to dismantle or change any part of the equip-
ment, if this action is not contemplated in this document. 

Manipulation inside the UPS due to any modification, reparation 
or any other cause, can make an electrical discharge of high 
voltage and it is restricted to qualified staff only. Do not open the 
equipment.
A part from the implicit stated risks, any action that make the 

modification, internal or external of the equipment or just only 
the simple intervention inside of itself, which is not stated in this 
document, it can expire the warranty. 

•  if it is observed that the UPS exhausts smoke or toxic gas, shut-

down it immediately and disconnect it from the power supply. 
This kind of fault can cause fire or electrical discharge. Contact our 
KESS Support-Team.

•  in case of an accidental equipment dropping or if the enclosure is 

damaged, do not start it up under any concept. This kind of fault 
can cause fire or electrical discharge. Contact our KESS Support-
Team.

•  Do not cut, manipulate the electrical cables, do not put heavy 

objects over them too. Any of these actions could cause a short-
circuit and make a fire or electrical discharge.
Check that the electrical cables of connection, plugs and outlets 
are in good conditions.

•  when moving an equipment from a cold place to a warm en-

vironment and vice versa, it can cause condensation (small 
water drops) in the external and internal surfaces. before 
installing a moved equipment from another place or even 
packaged, the equipment will be left for a minimum time 
of two hours in the new location before making any action, 
with the purpose of adapting it to the new environmental 
conditions and avoid the possible condensations.
The UPS has to be completely dry before starting any installation 
task.

•  Do not store, install or expose the equipment in corrosive, wets, 

dusty inflammable or explosive environments and never out-
doors.

•  Avoid to locate, install or store the equipment in a place with 

direct sunlight or high temperatures. batteries could be dam-
aged.
in the exceptional case and long exposition to intense heat, 
batteries can cause filtrations, overheating or explosions, 
which can cause fires, burn or other injuries. High tempera-
tures can also make deformation in the enclosure.

•  The location will be spacious, airy, away from heat sources and 

easy access.

•  Do not obstruct the cooling grids by entering objects through 

themselves or other orifices.

•   in equipments of low power rate (up to 3kVA), leave as minimum 

space of 25 cm in the equipment peripheral and 50 cm for higher 
power rates equipments.

•   Also in the UPS with power blocks, it is recommended to leave 

another additional 50 cm for an eventual intervention of the 
KESS Support-Team, considering that if it means to move the 
UPS, the connected cables will have the needed clearance.

•  Do not put materials over the equipment or parts that obstruct 

the correct visualization of the synoptic.

•  be careful to not wet it, because it is not waterproof. Do not allow 

entering any kind of liquids in. if accidentally the outside of the 
machine comes into contact with liquids or salt air, dry it with a 
soft and absorbent cloth. 

•  To clean the equipment, wipe over a damp cloth and then dry it. 

Avoid sprinkling or spillage that could enter through the slots or 
cooling grids, which may cause fire or electric shock.
Do not clean the equipments with products that could have al-
cohol, benzene, solvent or other inflammable substances, or they 

Summary of Contents for KESSUPS 91RT

Page 1: ...UPSseriesKESSUPS91RT 700VA 10kVA Uninterruptible Power Supply User s manual...

Page 2: ...3kVAequipmentsonly 4 3 8 Dry_out terminals drycontactforalarm 0 7to3kVAequipmentsonly 4 3 9 Connectioninparallel 4 3 9 1 Introductiontotheredundancy 4 3 9 2 Installationandparalleloperating 4to10kVAeq...

Page 3: ...amage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic instructionsandfeaturesfortheequipmentsafety Tonotrespect these indications can c...

Page 4: ...UPSdrivestheleakagecurrentof theloaddevices Anisolatedearthcablehastobeinstalledas part of the circuit that supplies the equipment Cross cable section and its features will be same as the power supply...

Page 5: ...art from the implicit stated risks any action that make the modification internal or external of the equipment or just only the simple intervention inside of itself which is not stated in this documen...

