17
KESS Power Solutions Gmbh / www.kess.at / info@kess.at
5.6 SiTE ANd CoNSTRUCTioN
All KESSUPS 92RT UPS are designed to be mounted as a tower (vertical) or rack
(horizontal) for installation in a 19“ cabinet. This applies for single as well as
parallel systems, whether a battery module is existing or not.
follow the instructions indicated in this manual regarding the special features of
your device.
As example, fig. 4 to 6 show illustrations of a device or a battery module. These
illustrations provide help and guidance in the following steps, but the instructions
are not intended to refer to a single model. Although the carried out actions are
in practice always the same for all of them.
for all instructions regarding the connections, refer to chapter 6.
5.6.1 RoTATioN of ThE CoNTRoL PANEL wiTh LCd MoNiToR
To facilitate reading the messages on the
display, it is possible to rotate the control
panel clockwise by 90º (see fig. 4).
Proceed as follows:
fig.4: Rotatable LCd monitor
• Insert your fi ngertips into the recesses of
the plastic housing around the display
and pull outwards.
•
Rotate the control panel with LCd mo-
nitor 90º to the right and put it on its in-
itial position.