Page 6: ...y from the equip ment in another cabinet case or rack with the interlink cables among them Do not modify its length In those equipments requested without batteries their acquisi tion installation and...

Page 7: ...the event of any modification or intervention in the product by the cus tomer s side This is a product for its use in commercial and industrial ap plications so restrictions and additional measures c...

Page 8: ...91RT models from 4 to 6 kVA 3HE from 8 to 10 kVA 5HE Battery module from 0 7 to 3 kVA Battery module from 4 to 6 kVA 3HE from 8 to 10 kVA 5HE Fixing screws Front cover Fixing screws Front cover Fixing...

Page 9: ...put terminals IEC AC outlets LS2 Modelsfrom0 7to2kVAstandard USB COM port RS232 COM port IEC inlet for AC power supply Main earth for battery module Connectorfor remoteON OFF Auxiliary contact connect...

Page 10: ...other module Battery module for equipments from 0 7 to 3 kVA Earth bonding terminal to be connected to the equipment and with other module Battery module for equipments from4 to 6 kVA The connection o...

Page 11: ...rface or SNMP for controlling the equipment via Internet Intranet Models from 4 to 10 kVA allow the parallel connection of a second equipment of the same features for a redundant configuration or to i...

Page 12: ...SNMP adapter The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of control ling and management at the manager system disposal Th...

Page 13: ...ing C characteristic for circuit breaker Regardingthesize theywillbeasminimumtothecurrentsstated in the nameplate of each UPS In the nameplate of the equipment there are only printed the nominal curre...

Page 14: ...only 1 metallic piece and bolt to joint the battery module with the equipment on tower format Once the reception is finished it is advisable to pack the UPS and the battery module s again till its com...

Page 15: ...nofthispowerrangeintherackcabinetwhenthemanipula tionsaredonebyhand thebatteryblockhastoberemovedfrom the equipment Proceedasfollowstoremovethebatteryblockorpack basedon one pack for 4 to 6 kVA models...

Page 16: ...r side of the equipment see figure 11 All the instructions relating to connections will detailed later on less those ones regarding the battery connection Therefore this section will only describe the...

Page 17: ...ment vertical There are no supports or stabilizers A A B Fig 7 Vertical tower type assembling 4 2 5 3 Vertical tower type assembling with extended back up time battery module The description of this s...

Page 18: ...8 Model in vertical tower type assembling with extended back up time battery module Regarding the connections of the UPS with the battery module in models up to 6 kVA make the following steps but rea...

Page 19: ...frame of the cabinet by means of the screws B 4 2 5 5 19 rack cabinet assembling with extended back up time battery module This section describes a single equipment with only one battery module see fi...

Page 20: ...seconnectortoconnectitwith anotherbatterymodule Socketforbattery module Wireofbatterymodule Fig 11 Batterymoduleconnectionfor8and10kVAequipments 4 3 Connection Cross cable section used in the power su...

Page 21: ...t the circuit diagram of the particular Backfeed protection for the equipment without bypass line There can be no derivation in the line that goes from the Backfeed protection to the UPS as the safety...

Page 22: ...2 and respect the circuit diagram of the par ticular Backfeedprotection fortheequipmentwithbypassline There can be no derivation in the line that goes from the Backfeed protection to the UPS as the sa...

Page 23: ...the load connected to the respective outlet has to be checked otherwise the protection will be activated and deactivated cyclically and therefore the loads will suffer the consequences For hardwired...

Page 24: ...ting the power supply to the input power block Make sure that all the loads connected to the UPS are only con nectedtotheprotectiveearthbondingterminal Thefactof not restricting the earthing of the lo...

Page 25: ...3 9 2 Installationandparalleloperating 4to10kVA equipmentsonly Communication line COM is a very low voltage circuit of safety Topreservethequality ithastobeinstalledseparate from other lines that have...

Page 26: ...s the difference in the length between the input and output cables of the equipments has to be lower than 10 Input circuit breakers Output circuit breakers Manual bypass UPS nr 1 Input To loads UPS nr...

Page 27: ...other machines or devices through the 5 dry contacts supplied in the terminal strip included in the same card and to each one of them an alarm of the 8 available can be as signed see table 6 Also the...

Page 28: ...of the monitoring software 4 3 12 Considerations before starting up the connected loads It is recommended to charge the batteries for 2 hours as minimum before using the UPS for first time When sup p...

Page 29: ...3 seconds to shut down the inverter The acoustic alarm will beep for 3 sec The equipment will be established on Bypass mode When finishing the previous action there is still voltage at the UPS output...

Page 30: ...hrough the bypass Turn On the output circuit breaker switch of the distribution panel corresponding to the new integrated equipment The complete parallel system will supply output voltage through the...

Page 31: ...tem again 6 Control panel with LCD 6 1 Control panel Fig 20 Control panel view Button Function Description Inverter start up With no AC power supply and battery connected to the equipment press the bu...

Page 32: ...te In ECO mode Blue 65 State In converter mode Blue 71 Warning EPO active Blue 72 Warning On maintain Bypass only models of 4 10 kVA Blue 81 Fault Heatsink over temperature Red 82 Warning Ambient over...

Page 33: ...passwithoutputvoltagescreen Bypass without output voltage The UPS is running on bypass mode without output voltage Fig 25 Bypasswithoutoutputvoltagescreen ECO mode Once the UPS is started up the energ...

Page 34: ...se the UPS could fail Fig 28 Warningscreen Fault When a fault occurs it reveals that some serious problems have happened the UPS will break the output voltage or will transfertobypassandthealarmwillbe...

Page 35: ...ame main screen when pressing the key for more than 1 sec the Structure of the main menu will be displayed see figure 33 Todisplaythedifferentsubmenus pressthekeys or forless than 1 sec considering th...

Page 36: ...see figure 34 Whenpressingthekey formorethan1sec theLCDwillshow the UPS status screen of the main menu structure again Press 1 sec Press o 1 sec Event logger structure menu Main menu structure Press...

Page 37: ...ter When pressing the key for more than 1 sec the LCD panel will display the screen Event log from the main menu structure again Control submenu for 0 7 to 3 kVA models 6 3 4 Measurement submenu When...

Page 38: ...is single or it is parallel and power supply to load s is broken To restore the normal condition the EPO button has to be de activated previously close the circuit again and enter into the ClearEPOsta...

Page 39: ...ctions that could satisfy a special ap plication of the user In case you require any of these special functionalists contact the KESS Support Team to change the standard configuration from fac tory 6...

Page 40: ...as battery has to be charged every 2 months The charging time has to be 12 hours as minimum Under normal conditions the battery lifetime is from 3 to 5 years at20 C Eurobat Ahighertemperaturecancaused...

Page 41: ...ment is too high Check the UPS cooling and ambient temperature of the room 93 Back Feed only 3 kVA On battery mode bypass has voltage Transfer to manual bypass and consult our KESS Support Team Do not...

Page 42: ...9 Troubleshooting guide Warning indications 7 2 3 Troubleshooting guide Other circumstances Circumstance or condition Possible cause Solution Code DescriptionintheLCDpanel 01 Bypass Abnormal Bypass p...

Page 43: ...ered product UPS KESSUPS 91RT series 7 4 Description of the available maintenance and service contracts For the UPS series KESSUPS 91RT additional warranty services are available as an option Also pre...

Page 44: ...62040 3 non linear load Transient recover time of the output voltage with load step 0 100 0 9 Transient recover time of output voltage with load step 20 100 20 6 Frequency With mains present synchron...

Page 45: ...emperature 15 50 C Storage temperature without batteries 20 70 C Operating altitude 1000 m a s l for high altitude correct it according to table 14 Relative humidity 0 95 non condensing Protection deg...

Page 46: ...KESS Power Solutions GmbH Gentzgasse 55 A 1180 Wien T 43 0 1 4704731 0 info kess at www kess at MA_16_03_KESSUPS_91RT_E...

Reviews: